AC/DC Power Supply Series APPLICATION NOTE

Similar documents
AC/DC Power Supply Series APPLICATION NOTE

AC/DC Power Supply Series APPLICATION NOTE

AC/DC Power Supply Series APPLICATION NOTE

AC/DC Power Supply Series APPLICATION NOTE

AC/DC Modular Power Supply Series APPLICATION NOTES

AC/DC Modular Power Supply Series APPLICATION NOTES

Medical Safety Approvals (-M versions) Industrial Heavy Duty Terminals. Output Power up to 1500 W. High Power Density - 18W/in 3

Electrical Specifications

ECC100 Series. -40 ºC to +75 ºC Operation. 100 W - Baseplate Cooled. High Efficiency Resonant Topology. Screw Terminals Available.

NLP65 SERIES 75 Watt Open Frame Power Supply Measures: 5.00 x 3.00 x 1.26

Product Specification

These medical power supplies are ideal for monitoring, home health equipment as well as surgical devices.

Matrix Power Company MH xxx-va series Specification Document

Electrical Specifications

Low Profile. 3 Year Warranty

IMA 600 Watts Power Supply Series. for medical and industrial applications. Product datasheet

These power supplies are ideal for telecom, datacom, industrial equipment and other applications.

C B. Models. Models 2MOPP

CCH400 & CCH600 Series

The MDU150 Series provides the same benefits as the MPU150 Series, with nominal 48 volt DC input.

NV-350 / NV Watts Modular power solution With up to 1450W peak rating for 10 seconds

PDAM500 Series 500W Power Supply

IMA 1000 Watts Power Supply Series. for medical and industrial applications. Product data sheet

Electrical Specifications

LB115S 115W Single Output

420 W High Line Output Power. Rugged Industrial Construction. -40 C to +70 C Operation. 5 V Standby. Screw Terminals. SEMI F47 Compliant

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

IMA 400 Watts Power Supply Series. for medical and industrial applications. Product data sheet

Compliance. Safety Approvals USA Canada Europe. Isolation: General. Dimensions. AC Input CN1 Output CN2 Optional CN3. Weight

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

NV-350 / NV W W Modular power supply. Features Benefits Input How To Create A Product Description NV3 Converter NV3 3 NV7 7

Electrical Specifications. Adjustment range Main output ± 5% Total regulation (line and load) ± 2.0% ± 5.0% Turn-on 120 Vac Input 2.0 s max.

Electrical Specifications

CLP0205 Open Frame Power Supply Vac input; 5Vdc output; 200W Output Power; 0.25A stdby

DDP400 and MDP400, SC series, are sealed, full potted, compact, high efficiency, small form factor AC-DC power supplies.

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

NLP40 SERIES 50 Watt Open Frame Power Supply Measures: 4.25 x 2.50 x 1.15

ST-250MAK-05E. Switching Power Supply SPECIFICATION

Sirius F 250 Handbook (Page 1 of 5) Part Number 17133

Asia-Pacific North America Europe, Middle East Bel Power Solutions, Inc. BCD.

Efficiency (typ.) (Range) Load. Output Current Input Current Reflected Ripple

TC-600PD2. Switching Power Supply ( 600W PS2 ATX12V ) SPECIFICATION. Revision: 1.0

TB65 65W Single Output Test and Measurement/Industrial Series

Watts HCP Series

5 x 3 x 0.75 Inches form factor. 275 Watts with Forced Air Cooling. Efficiencies up to 92% Standby Power < 0.5 W

Sirius 250/350 Watts, Single / Multi output AC-DC, modular power solution

The MPB150 product line is approved to the latest international regulatory standards, and displays the CE Mark.

