SIGN STRUCTURE BOLT TESTING AND INSPECTION! WHAT HAVE WE FOUND AND WHAT ARE WE DOING

Similar documents
Procedure for Wrench Calibration and Snug Tightening

NTTC Tank Truck Week Awareness Gaskets/Fasteners/Flanges

Instruction Manual for installing

Instruction Manual for installing

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

Procedure for Testing Direct Tension Indicators (DTI) Assemblies

SIGNALS AND LIGHTING FIELD GUIDE

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the grade A325 structural bolt.

Contents. Grade 2, 5, 8 Hex Bolts 4. Heavy Hex Head Structural Bolts 6. A325 and A490 Tension Control Bolts (TC) 13. Nuts 22.

Tightening of Structural Joints

6o ft (18.3 m) Southwest Windpower, Inc West Route 66 Flagstaff, Arizona USA Phone: Fax:

Evaluation of In-Pavement Light Fixture Designs and Performance

Figure 11 Flange Adapter and Back-Up Ring

LOAD INDICATOR WASHERS USING DTI S WITH TENSION CONTROL BOLTS

TYPE J (20 FT - 40 FT) MICHIGAN DEPARTMENT OF TRANSPORTATION 10-0" 7-6" NOTE: sheet 5 & 6 of 10) DEPARTMENT DIRECTOR. Kirk T.

SECTION STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SIG-032-B TRAFFIC SIGNAL MAST ARM POLE AND MAST ARM DETAILS - CATEGORY III LUMINAIRE ARM (SEE CONTRACT) 6'-0", 8'-0", 10'-0" NOMINAL SPREAD

ERECTION & CONSTRUCTION

USER MANUAL MODEL MZ-100 BOLT TENSION CALIBRATOR

(50 FT FT) MICHIGAN DEPARTMENT OF TRANSPORTATION 10-0" 7-6" 8-0" 6-0" Truss Depth. 3" sheets 5 & 6 of 10) DEPARTMENT DIRECTOR. Kirk T.

712 - STRUCTURAL STEEL CONSTRUCTION SECTION 712 STRUCTURAL STEEL CONSTRUCTION

1.1 RELATED DOCUMENTS

5/16" Flange nut. Bolt Keeper Plate (8" Sq. SYS.) (3) 1/2" x 3" Hex head connector zinc plated bolt w/ washers and nut. Anchor 3" sq. 7 Ga.

ATTENTION. 4. Do not over tighten the hydraulic fittings. This will cause leakage and will not be covered under warranty.

What is a fastener? A device to locate or hold parts

Practical Bolting and Gasketing for the Non Standard-Flanged Joint

CONCRETE ACCESSORIES BAR-LOCK REBAR COUPLER SYSTEM

TECHNICAL CORRECTION October Process Industry Practices Structural. PIP STF05121 Fabrication and Installation of Anchor Bolts

SIG-030-B TRAFFIC SIGNAL MAST ARM POLE AND MAST ARM DETAILS - CATEGORY I LUMINAIRE ARM 6'-0", 8'-0", 10'-0" NOMINAL SPREAD (SEE CONTRACT) POLE CAP

2016 AASHTO BRIDGE COMMITTEE AGENDA ITEM: 24 (REVISION 1) SUBJECT: LRFD Bridge Design Specifications: Section 6, Various Articles (2)

Instruction Manual for Installing HIGH-STRENGTH BOLTS

Instruction Manual for Installing HIGH-STRENGTH BOLTS

11-1/4 OD at Transition Point. Microcosmic. 4th and Brannan Street Platform Station Project. Elevation. Moto Ohtake 2014

SYGEF Standard SYGEF Plus PVDF Flanges

Fluid Sealing Association

Tex-452-A, Rotational Capacity Testing of Fasteners Using a Tension Measuring Device

What is a fastener? A device to locate or hold parts

Guidelines for use of High Strength Friction Grip (HSFG) bolts on bridges on Indian Railways. Ordinary Bolt action 1: Bearing of bolt/ plate

ESR-2024* Reissued September 1, 2011 This report is subject to renewal September 1, 2013.

