Current Standard Plates including Transmittal Letters are available on the web at:

Similar documents
SUBJECT: Standard Plate 9102 Turf Establishment Areas At Pipe Culvert Ends

SUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends)

Standard Plate 7036 is discontinued. It is replaced by Standard Plan Pedestrian Curb Ramp Details.

Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D

SUBJECT: Standard Plates 4132, 4155, Drainage Structures and Castings Info

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012)

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

Current Standard Plates including Transmittal Letters are available on the web at:

Standard Plate Sheer Reinforcement for Precast Drainage Structures has been updated upon recommendation of the Bridge Office.

Plate 8132A - Preformed Rigid PVC Conduit Loop Detector, is a new plate requested by OTST.

STANDARD DRAWINGS INDEX MODIFIED FOR CENTRAL REGION Revised August 6, 2018

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

Government Of Newfoundland & Labrador Municipal Water, Sewer And Roads Master Construction Specifications

Miscellaneous. Demolition

STANDARD BID ITEM NUMBERS

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY

CITY OF DANA POINT DEVELOPMENT REVIEW

Pipe Product Catalog Table of Contents

CITY OF VISTA STANDARD DRAWINGS

CITY OF VISTA STANDARD DRAWINGS

LETTING : CALL : 029 COUNTIES : GOODHUE

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

Ohio Department of Transportation Office of Roadway Engineering January 18, 2013

50.24 Type, Size and Location Plans for Culverts, Bridges and Culvert Bridges

REVISIONS INDEX 2016 ROAD & BRIDGE STANDARDS. September 2017 Revision Letter August 2017 Revision Letter February 2017 Revision Letter

STANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN

REVISIONS INDEX 2016 ROAD & BRIDGE STANDARDS

STANDARD DETAILS Crow Canyon Road San Ramon, CA Telephone: (925) Fax: (925)

City of Regina Standard Construction Specification SECTION 2999 LISTING OF ROADWAY STANDARD DRAWINGS

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1

E:\Wilmot\DGN\14018pp.dgn 3/11/2015 6:49:16 AM

SUPPLEMENTARY STANDARD DETAIL DRAWINGS

RAIL PANEL AT TRANSITION SECTION PLAN - POST DETAIL PLAN - TUBE SPLICE. Colorado Department of Transportation. Staff Bridge Branch

MINIMUM C/L RADII OF CURVATURE OF LOCAL ROADS IN SUBDIVISIONS

M I N N E S O T A D O T BID TABULATION SUMMARY JOB PAGE 1 ON 01/14/97 MINNESOTA PROJECT NO.S: DPI 015-8(021) DPI 015-8(022)

3. DESIGN SPECIFICATIONS

CITY OF SAN MARCOS ENGINEERING DIVISION

MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop

STORM M ANHOLE FOR 42" PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30"MAX 3 OR 3.5 PRECAST ECCENTIC CONC

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED:

Appendix C Construction Details

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)

Revised BRIDGE REPORT AND LAYOUT PAVEMENT STRUCTURE DESIGN CHAPTER VII UTILITIES CHAPTER VIII TRAFFIC CONTROL DEVICES

CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST

TYPE 4-C TYPE 6 TYPE 7 TYPE 8

Standard Details Index NWTP Improvements and MF System Installation

24" B B Joint X501 Joint See MARKINGS Note PCB-RXX-350-TL3 " X501 Y301 (Typ.) " A PLAN (reinforced casting option shown) A " dia. Hinge Bar (Typ.) NOT

CITY OF MUSKEGO DRAFTING STANDARDS

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

City of Massillon Site Plan Checklist

Anne Arundel County Dept. of Inspections and Permits Storm Drain Checklist

PLAN RATINGS & COMMON ERRORS TO WATCH FOR IN PLANS

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS

Survey Data and TOPO Checklist

CITY OF STOCKTON 2016 STANDARD PLANS AND SPECIFICATIONS PROPOSED REVISIONS

5/16" Flange nut. Bolt Keeper Plate (8" Sq. SYS.) (3) 1/2" x 3" Hex head connector zinc plated bolt w/ washers and nut. Anchor 3" sq. 7 Ga.

