Variable Frequency Drives Motor Bearing Failure Mitigation

Similar documents
Motor Bearing Damage and Variable Frequency Drives: - Diagnosing the Causes, - Implementing a Cure, and - Avoiding the Pitfalls

Bearing Currents. Introduction. What are Bearing Currents? Application Note AP040061E Effective January 2014

Application Note. Motor Bearing Current Phenomenon. Rev: Doc#: AN.AFD.17 Yaskawa Electric America, Inc August 7, /9

ABB drives. Technical guide No. 5 Bearing currents in modern AC drive systems

Product Application Note

Technical Guide No. 5. Bearing Currents in Modern AC Drive Systems

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers

Technical White Paper

External Drive Hardware

Mitigation Techniques of shaft voltage and bearing current in Inverter Driven Three Phase Induction Motor

Application Note. Applicable Product: AC Drives

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Solution of EMI Problems from Operation of Variable-Frequency Drives

Fluke MDA-510 and MDA-550 Motor Drive Analyzer

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

MTE training MTE Corporation

A PRACTICAL GUIDE TO UNDERSTANDING BEARING DAMAGE RELATED TO PWM DRIVES

Measuring Reflected Voltage Spikes in VFD Motor Applications

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

Cable Solutions for Servo and Variable Frequency Drives (VFD)

6. du/dt-effects in inverter-fed machines

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

INDUSTRY WHITE PAPER. Inverter-Driven Induction Motors Shaft and Bearing Current Solutions

EVERGREEN EM INSTALLATION GUIDE

CEU Certification Test Drive Road Show: TRM040-DrivesRoadShow-CEU

Massachusetts Amusement Device Safety Seminar 2015

Bearing Currents and Shaft Voltages of an Induction Motor Under Hard and Soft Switching Inverter Excitation

The Multi-Technology Approach to Motor Diagnostics

IT HAS LONG been recognized that bearing damage can be

VARIABLE SPEED DRIVES AND MOTORS

Installation Guide. A Regal Brand. EvergreenCM ManPROOF _Fnl.indd 1

High Technology Control

CHAPTER-6 MEASUREMENT OF SHAFT VOLTAGE AND BEARING CURRENT IN 2, 3 AND 5-LEVEL INVERTER FED INDUCTION MOTOR DRIVE

Dynamo Brushless DC Motor and GreenDriveTM Manual

Application Note. About VFD Cables Steve Wetzel, Sr. Product Engineer

SECTION PANELBOARDS

DC CIRCUITS Part I of III Parts. Part II installation. Part III troubleshooting

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

VFD Level II: Application Considerations. Jason Fahey, Vice President John Fahey, President

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Bearing Damage Analysis by Calculation of Capacitive Coupling between Inner and Outer Races of a Ball Bearing

WATERFLUX 3000 Quick Start

b+m Training Maintenance

CHAPTER 1 INTRODUCTION

Insulation Testing Preventing Equipment Breakdown and Plant Shutdowns

High Frequency Sinewave Guardian TM Filter

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

AD-8100 & AD-8200 Servo Amplifiers

EPG. by Chris C. Kleronomos

WATERFLUX 3000 Quick Start

The Reflective Wave Phenomena

VSD cables in. Working with. industrial & automation applications

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

Mr. DILIP J. Final Year Mtech Student Dept of EEE The Oxford College of Engineering, Bangalore

SECTION AUTOMATIC TRANSFER SWITCH

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

ELECTRICAL INSTALLATION OPERATION MANUAL

Understanding RC Servos and DC Motors

ELECTRICAL INSTALLATION

A.V.R. R250. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. REQUEST A QUOTE

MT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D

vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide

INSTRUCTIONS YASKAWA. Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference.

EE171. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

ESR. The Dynamic Solution. Applications. Products, Consultation, and Service. ESR Pollmeier GmbH

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

High Frequency SineWave Guardian TM Filter

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

Figure 1 Typical Inverter Block Diagram

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Fireye. NEXUS FX04 and FX04-1 Servo Motor Installation DESCRIPTION SAFETY INFORMATION. FX04-1 Shown

NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 4 NOVEMBER 2009

Challenges of Parallel Operations

CHAPTER ELECTROMAGNETIC COMPATIBILITY. Contents of this Chapter...

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

BC145 SIGNAL ISOLATOR BOARD

Bearing Currents and Shaft Voltage Reduction in Dual-Inverter-Fed Open-End Winding Induction Motor With CMV PWM Methods Employing PID

Bearing Currents and Shaft Voltage Reduction in Dual-Inverter-Fed Open-End Winding Induction Motor With CMV PWM Methods Employing PID

Performance Rating of Variable Frequency Drives

EN 50178, IEC

Arc Flash Analysis Training

The Engineer s Guide: Lead Screws vs. Ball Screws

Power Quality Solutions

I Pr I P I OUT R L. Applications. Standards

VARIABLE FREQUENCY DRIVE

Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters

E3 Adjustable Speed Drive Engineering Specification

NEXUS NX50-1, -2 Servo Motor Installation. Fireye DESCRIPTION SAFETY INFORMATION

S11 Adjustable Speed Drive Engineering Specification

Industrial Electrician Level 3

Partial Discharge, Survey or Monitor?