SPECIFICATION. SilverStone OLYMPIA OP1000 Switching Power Supply Active PFC

IP67 DESCRIPTION KEY FEATURES MARKET SEGMENT AND APPLICATIONS TRC ELECTRONICS, INC

Inrush Current (cold start)

POWER. CPS250-M Series. 250 Watt AC-DC Power Supplies. Data Sheet. Total Power: 250 Watts Input Voltage: V # of Outputs: Single

solo Ultra-high efficiency 1U size Xsolo Single Output Power Supply 500W W 2 FEATURES APPLICATIONS INCLUDE

CM4 AC/DC Modular Power Supply Series APPLICATION NOTES

Output Power (W) Industry Leading Performance. Fuse

SPECIFICATION ARP

SFX Form Factor SST-SX650-G SST-SX500-G. The standard SFX power supply benchmark

General. Environmental. EMC & Safety

1500W Programmable Single Output AK V. 48V Rated Current. 31.3A Current Range 100A. 0~31.3A Rated Power 0~100A 1500W

Electrical Specifications VAC/390 VDC, Universal (Derate from 100% at 115VAC to 78% at 90VAC)

This convection-cooled series is designed for use in commercial and industrial environments in temperatures up to 50 C.

American Power Design, Inc.

Electrical Specifications

ECP225-A Series. 225 Watts. AC-DC Power Supplies. Models & Ratings

American Power Design, Inc.

PEAK OUTPUT CURRENT 1. MAP V 4.7V to 5.8V 8A 11A 0.2% ±1% 1% 4.9V to 5.1V PEAK OUTPUT CURRENT 4 LINE REGULATION

Model and Output Power Output Nominal Voltage Package Option Means of Protection Grade. 12 V DC: -US12 Open Frame: -OF. 24 V DC: -US24 U-Chassis: -UC

VOF XX - XXX - X

(typ.) (Range) Parameter Model Min. Typ. Max. Unit

(*) Reference the User Manual or contact the factory for parallel operation between modules plugged into slots 1/2/3/4 and slots 5/6/7/8.

RSP-2000 Series 2000W Single Output Enclosed Power Supplies

All specifications valid at normal input voltage, full load and +25 C after warm-up time unless otherwise stated.

MPDTH***60 Series Adjustable Non-isolated 10-Amp POLA DC/DC Converters

DC/DC Converter 9 to 36Vdc and 18 to 75Vdc input voltage, 20 Watt Output Power; 3.3 to 15Vdc Single Output and ±12Vdc to ±15Vdc Dual Output

TC-750PD8. Switching Power Supply ( PS2 ATX750W 8 0 PLU S ) SPECIFICATION. Revision: 1.0

VMS-300A - XX - XXX - X

10. High-Boost HAM. Design Guide & Applications Manual. Maxi, Mini, Micro Family DC-DC Converters and Configurable Power Supplies

1.2 KW, N+1 REDUNDANT, POWER-FACTOR CORRECTED, 12V FRONT END

AA SERIES (1 x 1 Package) Up to 30 Watt DC-DC Converter

Efficiency (typ.) (Range) Load VDC VDC ma ma(typ.) ma(typ.) μf % MCWI05-12S

10. High Boost HAM. Maxi, Mini, Micro Design Guide Rev 4.9 vicorpower.com

SPECIFICATION SWITCHING POWER SUPPLY BPS-300SP/2U 6-OUTPUT WITH ACTIVE PFC FUNCTION SINGLE POWER 300W BEST POWER SOLUTIONS, INC.

DDP400 SERIES KEY FEATURES DESCRIPTION MARKET SEGMENTS AND APPLICATIONS

Delphi Series H48SC3R325, 85W Half Brick Family DC/DC Power Modules: 48V in, 3.3V/25A out

MB120S 120W Single Output Medical Series

PSU s e r i es

TE90 90W Single Output External Power Test & Measurement/Industrial Series

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

DDP400 and MDP400, SC series, are sealed, full potted, compact, high efficiency, small form factor AC-DC power supplies.

POWER. CPS250-M Series. 250 Watt AC-DC Power Supplies. Data Sheet. Total Power: 250 Watts Input Voltage: V # of Outputs: Single

Model Vnom Power Description Set Point Dynamic Vtrim Imax Remote Power (V) (W) Adjust Range (V) Range (V) (A) Sense Good

SPECIFICATION SWITCHING POWER SUPPLY SINGLE POWER 250W BEST POWER SOLUTIONS, INC. 9F, NO.196-7, SEC.3, TA-TUNG RD SHI CHIH, TAIPEI, TAIWAN, R.O.C.