DELINEATOR REFERENCE POINT 200' TYPICAL SPACING (YELLOW DELINEATORS) END OF MERGE LANE TAPER DELINEATOR REFERENCE POINT

Manholes Table of Contents

OREGON DEPARTMENT OF TRANSPORTATION

SECTION MANHOLES

Project Name: County File No.: Checked by: For: Date:

Plan Preparation Checklist

Item 550 Chain Link Fence

SECTION 3 IMPROVEMENT PLAN REQUIREMENTS

Anti-Trust Statement

BRIDGE RAILING, 4 TUBE B-26-F POST DETAILS MICHIGAN DEPARTMENT OF TRANSPORTATION

STANDARD AND EXAMPLE DRAWINGS

SIGN MOUNTED BEACON SIG-027-A SINGLE SIGN MOUNTED FLASHING BEACON INSTALLED ON ONE WOOD POST DETAIL "A-1"

City of Beaumont. Public Works Engineering. Street Improvement Plan Checklist REV 4/18/16

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

Precast Concrete Box Culverts

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

C-M TMR Products Index

CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS

3. The PAC (Permit Application Center) will notify the design professional of plan review results.

The several methods for making linear measurements are quite simple and straightforward. They are described below:

Survey Requirements. Design Guidelines and Standards. June Office of the University Architect

SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS

CITY OF APACHE JUNCTION DEVELOPMENT SERVICES CIVIL ENGINEERING PLAN REVIEW CHECKLIST PROJECT: LOCATION:

SIGNALS AND LIGHTING FIELD GUIDE

Customer Connection Guide Updates Effective May 2017

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST

SECTION 9.00 AS-BUILT DRAWING REQUIREMENTS SUB-INDEX

Porter County Plan Commission

Engineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings

580 - NOISE BARRIERS OPSS 580 INDEX

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

Midwest Roadside Safety Facility

Town of Westlake Construction Plans Review Checklist

RECORD DRAWINGS REVISED TO CONFORM TO CONSTRUCTION RECORDS PROVIDED BY CONTRACTOR GMG BY DATE 11/13 CRS NO.

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

PROPOSED FIBER OPTIC CONDUIT INSTALLATION E. 50TH ST. AND S. COTTAGE GROVE AV. CHICAGO, ILLINOIS

SECTION G ESTIMATE OF QUANTITIES

Midwest Roadside Safety Facility

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006

Transcription:

MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (17-04) MANUAL: Standard Plates DATED: September 19, 2017 SUBJECT: Standard Plates 7102 and 8360 The following Standard Plate has been modified: 7102 - Concrete Curb and Gutter, Design D, Design S, and Design R The following Standard Plate is new: 8360 - Guardrail Post Length Marking See attached Summary of Changes for specifics. INSTRUCTIONS: Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual. The previous Transmittal Letter No. issued for this manual was 17-03, dated March 15, 2017. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (February 28, 2017) Standard Plate 7102J, Sheets 1-2 of 2, Concrete Curb and Gutter (July 25, 2011) Insert into the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 28, 2017) Standard Plate 7102K, Concrete Curb and Gutter (August 28, 2017) Standard Plate 8360A, Guardrail Post Length Marking (August 28, 2017) Current Standard Plates including Transmittal Letters are available on the web at: http://standardplates.dot.state.mn.us/stdplate.aspx Direct any technical questions regarding this transmittal to Tim Brown, Design Standards Unit at (651) 366-4613. Michael Elle, P.E. Design Standards Engineer

THIS PAGE INTENTIONALLY LEFT BLANK

Summary of Changes Standard Plate 7102K Concrete Curb and Gutter Design D, Design S, and Design R Transmittal Letter No. (17-04) General: 1. Plate renamed from Concrete Curb and Gutter Design D, Design S, Design B4, Design B5 and Design D3 to Concrete Curb and Gutter Design D, Design S and Design R. 2. Optional designs B4, B5 and D3 curbs & gutters eliminated. 3. Plate number incremented from 7102J to 7102K. 4. Number of sheets reduced to 1 sheet. Sheet 1 of 1 1. Design R curb & gutter added. 2. ½ radius rounding added to front lip of gutter pans on Design D and Design S. 3. Concrete quantities corrected for Design D. 4. Dimensions on the backs of curb and gutter clarified. 5. Minor wording changes to note No. 1. 6. Minor drafting changes made for consistency and clarification. Sheet 2 of 2 1. Optional design B and D curbs & gutters eliminated. 2. Sheet 2 of 2 eliminated.

