Photovoltaic System Based Interconnection at Distribution Level With Different Loads

Similar documents
FFT Analysis of THD in Distribution System with Grid Connected RES

Power Quality Improvement with Renewable Sources for Non-Linear Load with PI and Fuzzy Controller

Enhancement of Power Quality using D-Statcom Fed Induction Motor Drive

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

Power Control and Quality Management in DG Grid Interfaced Systems

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Renewable Energy Source Compensator for Power Quality Issues Using Active Power Filter in Grid

Matlab/Simulink Modeling of Novel Hybrid H-Bridge Multilevel Inverter for PV Application

Multilevel Inverter based Photovoltaic System with Distributed Generation System Fed Induction Motor Drive VENKATA V ANJANEYULU B 1, G.

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

A New Control Strategy for Three- Phase Inverter Applied To Induction Motor of Micro Grid

Power Quality Improvement of Grid Interconnected Distribution System

Control of Grid Interconnection of Renewable Energy Resources at Distribution Level with Power-Quality Improvement

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

2020 P a g e. Figure.2: Line diagram of series active power filter.

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

ISSN Vol.05,Issue.01, January-2017, Pages:

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

A Five Level Inverter for Grid Connected PV System Employing Fuzzy Controller

Mitigation of Voltage Sag, Swell and Load Hamonics by the Combined Opertation of Series APF and Solar System

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

Improving the Power Quality by Four Leg VSI

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Fuzzy Logic Based MPPT for Wind Energy System with Power Factor Correction

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

The Analysis Of Grid Interconnected System At Distribution Level Using Renewable Energy Resources

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Power Quality improvement of a three phase four wire system using UPQC

Multilevel Inverter for Grid-Connected PV SystemEmploying MPPT and PI Controller

Application of Model Predictive Control in PV-STATCOM for Achieving Faster Response

MMC based D-STATCOM for Different Loading Conditions

PMSM Drive Based D-STATCOM in Combination with Renewable Energy Sources to Enhance Power Quality

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING St. JOHNS COLLEGE OF ENGINEERING & TECHNOLOGY YERRAKOTA, YEMMIGANUR, KURNOOL, (A.P.

Available online at

Modelling of Five-Level Inverter for Renewable Power Source

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Application of Fuzzy Logic Controller in Shunt Active Power Filter

A Single Phase Multistring Seven Level Inverter for Grid Connected PV System

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

Indirect Current Control of LCL Based Shunt Active Power Filter

Modelling and Simulation of High Step up Dc-Dc Converter for Micro Grid Application

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

Resonant Inverter. Fig. 1. Different architecture of pv inverters.

Power Quality Improvement in Wind Energy Conversion System of Grid Interfacing Inverter using Hysteresis Band Current Controller

Simulation Study of PWM Techniques for Voltage Source Converters

Modular Grid Connected Photovoltaic System with New Multilevel Inverter

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Power Quality Improvement Wind/PV Hybrid System by using Facts Device

High Efficiency Single Phase Transformer less PV Multilevel Inverter

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Review on Shunt Active Power Filter for Three Phase Four Wire System

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

GRID CONNECTED HYBRID SYSTEM WITH SEPIC CONVERTER AND INVERTER FOR POWER QUALITY COMPENSATION

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

Photovoltaic Based Single Phase Grid Connected Transformer Less Inverter

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Delhi Technological University (formerly DCE) Delhi-42, India

An experimental Study of an Improved Active Frequency Drift Anti-Islanding Method for PV Application

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

SIMULATION, DESIGN AND CONTROL OF A MODIFIED H-BRIDGE SINGLE PHASE SEVEN LEVEL INVERTER 1 Atulkumar Verma, 2 Prof. Mrs.

CURRENT HARMONICS REDUCTION IN 3 PHASES 4 WIRE SYSTEM USING HYBRID FILTERS R.Saravanakumar 1#, S.Amritha 2#

SVPWM Buck-Boost VSI

Control of grid connected inverter system for sinusoidal current injection with improved performance

Three-Phase Modular Cascaded H-Bridge Multilevel Inverter with Individual MPPT for Grid-Connected Photovoltaic Systems

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER OF UPQC

Phase Shift Modulation of a Single Dc Source Cascaded H-Bridge Multilevel Inverter for Capacitor Voltage Regulation with Equal Power Distribution

A Pv Fed Buck Boost Converter Combining Ky And Buck Converter With Feedback

ADVANCES in NATURAL and APPLIED SCIENCES

MPPT WITH A NOVEL MODULAR CASCADED H-BRIDGE MULTILEVEL PV INVERTER FOR GRID-CONNECTED APPLICATIONS USING FUZZY

Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Grid disturbances

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Harmonics Elimination Using Shunt Active Filter