Midwest Roadside Safety Facility

Letter of Transmittal/Submittal

X-TENSION 350 Guardrail End Terminal Tangent and Flared

USER MANUAL Nord-Lock X-series washers

Re-tightening the Large Anchor Bolts of Support Structures for Signs and Luminaires

CAT-350 Product Manual

A training course delivered at a company s facility by Matrix Engineering, an approved provider of Bolt Science Training

ODOT ITB Group 4 Item 33 Qty. 1

GUIDELINES FOR HINGED AND BOLTED MANWAY ASSEMBLY

PROCEDURE:INSTALLATION OF BOLTED AND THREADED CONNECTIONS. as a result of improper lifting technique.

1. ANSI/ASME Standard B , Square and Hex Bolts and Screws, Inch Series

Assmann Corporation of America TANK INSTALLATION AND USE GUIDELINES FOR BULK STORAGE TANKS

SECTION 1050 STEEL BRIDGE SUPERSTRUCTURE

.84M Ku-Band Rx/O Antenna System

Disclaimer. Socket Products Socket depth limits maximum torque. Torque figures are based on 80% of maximum torque for a given key size.

MECH-100: Fundamentals of Precision Maintenance

SPIDA SAW OPERATIONS MANUAL

Bolt Tensioning. This document is a summary of...

Removing the Z-Axis lead screw

Row Pro 300. Standard Unit. Assembly Instructions and Operating Guide. Row Pro 300. Kongskilde Revision 1

Installation Manual. Things to remember - Page 2 The Technotill Seeding System. - Page 3 Assembling an Opener

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

CH # 8. Two rectangular metal pieces, the aim is to join them

LENGTH IDENTIFICATION

Installation Instructions TMW Antenna Tower Mount for 4ft (1.2m) Antennas.

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

A training course delivered at a company s facility by Matrix Engineering, an approved provider of Bolt Science Training

I-W07/W77. Couplings DETAIL A WARNING. Photo Showing Pipe with Weld Seam Ground 6 inches/152 mm Back from Pipe End and an AGS Groove

Gasket Installation Procedures. Assuring! joint integrity and! maximum safety

PART MATERIALS. Section Fencing Materials. Description

CIRRUS AIRPLANE MAINTENANCE MANUAL

Stargrip series 3000 Mechanical Joint Wedge Action Restraint for Ductile Iron Pipe

Page 1 of 6 Systems Inc.

Load Indicating Washers

1.8 METER SERIES 1194 ANTENNA SYSTEM

AVOID INSECURE AND IMPROPER DIE FASTENING

Barhale Construction plc. Excavator Pole Grab Standard

The Redi-Flange Method. How It Works. Services. Engineering & Costing Assistance

Assembly Instructions for. for 31" MGS (Midwest Guardrail System) ROAD SYSTEMS, INC.

8030 Synergy Jeep JK Rear Long Arm Frame Brackets

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

D. Thermally Sprayed Metallic Coating (Flame Spray): STD SPEC

Threaded Fasteners 2. Shigley s Mechanical Engineering Design

Motorized Tower Raising System Manual

SKT-SP Tangent Terminal

Installation Instructions

Joint Preparation prior to Tensioning: General:

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

Look Our New Technology

SECTION ROOF ACCESSORIES. Display hidden notes to specifier. (Don't know how? Click Here)

Index. Introduction. Arrow & ARP Care

Fasteners. Fastener. Chapter 18

RAIL PANEL AT TRANSITION SECTION PLAN - POST DETAIL PLAN - TUBE SPLICE. Colorado Department of Transportation. Staff Bridge Branch

ABSORB 350 Crash Cushion Product Specifications

X-Tension TM Guardrail End Terminal

Terminus TM CEN End Terminal

SECTION METAL FABRICATIONS

PIP STF05121 Anchor Fabrication and Installation Into Concrete

Installation Instructions for OPGW Bolted Dead End

400A 40113V, 401A 40120V, & 401AL 40120VL ALUMINUM VERTICAL 4000 LB LIFT INCLUDES SCREW LEG ASSEMBLY INSTRUCTIONS

ALUMINUM PIPE GUIDERAIL 01/01/

Transcription:

The Golden Anniversary of the Mid-Atlantic Quality Assurance Workshop SIGN STRUCTURE BOLT TESTING AND INSPECTION! WHAT HAVE WE FOUND AND WHAT ARE WE DOING Maryland State Highway Administration Bruce L. Abernathy, CWI / CIP II February 8, 2017

