PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

Similar documents
Utility Interconnection and System Protection

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

KENYA ELECTRICITY GENERATING COMPANY LTD

System Protection and Control Subcommittee

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

BUS2000 Busbar Differential Protection System

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Ground Fault Location. Turbo Sleuth. Instruction Manual

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Grounding Recommendations for On Site Power Systems

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Table of Contents. Introduction... 1

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Data Isolation Cards. 2-Wire HDSL/56KBS Isolation Card P Wire HDSL/56KBS Isolation Card P30050

American Electrical Institute

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

ELECTRICAL POWER ENGINEERING

2015 Relay School Bus Protection Mike Kockott March, 2015

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

Protection of Electrical Networks. Christophe Prévé

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Babak Enayati National Grid Thursday, April 17

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Transformer Protection

Single Line Diagram of Substations

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Transformer Protection

Specialists in HV and MV test and diagnostics. Testing in Substations

3. COMBINED TRANSFORMERS Oil-paper insulation

VI 3 - i TABLE OF CONTENTS

high RESISTANCE GROUNDING SYSTEM the power to protect SLEUTH Instruction Manual C-408EM

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

TABLE OF CONTENT

Upgrading Your Electrical Distribution System To Resistance Grounding

Industrial Electrician Level 3

Power Processor - Series 700F 10KVA to 150KVA

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

2014 NEC Changes Part 1

CP CU1. Coupling unit for line and ground testing

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Power systems Protection course

INTELLIMETER REGISTER

Unit 2. Single Line Diagram of Substations

2 Grounding of power supply system neutral

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Power Plant and Transmission System Protection Coordination Fundamentals

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Webinar: An Effective Arc Flash Safety Program

Generator Protection GENERATOR CONTROL AND PROTECTION

Transmission Facilities Rating Methodology for Florida

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

7. INSPECTION AND TEST PROCEDURES

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

N. TEST TEST DESCRIPTION

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Back to the Basics Current Transformer (CT) Testing

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SYNCHRONISING AND VOLTAGE SELECTION

Wisconsin Contractors Institute Continuing Education

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Impact of Incipient Faults on Sensitive Protection

Education & Training

Provisional Specifications

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Design of Differential Protection Scheme Using Rogowski Coil

This document covers common questions concerning the design of an effectively grounded system.

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

Protective Relays Digitrip 3000

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

CONTENTS. 1. Introduction Generating Stations 9 40

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

N. TEST TEST DESCRIPTION

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

How to maximize reliability using an alternative distribution system for critical loads

Substation: From the Outside Looking In.

ABB CUSTOMER WORLD, MARCH 13-16, 2017 Sensors in Critical Applications Ron Pate, Product Manager, Instrument Transformers and Sensors

TRAINING Learning and Training application on site. QUALIFYING Evaluation of quiz Knowledge Validation To learn required skills

Southern Company Interconnection Requirements for Inverter-Based Generation

PD300. Transformer, generator and motor protection Data sheet

Primary Metering. What is Primary Metering?

Installation Instructions and Reference Handbook. Installation instructions

The Advantages and Application of Three Winding Transformers

Short Circuit Current Calculations

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Transcription:

PC57.13.3 IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

OUTLINE Scope References Need for grounding; Warning Definition of Instrument transformers Grounding secondary circuits Grounding at a single location Conductor size for connecting to ground

Scope The scope of the guide includes the grounding practices presently used and the practices that were not previously reported. Specifically, the issue of the grounding of cases of electronic transducers is addressed.

Covers The practices described in this standard apply to all instrument transformers, including capacitive voltage transformers and linear couplers, irrespective of primary voltage or whether the primary windings are connected to, or are in, power circuits or are connected in the secondary circuits of other transformers as auxiliary cts or vts.

Does not cover This guide does not discuss the grounding of some applications. For example, grounding of gas insulated substations and metal clad switchgear is not discussed in this guide; the reader will find these topics addressed in reference [9] listed in clause 2. The grounding of circuits of core-balance CTs is also not discussed in this guide. The reader can find this information also in reference [9] listed in clause 2. Another issue that is not discussed in this guide is the practice of using separate safety and control grounds. For discussion on this topic, the reader is directed to reference [12] listed in clause 2.

