Satec Ltd. 3-Phase Power Meter PM135

Similar documents
Test Report According to EN V1.9.2; EN V Starcom GPS Systems Ltd.

DATE: 10 February 2010 I.T.L. (PRODUCT TESTING) LTD. CE EMC Test Report. for. MAXIMUM Security (1984) Ltd. Equipment under test:

DATE: 25 September 2012 I.T.L. (PRODUCT TESTING) LTD. FCC EMC Test Report. (Equipment Authorization Under FCC Verification Process) for

CERTIFICATE OF COMPLIANCE

Galcon Galil Control

FCC Radio Test Report

FCC Radio Test Report. Orpak Systems Ltd.

2620 Modular Measurement and Control System

EMC TEST REPORT For MPP SOLAR INC Inverter/ Charger Model Number : PIP 4048HS

Test Report. Guangdong East Power Co., Ltd. Fully Automatic AC Voltage Regulator. Brand Name:

TEST SUMMARY. Prüfbericht - Nr.: Test Report No.: Seite 2 von 25. Page 2 of 25

TEST REPORT... 1 CONTENT...

FCC Part 15 Subpart B

Test Report GUANGDONG EAST POWER CO., LTD

Advanced Compliance Solutions, Inc FAU Blvd, Suite 310 Boca Raton, Florida (561)

TEST SUMMARY. Prüfbericht - Nr.: Test Report No.: Seite 2 von 27. Page 2 of 27

C-Tick EMC TEST REPORT. For. AC/DC Switching Power Supply

EN 55015: 2013 Clause Pass. EN 55015: 2013 Clause Pass. EN 55015: 2013 Clause Pass

EMC standards. Presented by: Karim Loukil & Kaïs Siala

Page 1 of 20 No.: HM TEST REPORT FCC PART 15 SUBPART C CERTIFICATION REPORT FOR LOW POWER TRANSMITTER. TEST REPORT No.

L.S. Compliance, Inc. W66 N220 Commerce Court Cedarburg, WI

EMC TEST REPORT for LEDELS LIGHTING CO., LTD. LED module Model No. : LL-F12T4815X6B

EMC TEST REPORT for : DONGGUAN EVER DEVELOPMENT ELECTRONIC CO., Electronic calculator Model No.: KF15758

King Pigeon Communication Co., Limited

EMC Testing Report. Dual-120CS. Yuan Hsun Electric Co., Ltd.

Harmonic Current emission EN :2014 Class A Pass. Voltage Fluctuation and Flicker EN :2013 Clause 5 Pass

Sunlight Supply, Inc.

Report for Excelsys EMC Measurements for 4Xgen Purchase Order: Project Number EMT07J026 Rev. B

STC Test Report. Date : Page 1 of 13 No. : HM161169

Discontinuous Disturbance (Click) EN :2006+A1:2009+A2:2011 Clause N/A** Radiated Emission, 30MHz to 1000MHz

EN :2007+A1:2011 Electromagnetic compatibility Emission standard for residential, commercial and light-industrial environments

Certificate of Test AND KEEPS ALL REQUIREMENTS ACCORDING THE FOLLOWING REGULATIONS IEC :2001 IEC :2007

EMC Test Report. Report Number: M030826

Overview of EMC Regulations and Testing. Prof. Tzong-Lin Wu Department of Electrical Engineering National Taiwan University

EMC Bayswater Pty Ltd. EMC COMPLIANCE REPORT In accordance with: AS/NZS CISPR 15: Indice Ecotech Pty Ltd. 14W LED Downlight

STC Test Report. The Hong Kong Standards and Testing Centre Ltd.

FCC 47 CFR PART 15 SUBPART B

C E R T I F I C A T I O N

C E R T I F I C A T I O N

FCC CLASS B COMPLIANCE REPORT (DoC)

Guangdong East Power Co., Ltd. Uninterruptible Power Systems

Test and Measurement for EMC

No. 620 HuaYuan Commercial Center, No. 347 XiXiang Road,XiXiang Town, Bao An District, ShenZhen City Tel : Fax:

EN61326 EMC COMPLIANCE REPORT on the LP Series Ultrasonic Transmitter Remote Amplifier and Transducer for Hawk Measurement Systems Pty Ltd

ITUNER NETWORKS CORPORATION EMC REPORT Fremont Blvd. Fremont, CA

EMC TEST REPORT. For. Boardcon Technology Limited. MINI9G45 Computer on Module. Model No. : MINI9G45

EN 55022: 2010+AC:2011 Clause 6.1 Pass. Harmonic Current EN :2006+A1:2009+A2:2009 Class A N/A

Page 1 of 19 No.: HM TEST REPORT FCC PART 15 SUBPART C CERTIFICATION REPORT FOR LOW POWER TRANSMITTER. TEST REPORT No.

TEST SUMMARY Seite 2 von 19. Prüfbericht - Nr.: Test Report No.:

Shenzhen Toby Technology Co., Ltd. EMC Test Report. Report No.: TB-EMC Page: 1 of 20

TEST SUMMARY Seite 2 von 27. Prüfbericht - Nr.: Test Report No HARMONICS ON AC MAINS RESULT: Passed

AUSTRALIA TEST REPORT For. KLM Lighting Co., Limited. LED Down Light. Model No.: KLM-HP30WSN

FCC Test Report. Report No.: AGC FE08. Attestation of Global Compliance (Shenzhen) Co., Ltd

EMC Test report for LED Panel Light Models , , , , ,

TRANSMITTER MODEL: KAS-2030M

C E R T I F I C A T I O N

EMC TEST REPORT for SHENZHEN MUST ENERGY TECHNOLOGY CO., LTD

1 SUMMARY OF STANDARDS AND RESULTS

Page: 1 of 20 EMC TEST REPORT EN55024:1998+A2:2003

EMC COMPLIANCE TEST REPORT

FCC PART 15, CLASS B MEASUREMENT AND TEST REPORT. NanJing JingZe Lighting Technology Co.,Ltd

EN v1.2.1 ( ) TEST REPORT FOR n 1X2 PCIe MINICARD TRANSCEIVER MODEL NUMBER: AR5B91 REPORT NUMBER: 08U

EMC TEST REPORT For INNOKIN TECHNOLOGY CO., LIMITED. ITaste vv. Model No.: ITaste vv

STC Test Report. Date: Page 2 of 25 No.: MH The Hong Kong Standards and Testing Centre Ltd.