NEWS FLASH 904 OVER HEAD STRUCTURES IN INVENTORY 14,829 ANCHOR BOLTS TESTED 7 STRUCTURES REMOVED DUE TO CRACK LIKE INDICATIONS 1127 CANTILEVER STRUCTURES IN INVENTORY 8,216 ANCHOR BOLTS TESTED 1 STRUCTURE REMOVED DUE TO CRACK LIKE INDICATIONS 8 STRUCTURES HAVE SPLICE BOLTS (MECHANICAL) 2 WELDED NOT FULL PENETRATION WELDS 5 YEAR CYCLE COMPLETED IN 2016 WILL RESTART IN FY 18 FIRST CYCLE TOOK 5 YEARS BUT 2 ND CYCLE MAY RESULT AS MUCH AS A 50% TIME SAVINGS DUE TO NOT HAVING TO SPEND AS MUCH TIME PREPPING THE BOLT TOPS. (GRINDING SMOOTH)

NEWS FLASH AT THE PRESENT TIME SIGNAL POLES ARE BEING INSPECTED. THIS INCLUDES ANCHOR BOLTS AND ARM CONNECTION BOLTS. 1688 POLES 1292 ARMS 6792 ANCHOR BOLTS 5162 CONNECTION BOLTS INSPECTIONS OF SIGNAL POLES HAVE RESULTED IN LOCATING DAMAGE THAT MAY HAVE NEVER BEEN REPORTED.

WHAT ELSE DID WE FIND ~10% OF ALL BOLTS ARE LOOSE SHA AND WAGNALLS LOOSE ANCHOR BOLT. THE ABILITY OF ONE OR MORE WASHERS TO BE MOVED UNDER THE NUTS WITH LITTLE OR NO EFFORT.

WHAT DID WE FIND

HOW DID THIS HAPPEN? Project Inspector Well they were tight when we looked at them yesterday. Must have relaxed over night or they vibrated loose.

HOW DID THIS HAPPEN? #1 Priority Fix the Loose Bolts & Instal ALL NEW Structures Properly.

WHAT ARE THE REQUIREMENTS / RECOMMENDATIONS FHWA Guidelines recommend tightening the anchor bolts and nuts using the turn on the nut method after being brought to a SNUG TIGHT condition. Bolt Dim Less Than 1 1/2" 1 1/2" and Larger ASTM Bolt F1554 Gr36 Gr 55 Gr 105 1/6 turn 1/3 Turn 1/3 turn 1/12 turn 1/6 trun 1/6 turn This table should only be used with double nut moment joints.

NCHRP INFORMATION? NCHRP Report 494 Structural Supports for Highway Signs, Luminaires and Traffic Signals 2003

SNUG TIGHT OR FULLY TIGHTENED??? Of course, whenever practical, anchor rods should be installed in the fully tightened condition (i.e., tightened to one-third of a turn beyond snug for most anchor rod sizes). Although no benefit is recommended when designing fully tightened anchor rods for infinite life, it should be noted that the fully tightened condition precludes the possibility of anchor rod nuts becoming loose under service-load conditions. As a result, the fully tightened condition is inherently better with respect to the fatigue performance of anchor rods. Large-diameter rods will require the use of a hydraulic wrench with external lubrication of the threaded and bearing surfaces in order to achieve a fully tightened condition. NCHRP Report 469 Fatigue-Resistant Design of Cantilevered Signal, Sign and Light Supports.

5.17.5.2 Anchor bolt Pre-tensioning All anchor bolts shall be adequately tightened to prevent loosening of nuts and to reduce the susceptibility of fatigue damage. Anchor bolts in double-nut connection shall be pre-tensioned C 5.17.5.2 Lubrication of the threaded and bearing surfaces is typically performed prior to Tightening. In double-nut connections, lower nuts/washers should be in full contact with the base plate prior to snug tightening the top nuts. After top nuts are snug-tight, the lower nuts should be retightened to assure the full contact has been maintained.