TBD. Delphi E36SR Series DC/DC Power Modules: 18~60 in, 12V/4A out, 48W FEATURES OPTIONS APPLICATIONS

SPECIFICATION FOR APPROVAL

DATASHEET VXR S SERIES

PRODUCT OVERVIEW. APPLICATIONS: Distributed Power Architectures Mobile telecommunication Industrial applications Battery operated equipment

1500W Single Output Power Supply AK V 100A 0~100A 1500W. 150mVp-p. Adjustment of output current is between 40 ~ 105% of rated output

RSP-1000 series. 1000W Power Supply with Single Output. File Name:RSP-1000-SPEC Sicherheit ID

Datasheet. IC50X, 250 W Single-Output 600 Vin 750 Vin. Rev00

Voltage Adjustment. Load Regulation

NEVO+1200M. 6 x6 x W. 1.2kg DATA SHEET MAIN FEATURES

Transcription:

-350 + -700 AC/DC Power Supply Series APPLICATION NOTE NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 1 of 17

1. INPUT... 3 AC INPUT LINE REQUIREMENTS... 3 2. DC OUTPUT... 3 OUTPUT VOLTAGES... 3 REMOTE SENSE... 3 NO LOAD OPERATION... 5 SERIES/PARALLEL CONNECTION... 5 OUTPUT CHARACTERISTICS... 6 Ripple/Noise... 6 POWER SUPPLY TIMING... 7 PRIMARY OPTION SIGNALS... 8 STANDBY SUPPLY (+V Standby Pin 1, 0V Standby Pin 2)... 8 EN/ES Logic 1 (Primary Option Pin 3)... 8 IN/IS Logic 1 (Primary Option Pin 3)... 8 EN/ES Logic 0 (Primary Option Pin 4)... 9 IN/IS Logic 0 (Primary Option Pin 4)... 9 GLOBAL MODULE GOOD (Primary Option Pins 5 & 6)... 9 AC GOOD SIGNAL (Primary Option Pins 7 & 8)... 10 SECONDARY SIGNALS... 10 CH1 & CH2 OUTPUT GOOD (Module Pins 6 & 2)... 10 MODULE INHIBIT (Module Pin 4)... 11 OVERSHOOT AT TURN ON/OFF... 11 OUTPUT PROTECTION... 12 COOLING REQUIREMENTS... 12 TEMPERATURE DERATING... 13 ELECTROMAGNETIC COMPATIBILITY... 14 Installation for optimum EMC performance... 15 ESD Protection... 15 RELIABILITY... 16 CONNECTION... 17 Input... 17 Output... 17 Signals... 17 Pin Definition - Primary Option... 17 Pin Definition Secondary Signals... 17 MOUNTING... 17 NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 2 of 17

1. INPUT AC INPUT LINE REQUIREMENTS See datasheet for specification of input line requirements (including Input voltage range, Input frequency, Input harmonics, Input current and leakage current) The power supply will automatically recover from AC power loss and shall be capable of startup under full loading at 90VAC. Repetitive ON/OFF cycling of the AC input voltage shall not damage the power supply or cause the input fuse to blow. Input Fuse Not user serviceable. (6.3A in NV-350 and 16A in NV-700), fast acting, high breaking capacity, ceramic fuse. Input Undervoltage The power supply is protected against the application of an input voltage below the minimum specified so that it shall not cause damage to the power supply. 2. DC OUTPUT OUTPUT VOLTAGES All output channels have isolated 0V (except for the two outputs of the DA module that have a common 0V). See the datasheet for full specifications of the output, including adjustment range, output current, remote-sensing capability, regulation, ripple & noise and setting accuracy. The auxiliary supply is an independent, floating, isolated output that is present whilst the ac input is present, irrespective of the state of the other channels (or remote on/off). REMOTE SENSE Remote sensing is provided to compensate for voltage drops in the power connections to the load. Remote sense is available for Output 1 on all modules. Up to 0.5V total line drop can be compensated. The remote sense lines may be connected as follows:- If remote sense is not required, simply do not connect either +sense or sense If remote sense is required, connect -sense and +sense to the corresponding point at the load (see Figure 1 for details) CH1 CH1 CH1 +sense +sense +sense PSU Load PSU Load PSU Load -sense -sense -sense CH1 0V CH1 0V CH1 0V without using remote sense using remote sense Do not sense across an output fuse Figure 1: How to connect power supply to load Note do not connect remote sense across an output fuse NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 3 of 17