EMC VERIFICATION SUMMARY Report No.: SZHH

CENTRE OF TESTING SERVICE INTERNATIONAL

EMC TEST REPORT. For. Switching Mode Power Adaptor. Model No.: 9W/14.4V/EU(18V/1.0A), 19W/14.4V/EU(12V/1.5A)

TEST REPORT To: - ABO ELECTRONICS (SHENZHEN) CO., LTD Block B3, Haocheng Industrial Park, Hexiu West Rd, Heping Village, Fuyong, Baoan, Shenzhen

EMC TEST REPORT. for. Coliy Technology Co.,Ltd. Fluxgate Gaussmeter

BS EN TESTS ON THE IT TOXIC GAS DETECTOR MODULE

EMC TEST REPORT for Repel-it. REPEL-IT ULTRASONIC PEST REPELLER Model No. : REPEL-IT/UPR/AN-B019

C E R T I F I C A T I O N

Report for Excelsys EMC Measurements for 6Xgen Purchase Order: by Project Number EMT08J027

TABLE OF CONTENTS. Report Reference No.: GST E Issued: Oct. 21, 2011 Revised: None. Page 2 of 46

TEST REPORT To: - ABO ELECTRONICS (SHENZHEN) CO., LTD Block B3, Haocheng Industrial Park, Hexiu West Rd, Heping Village, Fuyong, Baoan, Shenzhen

EMC Test Report FATEK AUTOMATION CORP. FATEK. FBs-TBOX N/A

A) Documentation Page(s) Test report 1-17 Directory 2 Test Regulations 3 General Remarks and Summary 17 Test-setups (Photos) 18-23

Test Certificate A sample of the following product received on May 13, 2011 and tested on May 13, 18 and 19, 2011 complied with the requirements of,

PARTIAL RADIATED EMISSIONS AND RADIATED IMMUNITY TEST REPORT

Nemko-CCL, Inc West Alexander Street Salt Lake City, UT

FCC Verification TEST REPORT

TABLE OF CONTENTS. 6. PHOTOGRAPH Photo of Conducted Emission Measurement Photo of Radiation Emission Measurement...

Compliance Engineering Ireland Ltd

f02 January 11, TÜV Rheinland Nederland B.V. P.O. Box AA Leek (NL) Eiberkamp VT Leek (NL)

1 Introduction Test Specification Environment Relevant standards Emissions Immunity...

EMC TEST REPORT. Report No.: CE10-LIE040101E

Test Report No

Itron, Inc. TEST REPORT FOR. RF Telemetry Device Model: CCU100. Tested To The Following Standards:

FCC & RSS-216 (Class II Permissive Change) Wireless Power Transfer Report. for A Acer Incorporated

APPLICATION FOR VERIFICATION On Behalf of Carewell Electric Technology (Zhongshan) Co., Ltd. REMOTE CONTROL Model No.: AC8 FCC ID: 2AAZPAC8

TEST REPORT CONCERNING THE COMPLIANCE OF PART 15 JBP

CE TEST CERTIFICATION

FCC TEST REPORT On Behalf of GZTOD.CO., LTD The Multifunctional Platooninsert Model No.: YA30WSL-6AU6U

Electromagnetic Compatibility Test Report FCC test results of an automatic dog brush, model EUT: Type 1 AC/DC adaptor: SYS W2E

Contents. Report No.: EMC-CE-2114 Page: 2 of 39

CTS (NINGBO) TESTING SERVICE TECHNOLOGY INTERNATIONAL OPERATE ACCORDING TO ISO/IEC EMC TEST REPORT

ETSI EN V2.2.0 ( ) ETSI EN V2.1.1 ( ) TEST REPORT. United GULF GATE Co.

Nemko Canada Inc., 303 River Road, R.R. 5, Ottawa, Ontario, Canada, K1V 1H2

APPLICATION FOR EMC DIRECTIVE. On Behalf of. Shenzhen Qinhan Lighting Co., Ltd. led flood light. Trade Name:

Medtronic MiniMed TEST REPORT FOR. GST3 Glucose Sensor Transmitter, MMT-7763A. Tested To The Following Standards:

Transcription:

DATE: 07 August 2012 I.T.L. (PRODUCT TESTING) LTD. CE EMC Test Report for Satec Ltd. Equipment under test: 3-Phase Power Meter PM135 Written by: Y. Raz, Documentation Approved by: Y. Mordukhovitch, Test Engineer Approved by: I. Raz, EMC Laboratory Manager This report must not be reproduced, except in full, without the written permission of I.T.L. (Product Testing) Ltd. This report relates only to items tested. Test Report E115780.00 Satec Ltd. Page 1 of 44