References [1] NFPA 70-2002, National Electricity Code (NESC ) [2] ANSI C2-2002, National Electrical Safety Code (NESC ) [3] C37.103-2004, IEEE Guide for Differential and Polarizing Relay Circuit Testing [4] C57.13.1-1981 (Reaffirmed 1999), IEEE Guide for Field Testing of Relaying Current Transformers [5] C37.92-2004, IEEE Trial Use Standard for Low Energy Analog Signal Inputs to Protective Relaying

References [6] C62.92-2000, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems [7] Std. 80-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142-1991, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems [9] Std. 242 *2001, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems [10] Std. 518-1982 (R1996), IEEE Guide for the Installation of Electrical Equipment to Minimize Electrical Noise Inputs to Controllers from External Sources

References [11] Std. 525-1992, IEEE Guide for the Design and Installation of Cable Systems in Substations [12] Std. 665-1995, IEEE Guide for Generating Station Grounding [13] Std. 1050-1996, IEEE Guide for Instrumentation and Control Equipment Grounding in Generating Stations [14] Std. 1100-1999, IEEE Recommended Practice for Powering and Grounding Electronic Equipment [15] Std. 1143-1994 (Reaffirmed 1999), IEEE Guide on Shielding Practice for Low Voltage Cables

Need for Grounding Secondary Circuits To protect equipment connected to the circuits To Protect personnel who might come into contact with the equipment How the problem manifests When secondary circuit is not grounded When a case is not grounded Voltage due to charge accumulation on an ungrounded secondary circuit or case

Warning Grounding of secondary circuits is an issue of safety of personnel and equipment connected to the secondary circuits. The reader is urged to consider it seriously and follow the stipulations of relevant standards and ensure that the stipulations of the National Electrical Code [1] and the National Electric Safety Code [2] are always adhered to.

Warning Article 90.2 (A) of National Electrical Code [1] lists the installations that are covered by the Code [1] and Article 90.2 (B) lists the installations that are not covered by the Code. For immediate reference of the readers, Article 90.2 of National Electrical Code [1] is reproduced in Annex C.

Grounding of Instrument Transformer Secondary Circuits Definition of a secondary circuit for the purposes of the guide Issues Grounding at a single location Minimum size of the grounding conductor

Issues Grounding at a single location Voltage at different locations of the physical ground and circuits connected to ground is different when fault currents flow Convenience of testing a secondary circuit Problem with forming a common neutral of more than one instrument transformers and then grounding the neutral bus Isolation of all secondary circuits from ground

Issues Recommended point of grounding switchboard or relay panel Grounding unused secondary windings Grounding examples

Grounding 3 4 Wire VT Circuits

Grounding 3 3 Wire VT Circuits PA OPEN DELTA PB PC PA PB CONNECTIONS TO GROUND BUS AT SWITCHBOARD (#12 AWG CU MINIMUM) WYE PC NEUTRAL NOT BROUGHT OUT GROUND ISOLATING CONNECTION

Grounding unused CTs

ISSUES Minimum size of grounding conductor 12 AWG required by NESC

TYPICAL APPLICATIONS VT circuits Voltage provided from distribution transformers

Using Voltage from a Distribution Transformer

Generator Neutral Grounding Transformer TO GEN NEUTRAL R PG PN TO RELAYS, OSCILLOGRAPH, ETC. GROUND ISOLATING CONNECTION STATION GROUND MAT SWITCHBOARD GROUND

Generator Neutral Grounding Transformer TO GEN NEUTRAL R OPTIONAL CONNECTION PG TO RELAYS, OSCILLOGRAPH, ETC. PN STATION GROUND MAT CENTER TAP GROUND SOMETIMES USED SO THAT ACCIDENTAL GROUND ON PG WILL NOT COMPLETELY DISABLE GENERATOR GROUND PROTECTION

Generator Neutral Grounding Transformer

Generator Grounding Transformer R TO RELAYS, OSCILLOGRAPH, ETC. GROUNDING TRANSFORMER

Basic Synchroscope Circuit PB 25 SCOPE 25 PB CKT. 2 RUN INC CKT. 1 PN PN GROUNDING ISOLATION CONNECTION

Synchroscope with Multiple Incoming Circuits

Synchroscope with Multiple Incoming and Running Circuits PB 25-2 25-2 PB PB 25-1 SCOPE 25-1 PB CKT. 4 CKT. 3 RUN INC CKT. 1 PN 25-1 25-1 PN CKT. 2 PN 25-2 25-2 PN GROUNDS NOT NECESSARILY ELECTRICALLY CLOSE GROUNDING ISOLATION CONNECTION