Efficiency (%) Efficiency (%) EFFICIENCY The efficiency of the PSU is likely to vary depending on its exact configuration. Figure 2 shows a typical efficiency v output power characteristic of a PSU configured with three 12V single output modules. EFFICIENCY COMPARED TO LOAD 100% 95% 90% 85% 80% 75% 70% 65% 60% 0 50 100 150 200 250 300 350 400 O/P POWER (w) Efficiency (I/P Volts = 115v) Efficiency (I/P Volts = 230v) Figure 2. NV350 Efficiency Chart Power Out Versus Efficiency 90 85 80 75 70 65 60 55 50 Vin 90V Vin 110V Vin 230V Vin 264V 160 200 240 280 320 360 400 440 480 520 560 600 640 680 720 Pout (W) Figure 3. NV700 Efficiency Chart With 1x3.3V output, 1x5V output, 1x12V output and 1x24V output NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 4 of 17

NO LOAD OPERATION No minimum load is required for the power supply to operate within specification. SERIES/PARALLEL CONNECTION It is possible to connect multiple NV-350/NV-700 (or multiple outputs from the same NV-350/NV-700) in series. Do not exceed 160V for the total voltage of outputs connected in series. The outputs connected in series are non-selv (Safety Extra Low Voltage) if the total output voltage + 30% of the highest maximum rated output voltage exceeds 60V (the 30% margin allows for a single fault in any one individual channel). Outputs must not be connected in parallel. NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 5 of 17

OUTPUT CHARACTERISTICS Ripple/Noise Ripple and noise is defined as periodic or random signals over a frequency range of 10Hz to 20MHz. Measurements are to be made according to EIAJ methods. This is done with an 20MHz bandwidth oscilloscope with measurements taken at the end of a 150mm length of a twisted pair of cables, terminated with a 0.1µF ceramic capacitor in parallel with a 120µF electrolytic capacitor as shown in Figure 4. The earth wire of the oscilloscope probe should be as short as possible, winding a link wire around the earth collar of the probe is the preferred method. NV-350 Or NV-700 AC Input Live Neutral Load C1 = 120µF Electrolytic C2 = 100nF Ceramic 15cm twisted pair C1 C2 Scope probe tip Scope probe earth collar Scope Figure 4: RIPPLE AND NOISE MEASUREMENT METHOD NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 6 of 17

POWER SUPPLY TIMING T1 T3 Vac T2 Ch1 95% 10% T4 Ch1 Good AC Good min Typical max Description T1 1.5s Turn on time T2 200ms Output good hold off time T3 16ms Hold up time T4 5ms AC good warning time Figure 5: Output timing diagram NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 7 of 17

PRIMARY OPTION SIGNALS STANDBY SUPPLY (+V Standby Pin 1, 0V Standby Pin 2) 5V / 2A (2.5A Peak) or 12V / 1A (1.2A peak) Supply is isolated from all module outputs and is not inhibited or enabled by any signal/control. EN/ES Logic 1 (Primary Option Pin 3) TTL High level relative to 0V Standby enables the PSU fitted (including fan) with EN or ES type primary option. This signal does not enable the standby supply. If using this input then Pin 4 must be left open circuit. Signal Type Logic Minimum Current Required Maximum voltage (Pin 3 to Standby 0V) TTL Logic. Relative to 0V Standby Active High (High to enable) 0.5mA 5V IN/IS Logic 1 (Primary Option Pin 3) TTL High level relative to 0V Standby inhibits the PSU (including fan) fitted with IN or IS type primary option. This signal does not inhibit the standby supply. If using this input then Pin 4 must be left open circuit. Signal Type Logic Minimum Current Required Maximum voltage (Pin 3 to Standby 0V) TTL Logic. Relative to 0V Standby Active High (High to inhibit) 0.5mA 5V 5V Aux 5V Aux Switch closed PSU operating Switch open PSU inhibited Switch closed PSU inhibited Switch open PSU operating EN/ES Logic 1 Pin 3 IN/IS Logic 1 Pin 3 Figure 6: Example use of EN/ES & IN/IS Logic 1 NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 8 of 17

