Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Similar documents
Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Power Quality Improvement using Shunt Passive Filter

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Harmonics Elimination Using Shunt Active Filter

Active Harmonics Filtering of Distributed AC System

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

ABSTRACT I. INTRODUCTION

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

POWER QUALITY IMPROVEMENT USING SHUNT ACTIVE FILTER

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Power Quality improvement of a three phase four wire system using UPQC

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Power Control and Quality Management in DG Grid Interfaced Systems

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Review on Shunt Active Power Filter for Three Phase Four Wire System

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Chapter 2 Shunt Active Power Filter

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

2020 P a g e. Figure.2: Line diagram of series active power filter.

Power Quality improvement with Shunt Active Power filter using p-q control technique

A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply

PLL Synchronization with PID Controller Based Shunt Active Power Line Conditioners

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Implementation and Comparison of Different Switching Techniques for Shunt Active Power Filters

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Indirect Current Control of LCL Based Shunt Active Power Filter

A HYBRID ACTIVE FILTER FOR A DIODE RECTIFIER USED AS THE FRONT END OF AN INDUCTION MOTOR DRIVE

COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

International Journal of Advance Research in Engineering, Science & Technology

ISSN: (Online) Volume 2, Issue 2, February 2014 International Journal of Advance Research in Computer Science and Management Studies

Enhancement of Power Quality Using Advanced Series Active Power Filters

Simulation Study of PWM Techniques for Voltage Source Converters

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

Reactive Power Compensation of LC Coupling Hybrid Active Power Filters by DC Link Voltage Controls

REDUCTION OF HARMONIC EXPLOITATION DSP CONTROLLER BASED SHUNT ACTIVE FILTER FOR PEMFC FED NON-LINEAR LOAD

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

CURRENT HARMONICS REDUCTION IN 3 PHASES 4 WIRE SYSTEM USING HYBRID FILTERS R.Saravanakumar 1#, S.Amritha 2#

Comparison of Control Algorithms for Shunt Active Filter for Harmonic Mitigation

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter


Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

Single Phase Shunt Active Filter Simulation Based On P-Q Technique Using PID and Fuzzy Logic Controllers for THD Reduction

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Shunt Active Power Filter for Compensation of System Harmonics

Universal power quality conditioner

Load Compensation Performance of DSTATCOM with Hysteresis and Adaptive Hysteresis Current Controllers in Distribution Systems

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Power Factor Improvement Using a Three Phase Shunt Active Power Filter

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

Compensation of Harmonics Power by using Shunt Active Filter

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters P. Salmerón and S. P. Litrán

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

Enhancement of Power Quality using D-Statcom Fed Induction Motor Drive

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Literature Review for Shunt Active Power Filters

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

Transcription:

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction Anju Yadav 1, K. Narayanan 2, Binsy Joseph 3 1, 2, 3 Fr. Conceicao Rodrigues College of Engineering, Mumbai, India Abstract: Most of the power quality issues in power system are due to non-linear loads. The nonlinear load draws non-sinusoidal current from the AC mains which causes load harmonics and increases reactive power leading to pollution in power system. Shunt Active Power Filter (APF) has proven to be effective in improving power quality of distribution network. It compensates load current harmonics and reactive power simultaneously. The working of APF depends on its control strategy which includes generation of compensating reference current and generation of proper gating signal to make APF inject this reference current. This paper presents Sinusoidal current control (SCC) strategy for controlling the operation of shunt APF under balanced and unbalanced source voltage condition. This control strategy is based on instantaneous Reactive Power Theory (IRPT) and contains a positive sequence detector for detecting fundamental positive sequence component of input signal. The shunt APF contains a PWM current controlled voltage source inverter which is connected at the point of Common Coupling (PCC). The gating signal of VSI is derived from hysteresis band current controller (HBCC) and capacitor voltage is kept constant using a PI controller. Keywords: Shunt Active Power Filter (APF), Sinusoidal Current Control (SCC), Instantaneous Reactive Power Theory (IRPT), Hysteresis Band Current Controller (HBCC), Point of Common Coupling (PCC). 1. Introduction Power quality problems due to nonlinear load have been drawing lot of attention these years. The nonlinear load draws non-sinusoidal current from the AC mains leading to harmonics. These harmonics increases losses, causes overheating of equipment and reduces power factor as well. Hence, it is necessary to improve the power quality of the system. Filters are generally used for this purpose. Passive filters due to its tuning and resonance problems are not much used. APF contains power electronic switch and therefore does not have tuning problem. Among different topologies of APF, Shunt APF [1] is widely used for improving the power quality because of its ability to compensate current harmonics and reactive power simultaneously. 2. Shunt APF The shunt APF reduces load current harmonics by injecting equal but opposite harmonic compensating current. Figure 1 shows the circuit diagram of three phase three wire shunt APF. The currents i a, i b, i c are the source currents of phase A, B, C respectively. The point of common coupling (PCC) is the point at which the APF is connected in parallel to the load. i fa, i fb, i fc are the filter currents which are generated by the VSI using HBCC. i ca, i cb, i cc are the compensating currents found using SCC algorithm. L f is the filter inductance which is used for commutation purpose. Figure 1: Three phase three wire shunt APF The VSI is a three leg VSI having six IGBTs and a capacitor on the DC side. This capacitor is used as energy storage device to maintain voltage V dc at dc side of VSI. Control block represents the control algorithm for generating required gating pulses for VSI. Nonlinear load consist of a three phase diode bridge rectifier whose input is connected to three phase supply and output is connected to RL load. 3. Control Strategy of Shunt APF The performance of the APF strongly depends on the control strategy. The control strategy involves generation of compensating reference currents and then generating proper gating signals to three phase VSI. For the purpose of generating compensating currents SCC technique [4] is used. Paper ID: SUB156959 2128