TABLE OF CONTENTS 1. GENERAL INFORMATION ------------------------------------------------------------------------------- 4 1.1 Administrative Information... 4 1.2 Abbreviations and Symbols... 5 1.3 List of Accreditations... 6 2. APPLICABLE DOCUMENTS ---------------------------------------------------------------------------- 7 3. TEST SITE DESCRIPTION ------------------------------------------------------------------------------- 8 3.1 Location:... 8 3.2 Open Site:... 8 3.3 Ground Plane:... 8 3.4 Antenna Mast:... 8 3.5 Turntable:... 8 3.6 EMI Receiver:... 8 3.7 E.U.T. Support:... 8 3.8 Test Equipment:... 8 4. SUMMARY OF TEST RESULTS ------------------------------------------------------------------------ 9 5. EQUIPMENT UNDER TEST (E.U.T.) DESCRIPTION -------------------------------------------- 11 6. LIST OF TEST EQUIPMENT ---------------------------------------------------------------------------- 12 6.1 Immunity Tests... 12 6.2 Emission Tests... 13 7. E.U.T. PERFORMANCE VERIFICATION ------------------------------------------------------------ 14 7.1 Mode of Operation... 14 7.2 Monitoring of E.U.T.... 15 7.3 Definition of Failure... 15 8. CONDUCTED EMISSION -------------------------------------------------------------------------------- 16 8.1 Test Specification... 16 8.2 Test Procedure... 16 8.3 Test Results... 16 9. RADIATED EMISSION ------------------------------------------------------------------------------------ 21 9.1 Test Specification... 21 9.2 Test Procedure... 21 9.3 Test Results... 21 10. IMMUNITY TO ELECTROSTATIC DISCHARGE -------------------------------------------------- 23 10.1 Test Specification... 23 10.2 Test Procedure... 23 10.3 Test Results... 23 11. IMMUNITY TO RADIATED FIELD --------------------------------------------------------------------- 26 11.1 Test Specification... 26 11.2 Test Procedure... 26 11.3 Test Results... 26 12. IMMUNITY TO ELECTRICAL FAST TRANSIENT / BURST ------------------------------------ 28 12.1 Test Specification... 28 12.2 Test Procedure... 28 12.3 Test Results... 28 13. IMMUNITY TO CONDUCTIVE SURGES ------------------------------------------------------------- 30 13.1 Test Specification... 30 13.2 Test Procedure... 30 13.3 Test Results... 30 Test Report E115780.00 Satec Ltd. Page 2 of 44

14. IMMUNITY TO MAGNETIC FIELD -------------------------------------------------------------------- 33 14.1 Test Specification... 33 14.2 Test Procedure... 33 14.3 Test Results... 33 15. SET UP PHOTOGRAPHS ------------------------------------------------------------------------------- 35 16. SIGNATURES OF THE E.U.T'S TEST ENGINEERS --------------------------------------------- 40 17. APPENDIX A - CORRECTION FACTORS ----------------------------------------------------------- 41 17.1 Correction factors for CABLE... 41 17.2 Correction factors for Amplifier 8447F 30M-1.3G GAIN... 42 17.3 Correction factors for Bilog ANTENNA... 43 18. APPENDIX B - MEASUREMENT UNCERTAINTY ------------------------------------------------ 44 18.1 Radiated Emission... 44 18.2 Conducted Emission... 44 Test Report E115780.00 Satec Ltd. Page 3 of 44

1. General Information 1.1 Administrative Information Manufacturer: Satec Ltd. Manufacturer's Address: Har Hotzvim Science Based Industrial Park P.O.B. 45022 Jerusalem 91450 Israel Tel: +972-2-541-1000 Fax: +972-2-581-2371 Manufacturer's Representative: Ilya Yakobi Equipment Under Test (E.U.T): 3-Phase Power Meter Equipment Model No.: PM135 Equipment Serial No.: 928504 Date of Receipt of E.U.T: 04.03.12 Start of Test: 04.03.12 End of Test: 05.03.12 Test Laboratory Location: I.T.L (Product Testing) Ltd. 1 Batsheva St., Lod ISRAEL 71100 Test Specifications: See Section 2 (The tests listed in this section were performed according to the customer s request). Test Report E115780.00 Satec Ltd. Page 4 of 44

1.2 Abbreviations and Symbols The following abbreviations and symbols are applicable to this test report: A/m AC AM ARA Aux Avg CDN cm db dbm dbµv dbµv/m DC EFT/B EMC ESD E.U.T. GHz HP Hz khz kv LED LISN m mhn MHz msec N/A per QP PC RF RE sec V V/m VRMS ampere per meter alternating current amplitude modulation Antenna Research Associates auxiliary average coupling-decoupling network centimeter decibel decibel referred to one milliwatt decibel referred to one microvolt decibel referred to one microvolt per meter direct current electrical fast transient/burst electromagnetic compatibility electrostatic discharge equipment under test gigahertz Hewlett Packard Hertz kilohertz kilovolt light emitting diode line impedance stabilization network meter millihenry megahertz millisecond not applicable period quasi-peak personal computer radio frequency radiated emission second volt volt per meter volts root mean square Test Report E115780.00 Satec Ltd. Page 5 of 44

1.3 List of Accreditations The EMC laboratory of I.T.L. is accredited by the following bodies: 1. The American Association for Laboratory Accreditation (A2LA) (U.S.A.), Certificate No. 1152.01. 2. The Federal Communications Commission (FCC) (U.S.A.), Registration No. 861911. 3. The Israel Ministry of the Environment (Israel), Registration No. 1104/01. 4. The Voluntary Control Council for Interference by Information Technology Equipment (VCCI) (Japan), Registration Numbers: C-3006, R-2729, T-1877, G-245. 5. Industry Canada (Canada), IC File No.: 46405-4025; Site No. IC 4025A-1. 6. TUV Product Services, England, ASLLAS No. 97201. I.T.L. Product Testing Ltd. is accredited by the American association for Laboratory Accreditation (A2LA) and the results shown in this test report have been determined in accordance with I.T.L.'s terms of accreditation unless stated otherwise in the report. Test Report E115780.00 Satec Ltd. Page 6 of 44