Summary of Changes Standard Plate 8360A Guardrail Post Length Marking Transmittal Letter No. (17-04) General: 1. This is a new Standard Plate showing guardrail post length markings.

STANDARD PLATES BLANK... 0000 SERIES PAVEMENT... 1000 SERIES BLANK... 2000 SERIES CULVERTS AND APPURTENANCES... 3000 SERIES SEWER APPURTENANCES... 4000 SERIES EROSION CONTROL STRUCTURES... 5000 SERIES BLANK... 6000 SERIES CURB, CURB AND GUTTER, SIDEWALK... 7000 SERIES BARRICADES, SIGNALS, MARKERS, ETC.... 8000 SERIES MISCELLANEOUS... 9000 SERIES PLATE NO. 0000 SERIES BLANK 1000 SERIES PAVEMENT 1070M 1103K 1150R 1210G Supplemental Pavement Reinforcement Typical Dowel Bar Assembly (2 Sheets) Concrete Header Joints (2 Sheets) Concrete Pavement Adjacent to Railway Crossing 2000 SERIES BLANK 3000 SERIES CULVERTS AND APPURTENANCES 3000L Reinforced Concrete Pipe (5 Sheets) 3001B Reinforced Concrete Reducer Pipe 3002B Reinforced Concrete Increaser Pipe 3006G Gasket Joint for R.C. Pipe (2 Sheets) 3007E Shear Reinforcement for Precast Drainage Structures 3014J Reinforced Concrete Pipe Arch (2 Sheets) 3020G Reinforced Precast Concrete Cattle Pass (60" & 72") 3022C Precast Concrete Safety Apron (3 Sheets) 3040F Corrugated Metal Pipe Culvert (Standard 2-2/3" x 1/2" Corrugation) 3041D Corrugated Metal Pipe (3" x 1" Corrugation) 3050B Design Data Structural Plate Structures (18" Corner Radius) 3051B Design Data Structural Plate Structures (31" Corner Radius) 3065C Connection between Existing Culv. & New "C" Culv. Barrel (2 Sheets) 3066A C.M. Extension for Box Culvert 3100G Concrete Apron for Reinforced Concrete Pipe 3110G Concrete Apron for Reinforced Concrete Pipe-Arch 3114H Sectional Concrete Apron for Reinforced Concrete Pipe-Arch 3122K Metal Apron for C.M. Pipe-Arch Culvert 3123J Metal Apron for C.S. Pipe 3124B Metal Apron Connection 3125A Inlet Protection for Metal Culverts (90" dia. to 96" dia.) 3126B Inlet Protection for Structural Plate Pipe (60" thru 96" dia. or span) 3127A Inlet Protection for Structural Plate Pipe (102" thru 180" dia. or span) MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 1 of 4) August 28, 2017