3.1. Sinusoidal Current Control Strategy International Journal of Science and Research (IJSR) This strategy is based on IRPT also known as pq theory [4]. It involves clarke s transformation which transforms source voltage and load current from a-b-c coordinate to 0-α-β coordinate.the SCC strategy makes APF to compensate the current of non-linear load by forcing the compensated source current to become sinusoidal. In order to do so, the shunt APF compensates all harmonic components as well as the fundamental component that differs from the fundamental positive sequence current and to get the fundamental positive sequence component this control uses a positive sequence detector. Thus even if the voltage at the PCC is nonsinusoidal or unbalanced, it will not affect the system. The fundamental positive sequence voltage is then transformed to α-β coordinate using clarke transform, which is used for power calculation. A low pass 5 th order butterworth filter of cut off frequency equal to 50Hz is used to extract the dc component of power which is then subtracted from total power to get the oscillating power. These powers are used to get the compensating current in α-β coordinate which is converted to a-b-c coordinate using inverse clarke transform. The voltages v a, v b, v c are the fundamental positive sequence voltage of each phase obtained from positive sequence detector. These voltage and current can be used to find the real and reactive power in α-β coordinate. where, p is the real power and represents the total energy flow per time in the three-wire three-phase system, in terms of αβ components; q is the imaginary power and gives the measure of the quantity of power that flows in each phase without transporting energy at any instant. The real and imaginary power can be divided into its average and oscillating components. P = + q = The oscillating powers and are the undesirable power due to harmonic component in the load current. Using filter the compensating power p c and q c can be extracted which is used to find the compensating reference current (i ca, i cb, i cc ) using inverse Clarke transform. In order to make sure that only constant real power flows between source and the load, the power components which are needed to be compensated are, and. Where i ca, i cb, i cc are the required compensating currents. Figure 2: Block diagram of reference current extraction using SCC algorithm Figure 2 represents the complete block diagram of SCC algorithm. p loss represents the active power difference between source and load when the load changes. In order to compensate this difference capacitor is used. The peak value of the reference current must be adjusted proportionally to change the active power drawn from the source. This active power charged / discharged by the capacitor compensates the active power consumed by the load. PI controller is used to keep the capacitor voltage V dc constant and equal to reference voltage V ref. Figure 3 shows the block diagram of positive sequence detector which contains a PLL block. PLL block determines the auxillary currents i α and i β in α-β coordinate at fundamental frequency by continuously tracking the fundamental frequency of measured voltage. The source voltages are first transformed to α-β coordinates using Clarke transform. The V α and V β components and auxiliary currents i' α and i' β (produced from the PLL-synchronizing circuit) are used to calculate the auxiliary powers p' and q'. The auxiliary real and reactive power is computed as follows p'= V α i' α + V β i' β q'= V β i' α - V α i' β The auxiliary powers p' and q' are passed through fifth order Butterworth low pass filter with cut off frequency equal to 50 Hz for eliminating the higher frequency components. The average auxillary power obtained is used to find the fundamental positive sequence voltage as shown in fig.3 Where, v αβ 2 = v α 2 + v β 2 Paper ID: SUB156959 2129