2. Applicable Documents 2.1 EMC Directive: 2004 DIRECTIVE 2004/108/EC OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 15 December 2004 on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89/336/EEC 2.2 CISPR 22: 2008 Information technology equipment Radio disturbance characteristics Limits and methods of measurement 2.3 EN 61000-6-2: 2005 Electromagnetic Compatibility (EMC)-Part 6-2: Generic Standards Immunity for industrial environments 2.4 IEC 61000-4-2: 2008 Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques; Section 2: Electrostatic discharge immunity test: Basic EMC publication. 2.5 IEC 61000-4-3: 2006 Amendment A1: 2007 Amendment A2: 2010 2.6 IEC 61000-4-4: 2004 A1: 2010 Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques; Section 3: Radiated, radio frequency, electromagnetic field immunity test. Electromagnetic compatibility (EMC), Part 4. Testing and measurement techniques; Electrical fast transient /burst immunity test, Basic EMC Publication. 2.7 IEC 61000-4-5: 2005 Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques; Section 5: Surge immunity test. 2.8 IEC 61000-4-8: 2009 Electromagnetic compatibility (EMC), Part 4: Testing and measurement techniques, Section 8. Power frequency magnetic field immunity test. Test Report E115780.00 Satec Ltd. Page 7 of 44

3. Test Site Description 3.1 Location: The Electromagnetic Compatibility Test Facility of I.T.L. (Product testing) Ltd. Is located at Telrad Industrial Park, Lod, 71100 Israel. Telephone: +972-8-9153100 Fax: +972-8-9153101 3.2 Open Site: The OATS is located on a one floor-building roof. The OATS consists of 3 meter and 10 meter ranges, using a 21.5m X 8.5m solid metal ground plane, a remote controlled turntable and an antenna mast. 3.3 Ground Plane: The ground plane is made from steel plates, which are welded continuously together. The Ground plane is lies and welded on welded steel construction with vias to allow for water drainage. All the power, control, and signal lines to the turntable and the 3 m and 10m antenna mast outlets are routed in shielded conduits under the plane to the control building. 3.4 Antenna Mast: ETS model 2070-2. The antenna position and polarization are remote controlled via Fiber Optical Link using ETS/EMCO Dual Controller Type 2090. The antenna position is adjustable between 1-4 meters. Pressurized air is used to power changing the polarity of the antenna. 3.5 Turntable: ETS model 2087 series. The position of the turntable is remote-controlled via Fiber Optic Link, using ETS/EMCO Dual Controller Type 2090. The turntable is mounted in a pit and its surface is flush with the Open Site Ground Plane. Brushes near the periphery of the turntable ensure good conductive connection to the ground plane. The Turntable maximum load is 1250 Kg. 3.6 EMI Receiver: Type HP8542E, including HP85420E R.F. filter manufactured by Hewlett-Packard, being in full compliance with CISPR 16 requirements. 3.7 E.U.T. Support: Table mounted E.U.T.s are supported during testing on 80 cm high all-wooden tables (no metal nails or screws). 3.8 Test Equipment: See details in Section 6. Test Report E115780.00 Satec Ltd. Page 8 of 44

4. Summary of Test Results Test Conducted Emissions CISPR 22: 2008 Class A Results The E.U.T met the performance requirements of the specification. The margin between the emission levels and the specification limit is, in the worst case, 0.7 db for the phase line at 0.64 MHz and 0.6 db at 0.64 MHz for the neutral line. Radiated Emissions CISPR 22: 2008 Class A The E.U.T met the performance requirements of the specification. The margin between the emission level and the specification limit is 14.0 db in the worst case at the frequency of 111.48 MHz, vertical polarization. ESD IEC 61000-4-2: 2008 Air Discharge, 8kV Contact Discharge, 4kV The E.U.T met the performance requirements of the specification. Radiated Immunity IEC 61000-4-3: 2006 + Amendment A1: 2007 Amendment A2: 2010 (80-2700 MHz) 10 V/m, 80% A.M. by 1kHz The E.U.T met the performance requirements of the specification. EFT/B IEC 61000-4-4: 2004 + A1: 2010 2kV Power lines 1kV Signal lines The E.U.T met the performance requirements of the specification. Test Report E115780.00 Satec Ltd. Page 9 of 44

Summary of Test Results (cont d.) Test Conductive Surges IEC 61000-4-5: 2005 Differential mode; 1kV Results The E.U.T met the performance requirements of the specification. Immunity to Magnetic Field IEC 61000-4-8: 2009 30 A/m, 50Hz The E.U.T met the performance requirements of the specification. Test Report E115780.00 Satec Ltd. Page 10 of 44

5. Equipment Under Test (E.U.T.) Description The E.U.T. is a compact panel mounted 3 phase AC electronic microprocessor-based power meter for measurement, monitoring, and management of electrical parameters, presenting results in visual form on 3-row 7-segment LED display. It provides RS-485 interface for remote data reading and setup. The PM130EH PLUS is intended for use in industrial environments. The E.U.T. is powered from single phase, 85-265VAC. Test Report E115780.00 Satec Ltd. Page 11 of 44