EN/ES Logic 0 (Primary Option Pin 4) TTL Low level relative to 0V Standby enables the PSU (including fan) fitted with EN or ES type primary option. This signal does not enable the standby supply. If using this input then Pin 3 must be left open circuit. Signal Type Logic Minimum Current to sink Maximum voltage (Pin 4 to Standby 0V) TTL Logic. Relative to 0V Standby Active Low (Low to Enable) 0.5mA 5V IN/IS Logic 0 (Primary Option Pin 4) TTL Low level relative to 0V Standby inhibits the PSU (including fan) fitted with IN or IS type primary option. This signal does not inhibit the standby supply. If using this input then Pin 3 must be left open circuit. Signal Type Logic Minimum Current to sink Maximum voltage (Pin 4 to Standby 0V) TTL Logic. Relative to 0V Standby Active Low (Low to Inhibit) 0.5mA 5V EN/ES Logic 0 Pin 4 Switch closed PSU operating Switch open PSU inhibited IN/IS Logic 0 Pin 4 Switch closed PSU inhibited Switch open PSU operating 0V Standby Pin 2 0V Standby Pin 2 Figure 7: Example use of EN/ES & IN/IS Logic 0 GLOBAL MODULE GOOD (Primary Option Pins 5 & 6) (Available on EN/IN type Primary options only) This is an un-committed opto-coupler which turns on 200mS (typically) after all outputs are within 95% of nominal. The signal turns off if any output drops below 95% of nominal. The signal also turns off if an AC Fail condition is detected, in which case it provides 5mS (min) warning before any output is likely to drop below 95% of nominal. Do not connect on ES and IS type primary options. Signal Type Maximum Current Maximum voltage (collector to 0V) Logic low (when signal is turned on) Uncommitted opto-coupler. 5mA 30V <0.4V when sinking 5mA Global Module Good collector pin 5 Global Module Good emitter pin 6 External 5v Aux supply Logic 1 = DC Good Logic 0 = Global DC Not Good 4k7Ω resistor External Aux 0V Figure 8: Example use of Global Module Good NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 9 of 17

AC GOOD SIGNAL (Primary Option Pins 7 & 8) The AC Good signal is an uncommitted opto-coupler which turns on 5ms (typically) after ac is good and off 5ms (typically) before any channel falls below 95% of nominal. It is delayed after startup to ensure that sufficient primary side energy is stored by the power supply for continuous power operation within the specified hold-up time. When the input power is removed the AC Good Signal will go to an open circuit state. The specification for the Power Good Signal is shown below Signal Type Maximum Current Maximum voltage (collector to 0V) Logic low (when signal is turned on) Uncommitted opto-coupler. 5mA 30V <0.4V when sinking 5mA AC good collector pin 7 External 5v Aux supply AC good emitter pin 8 Logic 1 = AC Good Logic 0 = AC Fail 4k7Ω resistor External Aux 0V Figure 9: Example use of AC Good SECONDARY SIGNALS CH1 & CH2 OUTPUT GOOD (Module Pins 6 & 2) The Output Good signal is an open collector signal output which is turned on to indicate that output is operating within its regulation limits. When the Output falls to below 85% of nominal, the Output Good Signal will go to an open circuit state. The specifications for the Output Good Signal are contained below Signal Type Maximum Current Maximum voltage (collector to 0V) Logic low (when signal is turned on) Open collector output. Emitter connected to 0V of appropriate channel. 5mA 30V <0.4V when sinking 5mA Aux supply 4k7Ω Pull-up resistor Output Good Logic 0 = Output Good Logic 1 = Output Not Good Figure 10: Example use of Output Good NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 10 of 17