IJOSTHE ISSN: Volume 5 Issue 3 April

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

International Journal of Advance Research in Engineering, Science & Technology

A Novel 2 - Stage Power Conditioning System for PV Power Generation Using FPGA

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

International Journal Of Global Innovations -Vol.6, Issue.II Paper Id: SP-V6-I2-P05 ISSN Online:

International Journal of Advance Engineering and Research Development THREE PHASE 19 LEVEL MODULAR MULTI LEVEL INVERTER FOR RENEWABLE ENERGY RESOURCE

Simulation of Single Phase Grid Connected Photo Voltaic System Based On PWM Control Of Switched Boost Inverter For DC Nanogrid Applications

Modeling of Single Stage Grid-Connected Buck-Boost Inverter for Domestic Applications Maruthi Banakar 1 Mrs. Ramya N 2

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Transcription:

Research Article International Journal of Current Engineering and Technology ISSN 2277-4106 2013 INPRESSCO. All Rights Reserved. Available at http://inpressco.com/category/ijcet Photovoltaic System Based Interconnection at Distribution Level With Different Loads D.Jagadish Ȧ* anda.srinivas Ȧ Ȧ Department of Electrical and Electronics Engineering, Anurag Group of Institutions, Andhra Pradesh, India Accepted 25 December 2013, Available online 30 December 2013, Vol.3, No.5 (December 2013) Abstract In this paper grid is interconnected to Renewable Energy source i.e., Hybrid interconnection of WIND ENERGY & the PV cell. The 3-phase, 4-wire active power filter (APF) which is used as inverter in this paper The inverter is used to act as active power filter (APF), at different voltage i.e., in order to inject the voltage from RES into the grid to reduce the power quality problem to compensate the harmonic content in the total The active power filter is of 4-leg in which 3-legs are used to compensate at the 3-phases & the 4th leg is used to compensate the neutral current. A set of linear and Non-linear loads is used to study the performance of the system with some delay time to study waveforms both in linear & Non-linear loads acting simultaneously or instantaneously. The MATLAB/SIMULATION model of the proposed system & the waveforms is illustrated. Keywords: Grid, RES, APF, Linear and Non-Linear loads. 1. Introduction 1 Renewable energy sources such as Photo Voltaic cell and the wing energy is integrated at the distribution level for the distribution generation. The use of renewable energy sources plays important role on the present generation as it play important role in the power The need to use the renewable energy sources like wind energy and the photo voltaic power to integrate into power system is to make it possible to minimize the environmental impact on conventional plant. The integration of wind energy and solar energy into existing power system presents technical challenges and that requires consideration of power quality problems like voltage instability and harmonic distortions etc. Power quality is a term that means different things to different people. Institute of Electrical and Electronic Engineers (IEEE) Standard IEEE1100 defines power quality as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. As appropriate as this description might seem, the limitation of power quality to Sensitive electronic equipment might be subject to disagreement. The non-linear load current harmonics may result in voltage harmonics and can create a serious PQ problem in the power system network. Active power filters (APF) are extensively used to compensate the load current harmonics and load unbalance at distribution level. This results in an additional hardware cost. However, in this paper authors *Corresponding author:d.jagadish have incorporated the features of APF in the, conventional inverter interfacing renewable with the grid, without any additional hardware cost. Here, the main idea is the maximum utilization of inverter rating which is most of the time underutilized due to intermittent nature of RES. It is shown in this paper that the grid-interfacing inverter can effectively be utilized to perform following important functions: 1) transfer of active power harvested from the renewable resources (wind, solar, etc.); 2) load reactive power demand support; 3) current harmonics compensation at PCC; and 4) current unbalance and neutral current compensation in case of 3-phase 4-wire Fig: 1 Schematic of the proposed renewable energy 2079