6. List of Test Equipment 6.1 Immunity Tests Equipment indicated below by an X used in Tests IEC 61000-4:-2,-3,-4,-5,-6,-8,-11. Test equipment calibration is in accordance with ITL Q.A. Procedure PM 110, "Calibration Control Procedure", which complies with ISO 9002 and ISO/IEC Guide 17025. Instrument Manuf. Model Serial No. Used in Test IEC 61000-4: -2-3 -4-5 -6-8 -11 Transient Generator KeyTek CEMASTER 9612436 X ESD Simulator CDI ESD 2000i 426 X Isotropic Field Probe AR EP-2080 23190 X RF Amplifier AR 100W1000M1 19842 X Isotropic Field Monitor AR FM-2000 19719 X Biconilog Antenna EMCO 3142B 1078 X Horn Antenna A.H. systems SAS 200/571 199 X RF Amplifier OPHIR 5303081 1002 X RF Amplifier IFI SMX100 1194-4537 X RF Amplifier IFI M100 M612-0208 X Signal Generator HP 8657A 2849U01094 X BulkF Current Probe FCC F-120-9 105 CDN FCC FCC-801-M3-16A 9962 Transient Wave- form Monitor CDI TWM-100 3233 Phase Control Amplifier CDI PCA-1000 3217 Single Phase Isolated Backfilter CDI CDI-1kVA 3221 Surge Generator CDI CDI-1000i 3153 1.2/50; 8/20usec AC Surge Unit KeyTek E551 9512398 Surge Generator EM TEST UCS 500-M 1198-45 X AC Power Source EM TEST UCS 500-M 1198-45 Current Generator FCC F-1000-4-8-125A 9838 X Magnetic Loop FCC F-1000-4-8/9/10- L-1M 9836 X Test Report E115780.00 Satec Ltd. Page 12 of 44

6.2 Emission Tests The equipment indicated below by an X was used for testing Conducted Emission (CE), Radiated Emission (RE), and IEC 61000-3-2;3 Test equipment calibration is in accordance with ITL Q.A. Procedure PM 110 "Calibration Control Procedure", which complies with ISO 9002 and ISO/IEC Guide 17025. Used in Test Instrument Manufacturer Model Serial No. CE RE -2-3 LISN EMCO 3810/2BR 1297 X Transient Limiter HP 11947A 3107A03041 X RF Amplifier HP 8447F 3113A06386 X Current Probe FCC F51 163 EMI Receiver Rohde & Schwarz ESCI7 100724 X EMI Receiver HP 8546A 3650A00365 X Receiver RF Filter Section HP 85460A 3650A00365 X EMC Analyzer HP HP8593 3536A00120 X Biconilog Antenna EMCO 3142B 1250 X Horn Antenna ETS 3115 6142 Antenna Mast ETS 2070-2 ETS X Turntable ETS 2087 ETS X Mast & Table Controller ETS/EMCO 2090 ETS/EMCO X Power Analysis System EM Test DPA 500 0501/09 AC Power Source EM Test ACS 500 1101/01 Test Report E115780.00 Satec Ltd. Page 13 of 44

7. E.U.T. Performance Verification 7.1 Mode of Operation During the tests, The E.U.T. was set as follows: 1. Displays active energy at front panel. 2. Communicates through RS485 connection to laptop monitor. 3. All parameters were displayed in real time through the laptop. 4. Figure 1. Conducted and Radiated Emission Test Set-up Test Report E115780.00 Satec Ltd. Page 14 of 44

Figure 2. Immunity Tests Set-up 7.2 Monitoring of E.U.T. The E.U.T. and laptop display were monitored while reading the energy measured level. 7.3 Definition of Failure i) For Radiated Immunity and Conducted Disturbances tests: reading of energy level was out of 153±1kW. ii) For all other immunity tests: Same as paragraph 7.3.i) above, after the cessation of the disturbances. Test Report E115780.00 Satec Ltd. Page 15 of 44

8. Conducted Emission 8.1 Test Specification 0.15-30 MHz, CISPR 22: 2008, CLASS A 8.2 Test Procedure The E.U.T operation mode and test set-up are as described in Section 7.1. In order to minimize background noise interference, the conducted emission testing was performed inside a shielded room (see Section 3), with the E.U.T (table-top) placed on an 0.8 meter high wooden table, 0.4 meter from the room's vertical wall. In the case of a floor-standing E.U.T., it was placed on the horizontal ground plane. The E.U.T was powered from 230 V AC / 50 Hz via 50 Ohm / 50 µhn Line Impedance Stabilization Network (LISN) on the phase and neutral lines. The LISN's were grounded to the shielded room ground plane (floor), and were kept at least 0.8 meters from the nearest boundary of the E.U.T The center of the E.U.T. s AC cable was folded back and forth, in order to form a bundle less than 0.40 meters and a total cable length of 1 meter. The effect of varying the position of the cables was investigated to find the configuration that produces maximum emission. The configuration tested is shown in the photograph, Figure 15. Conducted Emission Test. The emission voltages at the LISN's outputs were measured using a computerized receiver, complying to CISPR 16 requirements. The specification limits are loaded to the receiver via a 3.5" floppy disk and are displayed on the receiver's spectrum display. A frequency scan between 0.15 and 30 MHz was performed at 9 khz I.F. band width, using peak detection. The spectral components having the highest level on each line were measured using a quasi-peak and average detector. 8.3 Test Results The E.U.T. met the requirements of the CISPR 22: 2008, CLASS A specification. The margin between the emission levels and the specification limit is, in the worst case, 0.7 db for the phase line at 0.64 MHz and 0.6 db at 0.64 MHz for the neutral line. The details of the highest emissions are given in Figure 3 to Figure 6. Test Report E115780.00 Satec Ltd. Page 16 of 44

Conducted Emission E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: Lead: Detectors: CISPR 22: 2008, Class A Phase Quasi-peak, Average Figure 3. Detectors: Quasi-peak, Average Note: DELTA LIMIT refers to the test results obtained minus specified requirement; thus a positive number indicates failure, and a negative result indicates that the product passes the test. Test Report E115780.00 Satec Ltd. Page 17 of 44

Conducted Emission E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: Lead: Detectors: CISPR 22: 2008, Class A Phase Quasi-peak, Average Figure 4. Detectors: Quasi-peak, Average Test Report E115780.00 Satec Ltd. Page 18 of 44