MODULE INHIBIT (Module Pin 4) TTL Logic high (relative to 0V of Channel 1) inhibits the output (both outputs for dual modules) of the module. Signal Type TTL Logic. Relative to CH1 0V. Minimum Current to source 5mA Maximum voltage (Pin 4 to 0V) 5V External 5V Module Inhibit Pin 4 Switch closed PSU inhibited Switch open PSU operating Channel 1 0V Pin 5 Figure 11: Example use of Module Inhibit CHANNEL 2 ON/OFF (Module Pin 3) (Only for dual output modules. Do not connect on single output modules) TTL Logic low (relative to 0V of Channel 2) inhibits output 2 of the module. Signal Type TTL Logic. Relative to CH1 0V. Minimum Current to sink 5mA Maximum voltage (Pin 3 to 0V) 5V External 0V Channel 2 on/off Pin 3 Channel 2 0V Pin 1 Switch closed PSU inhibited Switch open PSU operating Figure 12: Example use of Channel 2 on/off OVERSHOOT AT TURN ON/OFF The output voltage overshoot upon the application or removal of the input mains voltage shall be less than 10% above the nominal voltage. No voltage of opposite polarity shall be present on any output during turn on or turn off. NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 11 of 17

OUTPUT PROTECTION Over temperature protection If the NV-350/NV-700 is operated without adequate cooling, it will cause an over temperature condition and the PSU will shut down. To restart the PSU, remove the ac supply allow the unit to cool down and then reapply the ac supply. Over voltage protection An overvoltage on any of the output channels will cause that module to shutdown. To restart the module, remove the ac supply for 2 seconds and then reapply. Short-Circuit Protection A short circuit is defined as an impedance of <0.06Ω placed between the DC return and any output. A short circuit will cause no damage to the power supply and will cause it to shutdown. After removal of the short circuit, the PSU will resume normal operation. Overcurrent Protection Overload currents applied to each output will cause the output to trip without damaging the module. COOLING REQUIREMENTS For full details of the cooling requirements, please refer to the NV700 Handbook and NV350 Handbook documents available on our website. Natural Convection The power supply is not designed to operate without forced air cooling. NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 12 of 17

Power (W) Power (W) TEMPERATURE DERATING NV-350/NV-700 achieves full power output up to 50 C ambient temperature. Above this temperature, the total output power (and individual output currents) must be derated by 2.5%/ C up to 70 C. See diagram below. 400 350 300 250 200 150 100 50 0 0 10 20 30 40 50 60 70 80 Temp C Figure 13: NV-350 Thermal Derating 1200 1000 Input below 150Vac Input above 150Vac 800 600 400 200 0 0 10 20 30 40 50 60 70 80 Temp C Figure 14: NV-700 Thermal Derating NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 13 of 17

ELECTROMAGNETIC COMPATIBILITY Figure 15: Sample plot of NV350 Measured at 230V input, 3V3B@35A; 24B@4A; 3V3/12DB@15/4A Figure 16: Sample plot of NV700 Measured at 230V input NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 14 of 17

Installation for optimum EMC performance Mounting All equipment should be mounted inside an earthed metal box. If this is not possible then use an earthed metal plane to mount the power supply and load. Cables All cables (both ac input and dc output) should be run as close as possible to the earthed metal box/plane. AC input cable should be twisted group laid as flat to the earthed metal box/plane as possible. All output cables should be routed as far away from input cables as possible. If the input and output cables must be run close to each other then screen one or other (or ideally both). The positive and negative supply cables should be twisted together. The remote sense wires (if used) should be twisted together and run alongside their related supply cables. All cable run loops should be kept as small as possible (this should be implemented in PCB design also). Connecting between boxes If cables must be connected between equipment boxes then at the closest possible point to the port where the cables exit the 1 st enclosure connect 100nF decoupling Y caps (between the output and earth). Note that these capacitors must be rated at the working voltage. Ideally these capacitors should be between all signal cables which have to connect between boxes although this may not be practical if fast switching [digital] signals are involved (if this is the case then smaller value Y capacitors should be used). Earth star point If the power supply is supplied without an IEC inlet then where the ac supply enters the equipment, this should be taken to a star point chassis mounted earth point as close as possible to the ac inlet. All other earth points should be taken back to this point only. If the power supply is supplied fitted with an IEC inlet then a star point should be created as near as possible to the mounting screw closest to the inlet side of the power supply. (Note compliance with EN609050 practices that require own star point washer and nut). ESD Protection Where signal or control ports are connected to a user accessible panel (for example PSU inhibit to a switch, module good to an indicator circuit, etc), these ports must be protected from electrostatic discharges. This can be done by selecting suitable panel controls or by fitting ESD suppression devices to the connections on the panel NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 15 of 17