Moreover, with adequate control of grid-interfacing inverter, all the four objectives can be accomplished either individually or simultaneously. The PQ constraints at the PCC can therefore be strictly maintained within the utility standards without additional hardware cost. The paper is arranged as follows: Section II describes the system under consideration and the controller for grid-interfacing inverter. RES study is presented in Section III. Control circuit is discussed in Section IV, MATLAB/SIMULATION results are shown in Section V and, finally, Section VI concludes the paper.the block diagram of the proposed renewable energy system is given below: the linear & nonlinear loads. The harmonics present in the current is reduced at the PCC, to maintain the source unaffected at the source side. Renewable Energy Source A PV cell is the basic structural unit of the PV module that generates current carriers when sunlight falls on it. The power generated by these PV cell is very small. To increase the output power the PV cells are connected in series or parallel to form PV module. The equivalent circuit of the PV cell is shown in fig: 3. Fig: 3 Equivalent circuit of the PV cell. The main characteristics of the PV cell are given by: * ( ( ) ) + Fig: 2Block diagram of the proposed Renewable energy System Description The above Fig.1 shows the schematic of the proposed RES interconnected to the grid, in which Grid, Distribution transformer, set of loads (Linear & Non-Linear), Control Circuit (DSP control & Hysteresis controller), RES & 4- leg inverter are connected as shown. The Voltage is supplied from the grid is connected to the Delta-Star distribution transformer in order to distribute to different loads connected to it i.e., Commercial loads, Industrial loads & House hold loads. A capacitor is placed across the renewable energy sources to regulate the DC voltage. As the voltage from the RES may not be constant throughout the day so, in order to maintain the voltage constant a capacitor is used and acts as voltage regulator. The Digital signal processing control (DSP) is used to generate the reference currents (I a *, I b *, I c * ) from the voltages from the source &propotional integral controller is used to generate the imaginary current from the DC voltage by comparing with the same voltage of the DC voltage, which in turn connected to the external hysteresis control board which will compare the reference currents & actual currents i.e., source currents (I a, I b, I c ). The figure: 2 shows the block diagram of the proposed renewable energy system in which grid is fed to the Non- Linear load. The 3-phase 4-leg inverter connected to the PV & Wind energy system in order to supply the DC source gird to compensate the current harmonics at the Point of Common Coupling (PCC). At the point of common coupling the voltage s maintained constant in this scheme & the current behavior is changing with respect to ( ) [ ] ( ) [ ( )] Where, I and V- Cell output current and voltage; Io- Cell reverse saturation current; T- Cell temperature in Celsius; K- Boltzmann s constant; q- Electronic charge; Ki- short circuit current/temperature coefficient; G- Solar radiation in W/m2; Gn- nominal solar radiation in W/m2; Eg- energy gap of silicon; Io,n- nominal saturation current; Tn- nominal temperature in Celsius; Rs- series resistance; Rsh- shunt resistance; α- ideality factor between 1.0 to 1.5; Ipv- light generated current; Fig: 4 Current versus voltage at constant cell temperature T=25 0. 2080

The I-V characteristic of a PV module is highly non-linear in nature. This characteristics drastically changes with respect to changes in the solar radiation and cell temperature. Whereas the solar radiation mainly affects the output current, the temperature affects the terminal voltage. The IV characteristics of the PV module under varying solar radiation at temperature T=25 0 is shown in fig 4 Fig.5 shows the I-V characteristics of the PV module under varying cell temperature at constant solar radiation (1000 W/m 2 ). electricity. The wind turns the blades, which spin a shaft, which connects to a generator and makes electricity. Even though the cost of wind power has decreased dramatically in the past 10 years, the technology requires a higher initial investment than fossil-fueled generators. Although wind power plants have relatively little impact on the environment compared to fossil fuel power plants, there is some concern over the noise produced by the rotor blades, aesthetic (visual) impacts, and birds and bats having been killed (avian/bat mortality) by flying into the rotors. Most of these problems have been resolved or greatly reduced through technological development or by properly sitting wind plants. Control Circuit Fig. 5 Current versus voltage at constant solar radiation G = 1000 W/m 2. WIND ENERGY: The terms wind energy or wind power describe the process by which the wind is used to generate mechanical power or electricity. Wind turbines convert the kinetic energy in the wind into mechanical power. This mechanical power can be used for specific tasks (such as grinding grain or pumping water) or a generator can convert this mechanical power into electricity to power homes, businesses, schools, and the like. The control circuit is used to generate the triggering pulses for the 4-leg inverter to compensate the harmonic currents at the PCC. In the control circuit the DSP control, PI controller & the External hysteresis controller is placed. The multiplication of active current component (I m ) with unity grid voltagevector templates (U a, U b and U c ) generates the reference grid currents (I a *, I b * and I c * ). The reference grid neutral current is set to zero, being the instantaneous sum of balanced grid currents. The grid synchronizing angle obtained from phase locked loop (PLL) is used to generate unity vector template as. U a = Sin (θ) (1) U b = Sin (θ-120) (2) U c = Sin (θ-240) (3) Fig: 7 Block diagram representation of grid-interfacing inverter control. Fig: 6Shows the Wind Energy and Wind Power generated per year. Wind turbines, like aircraft propeller blades, turn in the moving air and power an electric generator that supplies an electric current. Simply stated, a wind turbine is the opposite of a fan. Instead of using electricity to make wind, like a fan, wind turbines use wind to make The instantaneous values of reference three phase grid currents are computed as Ia * = I m.u a (4) I b * = I m.u b (5) I c * = I m.u c (6) The neutral current, present if any, due to the loads connected to the neutral conductor should be compensated by forth leg of grid-interfacing inverter and thus should not be drawn from the grid. In other words, the reference current for the grid neutral current is considered as zero and can be expressed as I n * =0 (7) The reference grid currents (I a *, I b * and I c * ) are compared with actual grid currents (I a, I b and I c ) to compute the current errors as: I aerr = I a * -I a (8) 2081