Conducted Emission E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: Lead: Detectors: CISPR 22: 2008, Class A Neutral Quasi-peak, Average Figure 5. Detectors: Quasi-peak, Average Note: DELTA LIMIT refers to the test results obtained minus specified requirement; thus a positive number indicates failure, and a negative result indicates that the product passes the test. Test Report E115780.00 Satec Ltd. Page 19 of 44

Conducted Emission E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: Lead: Detectors: CISPR 22: 2008, Class A Neutral Quasi-peak, Average Figure 6 Detectors: Quasi-peak, Average, Test Report E115780.00 Satec Ltd. Page 20 of 44

9. Radiated Emission 9.1 Test Specification 30-1000 MHz, CISPR 22: 2008 CLASS A 9.2 Test Procedure The E.U.T operation mode and test set-up are as described in section 7.1. A preliminary measurement to characterize the E.U.T was performed inside the shielded room. The preliminary measurements produced a list of the highest emissions. The E.U.T was then transferred to the open site, and placed on a remotecontrolled turntable. For table-top products, the E.U.T was placed on a non-metallic table, 0.8 meters above the ground. For floor-standing products, the E.U.T. was placed directly on the horizontal ground plane, but was separated from metallic contact with the ground plane by up to 15 cm of insulation. The effect of varying the position of the cables was investigated to find the configuration that produces maximum emission.. The configuration tested is shown in Figure 16. Radiated Emission Test. The E.U.T. highest frequency source or used frequency is 20 MHz. The frequency range 30-1000 MHz was scanned, and the list of the highest emissions was verified and updated accordingly. The emissions were measured using a computerized EMI receiver complying to CISPR 16 requirements. The specification limits and applicable correction factors are loaded to the receiver via a 3.5" floppy disk. The readings were maximized by adjusting the antenna height between 1-4 meters, the turntable azimuth between 0-360, and the antenna polarization. Verification of the E.U.T emissions was based on the following methods: Turning the E.U.T on and off. Using a frequency span less than 10 MHz. Observation of the signal level during turntable rotation. Background noise is not affected by the rotation of the E.U.T. The emissions were measured at a distance of 3 meters. 9.3 Test Results The E.U.T met the requirements of the CISPR 22: 2008 CLASS A specification. The margin between the emission level and the specification limit is 14.0 db in the worst case at the frequency of 111.48 MHz, vertical polarization. The details of the highest emissions are given in Figure 7. Test Report E115780.00 Satec Ltd. Page 21 of 44

Radiated Emission E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: CISPR 22: 2008 Class A Antenna Polarization: Horizontal/Vertical Antenna: 3 meters distance Frequency range: 30 MHz to 1000 MHz Detectors: Peak, Quasi-peak Frequency QP Amp Antenna Polarization: Limit Margin (MHz) dbµv/m Hor. Ver. dbµv/m (db) 84.39 22.6 X 50.5-27.9 240.02 38.1 X 57.5-19.4 360.01 36.4 X 57.5-21.1 111.48 36.5 X 50.5-14.0 126.83 36.5 X 50.5-14.0 240.02 38.7 X 57.5-18.8 Figure 7. Radiated Emission. Antenna Polarization: HORIZONTAL/VERTICAL Detectors: Peak, Quasi-peak Note: Margin refers to the test results obtained minus specified requirement; thus a positive number indicates failure, and a negative result indicates that the product passes the test. Test Report E115780.00 Satec Ltd. Page 22 of 44

10. Immunity to Electrostatic Discharge 10.1 Test Specification IEC 61000-4-2: 2008 10.2 Test Procedure In the case of tabletop equipment, the E.U.T. was set up on a wooden table 0.8m high on an insulating support 0.5 mm thick above the reference ground plane. In the case of floor-standing equipment, the EUT and cables were set up on an insulating support 0.1m above the reference plane. The test setup is illustrated in the photograph, Figure 17. Immunity to Electrostatic Discharge Test. Photographs in Figure 8 to Figure 9 show the locations of test points. 10.2.1 Air Discharge Potentials of 2, 4 and 8 kv were applied near each applicable test point. At places where discharge occurred, the potential was applied twenty times; ten times negative and ten times positive. The E.U.T.'s performance during the test was verified as detailed in Section 7. 10.2.2 Contact Discharge Potentials of 2 and 4 kv were applied to each applicable test point. In places where discharge occurred, the potential was then applied twenty times; ten negative and ten positive discharges. The E.U.T.'s performance during the test was verified as detailed in Section 7. 10.2.3 Indirect Discharge (vertical and horizontal coupling plane) Potentials of 2 and 4 kv were applied to the center of the vertical edge of the coupling plane at a distance of 0.1 meters from the outer casing of the E.U.T. to each applicable test point. The potential was applied 10 times for each polarity, to each location of the coupling plane. All four faces of the E.U.T. were completely illuminated. An ESD of the same characteristics as for the vertical coupling plane was applied to the horizontal coupling plane, at each side of the E.U.T., at a distance of 0.1 meter from it's outer casing. Additional details are shown in Figure 5 of IEC 61000-4-2: 2008. The E.U.T.'s performance during the test was verified as detailed in Section 7. 10.3 Test Results The E.U.T met the requirements of specification IEC 61000-4-2: 2008. Test Report E115780.00 Satec Ltd. Page 23 of 44

Immunity to Electrostatic Discharge E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: IEC 61000-4-2: 2008 Air Air Figure 8. ESD Test Points Test Report E115780.00 Satec Ltd. Page 24 of 44

Immunity to Electrostatic Discharge E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: IEC 61000-4-2: 2008 Air Figure 9. ESD Test Points Test Report E115780.00 Satec Ltd. Page 25 of 44