RELIABILITY Calculated using Telcordia Issue 1, Case 3 Operating continuously, Ground Benign / Ground Controlled Environment. FPMH (Failures per million hours) Temperature 0 C 30 C 40 C 50 C 60 C 70 C 350W Converter 0.312 0.763 1.035 1.416 1.959 2.742 700W Converter 0.309 0.787 1.090 1.522 2.146 3.050 B Module 0.254 0.614 0.847 1.192 1.717 2.519 FEP Module 0.402 0.831 1.109 1.526 2.167 3.166 C Module 0.256 0.600 0.823 1.154 1.658 2.440 DB Module 0.441 1.054 1.443 2.014 2.870 4.178 Primary Option 0.076 0.254 0.405 0.664 1.106 1.880 DA Module 0.136 0.365 0.531 0.790 1.197 1.837 NV-350 Fan 2.396 1.941 3.067 4.845 7.656 12.096 NV-700 Fans 4.792 3.882 6.133 9.691 15.311 24.192 To calculate MTBF, sum the FPMH for all component parts at the required temperature. This gives total failures per million hours (FPMH). Convert this to MTBF by dividing 1000000 by the FPMH. For example:- Require the MTBF for NV3SSS 5B 12/12DB at 30 C 350W Converter 0.763 B module 0.614 DB module 1.054 Fan 1.941 Total FPMH 4.372 Therefore MTBF = 1000000 / 4.372 = 228728 hours (228k hours) Require the MTBF for NV7CSSES5V 12C at 50 C 700W Converter 1.522 Primary Option 0.664 C module 1.154 Total FPMH 3.340 Therefore MTBF = 1000000 / 3.340 = 299401 hours (299k hours) NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 16 of 17

CONNECTION Input Input is via IEC320 connector (if specified) or 3 x 6-32 screws with 8.25mm spacing between screw head centres. The screw head diameter is 6.6mm. Maximum Torque setting is 0.8Nm. Output The screws used for single output modules and channel 1 of dual channel modules are 2 x M4. Maximum torque setting is 1.3Nm. The screws used for Channel 2 of dual channel modules are 2 x M3. Maximum torque setting is 0.6Nm. Signals The signals connector (both primary option and module signals) should be connected using Molex Part Numbers Housing: 51110-0860 Crimp pin: 50394 Hand Crimp Tool: 69008-0959 or equivalent part from alternative manufacturer 25 housings and 200 crimps are available as a single part number from TDK-Lambda. The part number is 94158. Pin Definition - Primary Option Pin Function 1 +V standby 2 0V Standby 3 EN/ES & IN/IS Logic 1 4 EN/ES & IN/IS Logic 0 5 Global Module Good Collector 6 Global Module Good Emitter 7 AC good Collector 8 AC good Emitter See SIGNALS section of Application note for use of these signals. Pin Definition Secondary Signals Pin Channel Function 1 2 0V Only on twin modules 2 2 Output Good Only on twin modules 3 2 On/Off Only on twin modules 4 Module Inhibit 5 1 0V 6 1 Output Good 7 1 Remote Sense - 8 1 Remote Sense + See SIGNALS section of Application note for use of these signals. MOUNTING Refer to the handbook for permitted mounting orientation. NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 17 of 17