I berr = I * b -I b (9) I cerr = I * c -I c (10) I nerr = I * n -I n (11) The difference between the reference current & the actual current give the resultant gating pulses to the inverter & it is given for the 8 switches using NOT gate so that the 8 switches act simultaneously for the Positive cycle & Negative cycle. Matlab/Simulation Circuits Fig: 12 Shows the MATLAB/SIMULATION model of the grid with control circuit with linear & Non-linear loads acting simultaneously Fig: 8The simulation model of the grid interfacing circuit without control circuit. Fig: 9Shows the waveform for the source voltage for the APF without control circuit. Fig: 13 Shows the control circuit to give triggering pulses to the inverter Fig: 10 Figure shows the waveform for the source current for the APF without control circuit. Fig: 14. Shows the waveform for the source voltage for the grid interfacing inverter which acts after time interval of 0.1 seconds Fig: 11 Figure shows the waveform for the load current for the APF without control circuit Fig: 15 Shows the waveform for the source current for the grid interfacing inverter & inverter acts after 0.1 seconds. 2082

Conclusion Fig: 16 Shows the load current waveform for the grid interfacing inverter which acts after 0.1 seconds Fig: 17 Shows the waveform for the inverter current which will acts after 0.1 seconds Fig: 18 Shows the power factor waveform for the grid interfacing inverter which attains unity power factor after 0.1 seconds Fig: 19Shows the total harmonic distortion for the grid interfacing inverter when the triggering pulses is not given to the inverter & the THD= 21.33% Fig: 20 Shows the total harmonic distortion for the APF when the triggering pulses are given to the inverter & the THD is reduced to 3.08%. This paper presents a novel control strategy for the existing system grid interfacing inverter to improve the power quality at point of common coupling (PCC) with 3- phase 4-leg inverter The grid interfacing inverter can be effectively utilized for power conditioning without affecting its normal operating of real power transfer. The grid-interfacing inverter with the proposed approach can be utilized to: i) inject real power generated from RES to the grid, and/or, ii) operate as a shunt Active Power Filter (APF). This approach thus eliminates the need for additional power conditioning equipment to improve the quality of power at PCC. The MATLAB/SIMULINK simulation model of the proposed system with hybrid connection of renewable energy sources (RES) is shown and validated. The control circuit is operated with phase lock loop (PLL), proportional integral controller (PI) and hysteresis controller which is used to generate the gating pulses for the 4-leg inverter. The proposed model is carried out for four different cases at load side, (i). Linear balanced load. (ii). Linear unbalanced load. (iii). Nonlinear balanced load. (iv). Nonlinear unbalanced load. When the power generated from RES is more than the total load power demand, the grid-interfacing inverter with the proposed control approach not only fulfills the total load active and reactive power demand (with harmonic compensation) but also delivers the excess generated sinusoidal active power to the grid at unity power factor. The total harmonic distortion (THD) is reduced to 3.08% from 21.33%. References Mukhtiar Singh, VinodKhadkikar, Ambrish Chandra, and Rajiv K. Varma (Jan 2011), Grid Interconnection of Renewable Energy Sources at the Distribution Level with Power-Quality Improvement Features IEEE Trans. on power delivery, vol. 26, no.1. J. P. Pinto, R. Pregitzer, L. F. C. Monteiro, and J. L. Afonso (2007), 3-phase, 4-wire shunt active power filter with renewable energy interface, presented at the Conf. IEEE Rnewable Energy & Power Quality, Seville, Spain. M. Calais, J. Myrzik, T. Spooner, and V. G. Agelidis (June 2002), Inverters for single-phase grid connected photovoltaic systems An overview, in Proc. 33th IEEE Power Electronics Specialists Conf. (PESC 02), Cairns, Australia. P. Rodríguez, J. Pou, J. Bergas, J. I. Candela, R. P. Burgos, and D.Boroyevich (Mar 2007), Decoupled double synchronous reference frame PLL for power converters control, IEEE Trans. Power Electron, vol. 22, no. 2,pp. 584 592. S. B. Kjaer, J. K. Pedersen, and F. Blaabjerg (Sept 2005), A review of single-phase grid-connected inverters for photovoltaic modules, IEEE Trans. Ind. Appl., vol. 41, no. 5, pp. 1292 1306. J. M. Carrasco, L. G. Franquelo, J. T. Bialasiewicz, E. Galván, R. C. P. Guisado, M. Á. M. Prats, J. I. León, and N. M. Alfonso (Aug 2006), Powerelectronic systems for the grid integration of renewable energy sources: A survey, IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 1002 1016. F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus (Oct 2006), Overview of control and grid synchronization for distributed power generation systems, IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398 1409. 2083