Line to line source voltage Vs is 200 V (rms); System frequency (f) is 50 Hz; Source impedance of R S, L S is 0.1 Ω; 0.1 mh respectively; Filter inductance Lc is 6.5 mh; Diode rectifier R L, L L load: 10 Ω; 14 mh respectively; Unbalanced source voltages for phase A, B, C are: Va = 200 Ω, Vb = 180 Ω, Vc= 210 Ω respectively; DC side capacitance (C DC ) is 3 mf; Reference voltage (V dc, ref ) is 400V. A. System without Shunt APF under balanced source voltage condition Figure 3: Positive Sequence Detector block diagram 3.2 Generation of Gate Pulses Once the compensating reference currents are obtained the next step is to give proper pulses to the VSI so that the filter injects the compensating reference current which is nothing but the load harmonic current. HBCC generate pulses using Hysteresis band PWM technique. It is an instantaneous feedback current control method of PWM where the actual current continually tracks the reference current within a specified hysteresis band. Figure 5: Souce voltage waveform Figure 6: Souce current waveform Figure 4: Hysteresis Band Current Control The hysteresis current controller gives output pulses to the inverter according to following rule If i ref i act < i than keep the output pulse at the same state If i ref i act > i than the output pulse goes at the high state If i ref i act < - i than the output pulse goes at the low state Where i is hysteresis band limit, i ref is the reference current and i act is the actual filter current. Thus if the difference between the reference and the actual current is within the hysteresis band the pulse is in same state and if it goes beyond Hysteresis band then the pulse state changes forcing the current to be within hysteresis limit. Figure 7: FFT Analysis of Souce Current (THD=18.85%) B. System with Shunt APF under Balanced source voltage condition 4. Simulation Results The Shunt APF model is simulated in MATLAB/SIMULINK under balanced and unbalanced source voltage condition. The System parameters used are: Figure 8: Souce voltage waveform Paper ID: SUB156959 2130

Figure 9: Souce current waveform Figure 13: Souce current waveform Figure 10: Filter Current waveform Figure 14: FFT Analysis of Souce Current (THD= 18.45%) D. System with Shunt APF under Unbalanced Source Voltage Condition Figure 11: FFT Analysis of Souce Current (THD=3.65%) When the filter is not being used, the source current is highly distorted with THD equal to 18.85% (figure 6). As seen from the FFT analysis (figure 7), the source current contains a high percentage of 5 th and 7 th harmonic. Figure 15: Souce Voltage waveform By using filter the THD is reduced from 18.85% to 3.65% (figure 11). Figure 10 shows the current injected by the filter which is nothing but the harmonic current. Since this harmonic current is injected by filter, the source current is almost sinusoidal. C. System without Shunt APF under Unbalanced Source Voltage Condition Figure 16: Souce current waveform Figure 12: Souce voltage waveform Figure 17: Filter current waveform Paper ID: SUB156959 2131

Figure 18: FFT Analysis of Souce Current (THD= 4.92%) When the source voltage is unbalanced the distortion increases, but since the shunt APF contains positive sequence detector the THD is reduced to 4.92% (figure 18). The simulation results obtained are summarized through table 1 and table 2. As shown in table 1 and 2 the power factor is also improved and is very close to unity due to reduction in harmonics. Table 1: Simulation Result for Balanced Voltage Condition Parameter Values without Shunt APF Values with Shunt APF Is(THD) 18.85% 3.65% P.f 0.7 0.98 Table 2: Simulation Result for Unbalanced Voltage Condition Parameter Values without Shunt APF Values with Shunt APF Is(THD) 18.45%, 20.8%, 17.6% 4.92% P.f 0.67 0.9 5. Conclusion This paper presented shunt APF based on SCC algorithm for reducing current harmonics injected by nonlinear RL load under balanced and unbalanced source voltage condition. Shunt APF allows compensation of current harmonics and unbalance along with correction of power factor. SCC algorithm guarantees sinusoidal source current even if the source voltage is unbalance because of the presence of positive sequence detector which extracts the fundamental positive sequence component of input voltage. Therefore even if the voltage at PCC is unbalanced, it will not affect system s performance. References [1] Bhim Singh, Kamal Al-Haddad and Ambrish Chandra. A Review of Active Filters for Power Quality Improvement IEEE Transaction on industrial electronics,vol. 46, No. 5, October 1999. [2] Joao Afonso, Carlos Couto, Julio Martins, Active Filters with Control Based on the p-q Theory IEEE Industrial Electronics Society Newsletter vol. 47, nº 3, Sept. 2000, ISSN: 0746-1240, pp. 5-10 [3] Leszek S. Czarnecki, Instantaneous Reactive Power p-q Theory and Power Properties of Three-Phase Systems IEEE Transactions on Power Delivery, Vol. 21, No.1, Jan. 2006, pp. 362-367. [4] H. Akagi, E. Watanabe and M. Aredes, Instantaneous Power Theory and Applications to Power Conditioning, IEEE Press Series on Power Engineering, 2007. [5] V. F. Corasaniti, M. B. Barbieri, P. L. Arnera, M. I. Valla Comparison of Active Filters Topologies in Medium Voltage Distribution Power Systems Power and Energy Society General Meeting- Conversion and delivery of Electrical Energy in the 21 century, 2008 IEEE. [6] Gabrio Superti-Furga, Grazia Todeschini, Discussion on Instantaneous p-q Strategies for Control of Active Filters, IEEE tansaction on industrial electronics, Vol. 23, No. 4, July 2008. [7] Reyes S. Herrera, Patricio salmeron, Instantaneous reactive power theory: A reference in the nonlinear loads compensation IEEE tansaction on industrial electronics, vol-56, no-6, june 2009. Paper ID: SUB156959 2132