SO HOW MUCH IS REQUIRED Anchor Bolt ASTM F1554 "Pre Load Value" F1554 Gr55 Gr 55 Bolt Gr 36 Bolt Gr 55 Bolt Gr 105 Bolt Bolt Size Inch TPI Area inch 2 Threa d Area inch 2 GR 36 F u PSI GR 55 F u PSI Gr 105 F u PSI Snug PSI 50% PSI 60% PSI Snug Tight Ft/Lbs* Torque Value Ft/Lbs* Torque Value Ft/Lbs* Torque Value Ft/Lbs* 1 1/2 6 1.76 1.41 102080 132000 220000 6600 66000 79200 119 990 1188 1980 1 3/4 5 2.41 1.9 139780 180750 301250 9037.5 90375 108450 190 1582 1898 3163 2 4 1/2 3.14 2.5 182120 235500 392500 11775 117750 141300 283 2355 2826 4710 2 1/4 4 1/2 3.98 3.25 230840 298500 497500 14925 149250 179100 403 3358 4030 6716 2 1/5 4 4.91 4 284780 368250 613750 18413 184125 220950 486 4051 4861 8102 2 3/4 4 5.94 4.93 344520 445500 742500 22275 222750 267300 735 6126 7351 12251 3 4 7.07 5.94 410060 530250 883750 26513 265125 318150 954 7954 9545 15908 3 1/4 4 8.3 7.1 481400 622500 1037500 31125 311250 373500 1214 10116 12139 20231 3 1/2 4 9.62 8.33 557960 721500 1202500 36075 360750 432900 1515 12626 15152 25253 *Anchor Rod Tightening for Highmast Light Towers and Cantilever Sign Structures Collins Engineering, Inc. July 30, 2010 (TRB 2011)

SO HOW MUCH IS REQUIRED? The torque requirements are based on new and well lubricated anchor rod threads and nuts. The NCHRO 469 report recommends that new installations have rod tightness rechecked after two days using a verification torque of 110 % Apparently, the reason for this check is possible connection loosening due to deformation or creep of the galvanizing within the threads. 1 1 Anchor Rod Tightening for Highmast Light Towers and Cantilever Sign Structures Collins Engineering, Inc. July 30, 2010 (TRB 2011)

SO HOW MUCH IS REQUIRED? SHA/OMT performed limited load cell tests in 2016 using 2 ¼ HDG Studs that showed the torque values were not achievable with hand tools or slugging wrenches. The tests also showed a small relaxing or compression of the zinc after being tensioned. ~2% and resulted in less than 30 mins. One sample was left for over 48 hours and showed no creep after the first 30mins. Our Feeling, if it is not tight now it never was tight. 1 Anchor Rod Tightening for Highmast Light Towers and Cantilever Sign Structures Collins Engineering, Inc. July 30, 2010 (TRB 2011)

MARYLAND S APPROACH New Special Provision has been written to require the use of Hydraulic Wrenches for all NEW installations on Traffic Structures. Calibration will be required on all units no less than Once a Year OMT in process of ordering new Load Cell Units up to 3 bolt diameter. Bolt diameters are being restricted in design to standard limited sizes 2 2 ½ 3 OOTS and or OMT personnel will be on site during tightening evaluations. TRAINING TRAINING and more TRAINING!

MARYLAND S APPROACH Loose Bolts being re-tightened under OOTS Contract. Use of Slugging Wrench 10 Structures are being selected to use the hydraulic wrench system. Value will be based on grade 36 bolts and the thread area. Due to we don t have a 100% guarantee of what bolts was used. 100% UT before, after and 90 days after re-tighting.

MARYLAND S APPROACH Top nuts will be removed cleaned and relubricated before being re-tightened Lower (Leveling) nuts will be brought into full contact before re-tightening of top nuts Tension will be based on Gr 36* bolts and 50% of F u. *Based on not knowing what bolts are in the foundations

MARYLAND S APPROACH Hydraulic Equipment

MARYLAND S APPROACH Equipment for Small Bolts 36Volt Can install 1 plus A325 bolts to proper tension Repeatability End of Day Reports

CONCLUSION Loose anchor bolts can reduce the life span of cantilever and single structures. Ongoing training for personnel tightening and inspecting the operation is a high priority. Oversight inspection of anchor bolt tightening is required NEXT STEPS TRB 2017 Traffic Signal Sub-Committee agreed to submit a new problem statement to look at the true pre load requirements Maryland SHA, VA Research Counsel And VDOT have agreed to performing laboratory testing of real time samples during 2017 that will include vibration testing.

QUESTIONS