11. Immunity to Radiated Field 11.1 Test Specification IEC 61000-4-3: 2008 + A1: 2007; A2: 2010 11.2 Test Procedure The E.U.T. was subjected to a field of 10V/m, amplitude modulated 80% by a 1kHz sinusoidal signal in the frequency range 80-2700; 1400-2000 MHz. The Radiated Field was applied in vertical and horizontal polarization using Biconilog antennas in the frequency ranges of 80-1000 MHz and horn antennas in the frequency ranges 1400-2700MHz. The Radiated Field was calibrated and tested for uniformity in accordance with Section 6.2 of IEC 61000-4-3. The calibration values for the driver signal generator were based on the data given in I.T.L. "Radiated Immunity Calibration Test Report" No. PM-112R-IMM. The frequency was swept using discrete increments having a value less than 1% of the fundamental frequency. The performance of the E.U.T. was verified during the test as described in Section 7. The test setup is illustrated in the photograph, Figure 18. Immunity to Radiated Field Test. Note: Opinion and Interpretation: The most sensitive surface of the E.U.T. was fully tested. The most sensitive E.U.T. surface was determined as follows: A preliminary radiated emission test in the frequency range 80 1000 MHz was performed inside the semi-anechoic chamber using an E-field probe and spectrum analyzer. The surface having the maximum radiation level was selected as the most sensitive surface. 11.3 Test Results The E.U.T. passed the Radiated Immunity Tests as required by specifications: IEC 61000-4-3: 2006 + A1: 2007; A2: 2010. For additional information see Figure 10. Test Report E115780.00 Satec Ltd. Page 26 of 44

Radiated Immunity E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: IEC 61000-4-3: 2006 + A1: 2007; A2:2010 80-1000; 1400-2000; 2000-2700 MHz Amplitude Modulation: 80% AM by 1 khz Frequency (MHz) From To Antenna Polarity Specification (V/m) PASS / FAIL 80 2700 Horizontal 10.0 Pass 80 2700 Vertical 10.0 Pass Immunity Threshold (V/m) Figure 10. Immunity to Radiated Field Test Report E115780.00 Satec Ltd. Page 27 of 44

12. Immunity to Electrical Fast Transient / Burst 12.1 Test Specification IEC 61000-4-4: 2004 + A1: 2010 12.2 Test Procedure The E.U.T. was placed 0.1 m above a reference ground plane. The EFT/B generator was placed on, and grounded to, this ground plane. See the photograph, Figure 19. Immunity to Electrical Fast Transient / Burst Test. A test signal having the waveform described in Figure 20. Transient Waveforms was applied to the phase neutral and ground lines of the E.U.T mains input, at a distance of 1 meter from the E.U.T. The test signal voltage was 2 kv and it was applied for 1 minute to each line, in negative and positive polarities. The same test signal was applied to the signal lines, control and DC lines (as applicable), that are connected to the E.U.T. The voltage level was 1 kv in this case Applicable signal and control lines should have a length greater than 3m. 12.3 Test Results The E.U.T. passed the immunity to electrical fast transients / bursts requirements as detailed by specification IEC 61000-4-4: 2004 + A1: 2010. Additional details are given in Figure 11. Test Report E115780.00 Satec Ltd. Page 28 of 44

Electrical Fast Transient / Burst E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: IEC 61000-4-4: 2004 + A1: 2010 [ x ] Positive Polarity [ x ] Negative Polarity TEST POINT PASS / FAIL ANOMALY SPECIFICATION (kv) Phase Pass No anomaly 2.0 Neutral Pass No anomaly 2.0 THRESHOLD (kv) CAPACITIVE CLAMP TEST POINT PASS / FAIL ANOMALY SPECIFICATION (kv) Measuement Input Port Pass 1.0 RS485 Port Pass 1.0 THRESHOLD (kv) Figure 11. Immunity to Electrical Fast Transient / Burst Test Report E115780.00 Satec Ltd. Page 29 of 44

13. Immunity to Conductive Surges 13.1 Test Specification IEC 61000-4-5: 2005 13.2 Test Procedure The E.U.T. was subjected to transient signals of the form of double exponential waves with a rise time of 1.2 µs and a pulse width of 50 µs (open circuit). The short circuit waveform is an 8 x 20µs double exponential. See Figure 21. Open Circuit Waveform (1.2 x 50µs double exponential). The surges were applied to the E.U.T. AC power lines in differential mode. The differential (between phase and neutral) voltages were 0.5 and 1 kv. The surges were injected in both positive and negative polarities in to the AC line, at phase angles of 0, 90, 180, 270 and 360 ; both peak and zero crossings. At least five surges were applied at each polarity. The surge repetition rate was kept to not more than one per minute. Signal lines were tested at 2 kv. The performance of the E.U.T. was verified during the test as described in section 7. The test setup is shown in the photograph, Figure 22. Immunity to Conductive Surges 13.3 Test Results The E.U.T. passed the immunity to surges requirements as detailed by specification IEC 61000-4-5: 2005. Additional details are given in Figure 12 to Figure 13. Test Report E115780.00 Satec Ltd. Page 30 of 44

Immunity to Conductive Surges E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: IEC 61000-4-5: 2005 TEST POINT Polarity 0 /360 90 180 270 Specified Level Remarks Phase to Neutral + P P P P 0.5, 1 kv - P P P P 0.5, 1 kv Figure 12. Immunity to Conductive Surges on AC Mains NOTE: Each test was executed at least five times. Test Report E115780.00 Satec Ltd. Page 31 of 44

Immunity to Conductive Surges E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: IEC 61000-4-5: 2005 TEST POINT Polarity Specified Level Remarks RS485 Port + 2 kv - 2 kv Measurement Port + 2 kv - 2 kv Figure 13. Immunity to Conductive Surges on Signal lines NOTE: Each test was executed at least five times. Test Report E115780.00 Satec Ltd. Page 32 of 44