Stepper Motors WE CREATE MOTION

18600 PORTABLE POWER DRIVE THREADER PRODUCT INFORMATION AND OPERATING INSTRUCTIONS:

A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications

18500 PORTABLE ELECTRIC POWER DRIVE

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Electrical measurements on adjustable speed drives Ten measurements that tell you a lot

Electromagnetic and Radio Frequency Interference (EMI/RFI) Considerations For Nuclear Power Plant Upgrades

Welcome Because the field of grounding is so broad, todays presentation is intended not to give you the keys to the gold mine, but to give you a

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Transcription:

Variable Frequency Drives Motor Bearing Failure Mitigation Background Throughout the Commonwealth Campus various motors are controlled by VFDs and the University is seeing a rapid and high failure rate of the motor bearings. This document is intended to provide the technicians with information on how to diagnose the problem and possible mitigations to prolong the life of the motor bearings. Diagnosis A VFD is a type of adjustable-speed drive used in electro-mechanical drive systems to control AC motor speed and torque by varying the motor input frequency and voltage. A VFD s output to a motor is very different to that of an across-the-line starter or a reduced voltage/soft starter. The VFD outputs a Pulse Width Modulated (PWM) signal to the motor. This PWM signal is a DC signal that is switched on and off to act like an AC voltage. PWM drives are inherently associated with high frequency common mode voltages and currents which may cause trouble with motor bearings. When these high frequency voltages find a path to earth through a bearing Electrical Discharge Machining (EDM) typically occurs. Over time this creates a Fluting of the bearings race. Figure 1.1 shows the common path for the high frequency voltages to earth. Figure 1.1 Page 1 of 5

The main diagnosis of motor bearing failure at the University has been determined to be Fluting. Fluting or EDM occurs due to sparking between the bearing s ball and the bearing s race. Over time EDM-based sparking causes erosion in the bearing race that can be seen as a fluting pattern. In large motors, the stray capacitance of the windings provides paths for high frequency currents that pass through the motor shaft ends, leading to a circulating type of bearing current. Poor grounding of motor stators and rotors can lead to shaft bearing currents. Small motors with poorly grounded driven equipment are susceptible to high frequency bearing currents also. Figure 1.2 shows a typical Fluted bearing surface. Once a bearing has experienced EDM, it will only be a matter of time until the bearing fails. In the early stages of EDM, the bearing will appear normal with no apparent signs of EDM. However, over time the bearing will exhibit bearing noise that will ultimately increase towards the end of its life. Not all bearing failures are due to EDM when controlled by a VFD. Many times bearings fail due to: not being properly greased at the factory, not being re-greased during regular maintenance, or from ultimately reaching the end of their usable life. Corrective Action Figure 1.2 While there is no one solution to remedy motor bearing Fluting there are a few ways to mitigate the risk of Fluting. Remedies: 1. Look for proper grounding of the VFD, VFD cabinet, motor, conduit and driven equipment. See Figure 2.1 for a PREFERRED installation diagram of how a system should be grounded when Page 2 of 5

using conduit and shielded cable, Figure 2.1.1 shows a diagram for an ACCEPTABLE installation when using conduit only. Proper grounding means a good earth ground, the technician should verify that the installation is connected to a good earth ground before energizing equipment or returning the equipment to service. Figure 2.1 Figure 2.1.1 2. Ensure that the conduit has continuous electrical connectivity from the VFD enclosure to the motor connection box. Technicians are to verify that the conduit has continuous electrical Page 3 of 5

conductivity before energizing equipment or returning equipment to service. Technicians are to use the appropriate conduit hubs similar to Figure 2.2. If necessary technicians can helically wrap a green grounding wire, sized appropriately, around the flexible conduit leading up to a motor to ensure conduit conductivity. Figure 2.2 3. Set the carrier frequency of the VFD to lower than 6 khz if possible. Authorized qualified personnel shall be the only personnel to change parameters in the VFDs. Contact your supervisor for further assistance. *NOTE: Setting the carrier frequency to a lower value will increase the noise and or sound coming from the motor. This increase in noise and or sound is NORMAL and does not affect the operation of the motor. The technician will have to use their best judgment when setting the carrier frequency and will have to take into account the surroundings and location of the motor. 4. Verify that a VFD rated shielded cable is installed per the cable manufacture s recommendation, see Figure 2.3 for a general view of what a VFD might look like. Contact OPP Engineering Services, Electrical Engineers for further information on VFD cable. If a VFD cable is NOT found on a motor that has had bearing failure contact OPP Engineering, Electrical Engineers for further direction. Figure 2.3 5. At the direction of Engineering Services install a shaft grounding ring. Follow the manufacturer s instructions during installation; do not skip any steps during the installation. 6. Ensure that the VFD motor conductors are at least 6 from other power and control conductors. Page 4 of 5

7. Check that the motor is rated for Inverter or Vector Duty operation. This can sometimes be verified on the motor nameplate or by calling the manufacturer. If a motor is found to not be in compliance, contact OPP Engineering Services. See the list below for a quick check list to verify that a motor is rated for VFD control: a. NEMA Design Code: A b. Insulation Class H or F c. Duty: Continuous d. Constant Torque speed range: 10:1, 20:1, 1000:1, 2000:1 *NOTE: The list above may or may not guarantee that the motor in question is rated for VFD use. When in doubt contact the manufacturer for verification, DO NOT assume that the motor is rated for VFD use. The remedies above can be used as a check list for new installations and renovations to existing systems. However, the most critical items to check are 1, 2 & 3, since they will have the most possible affect on bearing failure. *NOTE: Although, not an electrical item the Technician should verify that the motor bearings are properly lubricated if applicable. If the Technician is unsure contact your supervisor to alert the proper crew to check the motor bearings lubrication and perform any maintenance. Publisher: Penn State University, Office of Physical Plant, Energy and Engineering Division, Engineering Services Editor: Cyle Vogt, Ph.: (717)-994-7903, email: cdv5002@psu.edu Created: November 1, 2013 Last Revision: Source Credits: http://en.wikipedia.org/wiki/variable-frequency_drive; http://electrical-zine.blogspot.com/; Allen Bradley Publication: Allen Bradley drives-in001_-en p.pdf; www.southwire.com; www.garvinindustries.com; Page 5 of 5