Synchroscope with Multiple Incoming and Running Circuits using Isolating Transformers PB 25-2 25-2 PB PB 25-1 SCOPE 25-1 PB CKT. 4 CKT. 3 RUN INC CKT. 1 CKT. 2 PN PN PN PN 1-1 ISOLATING TRANSFORMERS GROUNDING ISOLATION CONNECTION

Synchroscope with Synchronizing Lights SYNCHRONIZING LIGHTS PB 25 25 PB CKT. 2 RUN INC CKT. 1 PN 25 SCOPE OR SYNC-CHECK RELAY GROUNDS SHOULD BE ELECTRICALLY AS GROUNDING CLOSE AS PRACTICAL ISOLATION CONNECTION THIS CONTACT PERMITS THE TWO VOLTAGE CIRCUITS TO BE SEPARATELY GROUNDED PN

Grounding Distribution Station with one used for Instrumentation SWITCHBOARD TERMINALS PN GROUND ISOLATION CONNECTION G(N) NOTE: BECAUSE OF THE TWO GROUNDS ON G(N), IT SHOULD BE SUFFICIENTLY HEAVY SO THAT STATION GROUND FAULTS WILL NOT CAUSE DAMAGE TO G(N)

Grounding 1 CT Circuit CP BURDEN CN

Grounding 1 CT Circuit CP BURDEN CN GROUND ISOLATION CONNECTION

Grounding 3 CT Circuit

Grounding 3 CT Circuit

Grounding V Connected CT Circuit

Delta-Delta Connected CTs in a Differential Protection Relay

Delta-Wye Connected CTs in a Differential Protection Relay A B C C B A SWITCHBOARD TERMINALS DIFF. RELAYS CBC CBC CBB CBB CBA CBA GROUND ISOLATION CONNECTION

Percentage Bus Differential Scheme TO CTS ON CKT. 3 CD3A CD3B CD3C SWITCHBOARD TERMINALS RESTRAIN T OPERATE PHASE A CD3N CD2A TO CTS ON CKT. 2 CD2B CD2C PHASE B CD2N CKT. 1 A B C CD1A CD1B CD1C PHASE C CD1N GROUND ISOLATION CONNECTION

Ring Bus or Breaker and a Half Scheme TO METERS, RELAYS, ETC. TERMINALS AT CT LOCATION TERMINALS AT CT LOCATION GROUND ISOLATING CONNECTION CONTROL HOUSE GROUND BUS SWITCHBOARD TERMINALS (MAY BE SLIDING LINK TYPE TO FACILITATE TESTING)

Multiple use of CTs 51-C 51- A 51-B 51-C 51-B 51- A

Grounding of Cases Grounding metallic conductive cases Insulated cases with conductive internal parts Ungrounded metallic cases or internal parts Protected by suitable barriers or elevated to prevent contact if operating voltage exceeds 1,000 V

Exceptions to Grounding If the primary windings of instrument transformer circuits are connected to circuits of less than 1000 V with no live parts or wiring exposed or accessible to other than qualified persons, the circuits may not be grounded.

Exceptions to Grounding For instrument transformer cases, the cases or frames of CTs may not be grounded if the primary windings are not over 150 V to ground and are used exclusively to supply current to meters.

Exceptions to Grounding Cases of instruments, meters, and relays operating at less than 1000 V on switchboards having exposed live parts on the front of panels are not usually grounded. Mats of insulating rubber or other suitable floor insulation is provided where the voltage to ground exceeds 150 V.

Exceptions to Grounding Instruments, meters, and relays, whose currentcarrying parts operate at voltages to ground of 1000 V and over, are isolated by elevating them or protecting them by suitable barriers, grounded metal or insulating covers, or guards. In such situations, the cases are not usually grounded.

Grounding of Low-Energy Transducers

Grounding of Low-Energy Transducers

Grounding of Low-Energy Transducers

Annex A Grounding of shielded cables To consider current carrying capacity of the shield Cables with spiral design shields are grounded at both ends Cables with drain wires are grounded at one end

Annex A CTs installed over shielded cables

Annex B IEEE Standards reviewed by the WG

Annex C Clause 90.2, Scope of National Electricity Code Type of installations covered by the Code Type of installations not covered bye the Code Special permission

ANNEX D Survey of Grounding Practices Approximately one-third of the respondents do not ground voltage transformers at the first point of use as described in the Guide. The Working Group is of the opinion that grounding at the first point of use is better than grounding at other locations. Almost all respondents indicated that current transformers are grounded at the first point of use as described in the Guide.