14. Immunity to Magnetic Field 14.1 Test Specification IEC 61000-4-8: 2009 14.2 Test Procedure The E.U.T. operation mode and test setup are described in section 7.1. For table top equipment, the E.U.T. and cables were placed on an insulating support, 0.1m thickness, which was placed on a reference non-magnetic (aluminum) ground plane. The ground plane was placed on a wood table. For floor standing equipment, the E.U.T. and cables were placed on an insulating support, 0.1m thickness, which was placed on a reference non-magnetic (aluminum) ground plane. The ground plane was placed on the floor. The E.U.T. was subjected to the magnetic field by using an induction coil. The induction coil was rotated 90 to expose the E.U.T. to all the different field orientations. For E.U.T. s larger than the induction coil, the coil was shifted by steps of 50% (of the coil size), so that the volume of the E.U.T. was tested. In case of performing the tests outside of a shielded room, it will be verified that the magnetic field level with the E.U.T. in OFF, is at least 20 db below the test level. The test setup is illustrated in the photograph Figure 23. Immunity to Magnetic Field. 14.3 Test Results The E.U.T. passed the Magnetic Immunity tests as required by specification IEC 61000-4-8: 2009. Additional details are given in Figure 14. Test Report E115780.00 Satec Ltd. Page 33 of 44

Immunity to Magnetic Field E.U.T Description 3-Phase Power Meter Type PM135 Serial Number: 928504 Specification: IEC 61000-4-8: 2009 PASS / FAIL Strength of Magnetic Field (A/m) Vertical Pass 30 Vertical at 90 Pass 30 Horizontal Pass 30 Figure 14. Immunity to Magnetic Field Test Report E115780.00 Satec Ltd. Page 34 of 44

15. Set Up Photographs Figure 15. Conducted Emission Test Figure 16. Radiated Emission Test Test Report E115780.00 Satec Ltd. Page 35 of 44

Figure 17. Immunity to Electrostatic Discharge Test Figure 18. Immunity to Radiated Field Test Test Report E115780.00 Satec Ltd. Page 36 of 44

Figure 19. Immunity to Electrical Fast Transient / Burst Test Figure 20. Transient Waveforms Test Report E115780.00 Satec Ltd. Page 37 of 44

Figure 21. Open Circuit Waveform (1.2 x 50µs double exponential) Figure 22. Immunity to Conductive Surges Test Report E115780.00 Satec Ltd. Page 38 of 44

Figure 23. Immunity to Magnetic Field Test Report E115780.00 Satec Ltd. Page 39 of 44

16. Signatures of the E.U.T's Test Engineers Test Test Engineer Name Signature Date Conducted Emissions Y. Mordukhovitch 13.08.12 Voltage Fluctuations Y. Mordukhovitch 13.08.12 ESD Y. Mordukhovitch 13.08.12 Radiated Immunity Y. Mordukhovitch 13.08.12 EFT/B Y. Mordukhovitch 13.08.12 Conductive Surges Y. Mordukhovitch 13.08.12 Magnetic Immunity Y. Mordukhovitch 13.08.12 Test Report E115780.00 Satec Ltd. Page 40 of 44

17. APPENDIX A - CORRECTION FACTORS 17.1 Correction factors for CABLE from EMI receiver to test antenna at 3 AND 10 meter range. FREQUENCY CORRECTION FACTOR FREQUENCY CORRECTION FACTOR (MHz) (db) (MHz) (db) 30 1.96 700 11.25 35 2.08 800 12.53 40 2.26 900 13.86 45 2.43 1000 14.86 50 2.59 1200 15.7 55 2.65 1400 17.05 60 2.86 1600 18.2 65 2.96 1800 19.4 70 3.04 2000 21.3 75 3.27 80 3.41 85 3.54 90 3.68 95 3.77 100 3.93 110 4.19 120 4.41 130 4.6 140 4.83 150 5.06 160 5.35 170 5.57 180 5.7 190 5.84 200 6.02 250 6.86 300 7.59 350 8.09 400 8.7 450 9.15 500 9.53 550 9.82 600 10.24 650 10.74 NOTES: 1. The cable type is RG-214/U Test Report E115780.00 Satec Ltd. Page 41 of 44

17.2 Correction factors for Amplifier 8447F 30M-1.3G GAIN FREQUENCY (MHz) GAIN (db) 20 27.16 30 27.18 50 27.15 100 27.01 200 26.48 500 27.54 1000 26.96 1100 26.69 1200 26.28 1300 25.85 Test Report E115780.00 Satec Ltd. Page 42 of 44

17.3 Correction factors for Bilog ANTENNA Model: 3142 Antenna serial number: 1250 3 meter range FREQUENCY AFE FREQUENCY AFE (MHz) (db/m) (MHz) (db/m) 30 18.4 1100 25 40 13.7 1200 24.9 50 9.9 1300 26 60 8.1 1400 26.1 70 7.4 1500 27.1 80 7.2 1600 27.2 90 7.5 1700 28.3 100 8.5 1800 28.1 120 7.8 1900 28.5 140 8.5 2000 28.9 160 10.8 180 10.4 200 10.5 250 12.7 300 14.3 400 17 500 18.6 600 19.6 700 21.1 800 21.4 900 23.5 1000 24.3 Test Report E115780.00 Satec Ltd. Page 43 of 44

18. APPENDIX B - MEASUREMENT UNCERTAINTY 18.1 Radiated Emission Radiated Emission (CISPR 11, EN 55011, CISPR 22, EN 55022, ANSI C63.4) for open site 30-1000MHz: Expanded Uncertainty (95% Confidence, K=2): ± 4.96 db 18.2 Conducted Emission Conducted Emission (CISPR 11, EN 55011, CISPR 22, EN 55022, ANSI C63.4) 0.15 30 MHz: Expanded Uncertainty (95% Confidence, K=2): ± 3.44 db Test Report E115780.00 Satec Ltd. Page 44 of 44