PLATE NO. 3128H 3129A 3131C 3132A 3133D 3134D 3135A 3136B 3137B 3138B 3139B 3142A 3143C 3145G 3146C 3148A 3221C Metal Safety Apron & Grate (2 Sheets) Metal Apron for Corrugated Polyethylene Pipe (Use at Entrances and Driveways) Precast Concrete Headwall for Subsurface Drains Grate for 1:4 Precast Concrete Aprons Riprap at RCP Outlets Riprap at CSP Outlets Hand-Placed Riprap at Precast Concrete Cattle Pass Slotted Vane Drain for P.V.C. Pipe Slotted Drain for 12" thru 30" Dia. C.M. Pipe (Stackable) Slotted Drain for 12" thru 30" Dia. C.M. Pipe (Not Stackable) Riprap at Precast Concrete End Sections Outlet Screen for C.M. & S.C. Pipes Inspection Tees Concrete Pipe or Precast Culvert Ties Anti-Seepage Diaphragm (For CMP and CMP-A) Safety Slope Metal End Section for Circular & Arched Pipes (2 Sheets) Corrugated Steel Pipe Coupling Band (3 Sheets) 4000 SERIES--SEWER APPURTENANCES Drainage Structure and Castings (4 Sheets) Structure and Casting Combinations Standard Casting Assemblies List of Castings List of Drainage Structures 4000J Manhole or Catch Basin (Masonry, Field Constructed) - Design A 4002F Manhole or Catch Basin (Masonry, Field Construction) - Design C 4003B 30" Precast Catch Basin Design N 4005M Manhole or Catch Basin Type A & B Cone Sections Precast - Design F 4006L Manhole or Catch Basin Precast - Designs G and H 4007C Precast Mechanical Joint Sewer Manhole 4008E Catch Basin (Sectional Concrete Pipe) - Design I 4009H Manhole or Catch Basin (Sectional Concrete Pipe) - Design J 4010H Concrete Short Cone & Adjusting Ring (Sectional Concrete) 4011E Precast Concrete Base 4017C Catch Basin (Concrete Pipe and Metal Pipe) - Designs PC and PM 4018B Manhole or Catch Basin (Reducer Cone Section Precast) Design D 4020J Manhole or Catch Basin (For Use With or Without Traffic Loads) (2 sheets) 4021F Precast Curb Opening Catch Basin 4022A Manhole or Catch Basin Cover (3 ft. X 2 ft. Opening) 4024A 48" Dia. Precast Shallow Depth Catch Basin - Design SD 4025B Drop Inlets or Catch Basins - Design DI (Concrete & Metal) 4026A Concrete Encased Concrete Adjusting Rings 4101D Ring Casting For Manhole or Catch Basin 4108F Adjusting Rings for Catch Basins and Manholes 4110F Cover Casting for Manhole (For Use in all Traffic Areas) Casting No. 715 and 716 4125D Catch Basin Frame Casting (For Square Grate) Casting No. 806 4126F Catch Basin Frame Casting Casting No. 801 4129G Catch Basin Frame Casting (For Square Grate) - Casting No. 802A 4132F Catch Basin Frame Casting (For Square Grate) Casting No. 805 4133A Curb Box Casting for Catch Basin - Casting No. 824 4134A Curb Box Casting for Catch Basin (For Design B Curbs) - Casting No. 825 4140D Special Grate Castings for Catch Basin (Convex and Concave) - Casting No. 720 and 721 4143E Stool Grate & Concrete Frame (Median Drains) - Casting No. 731 4149C Grate Casting for Catch Basin - Casting No. 810 MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 2 of 4) August 28, 2017

PLATE NO. 4150C Grate Casting for All Pipe Drainage Structures 4151B Grate Casting for Catch Basin (Square Type) - Casting No. 811 4152C Catch Basin Grate Casting - Casting No. 814A 4153A Catch Basin Grate Casting - Casting No. 815 4154B Catch Basin Grate Casting - Casting No. 816 4160D Curb Box Casting for Catch Basin - Casting No. 823A and 833A 4161F Curb Box Casting for Catch Basin - Casting No. 821B, 822 and 831A 4180J Manhole or Catch Basin Step 5000 SERIES--EROSION CONTROL STRUCTURES 5010A Reinforced Concrete Pipe Energy Dissipater 6000 SERIES -- Blank 7000 SERIES--CURB, CURB AND GUTTER, SIDEWALK 7000E Integrant Curbs (Design B, Design V and Design D) 7020K Concrete Curb (Design B, Design V, Design S, Design DR and Design BR) (2 Sheets) 7038A Detectable Warning Surface Truncated Domes 7065C Bituminous Curb 7100H Concrete Curb and Gutter (Design B and Design V) 7102K Concrete Curb and Gutter (Design D, Design S, and Design R) 7105C Concrete Median (Mountable Type) 7107I Entrance Nose (Urban Design) 7108G Exit Nose (Urban Design) 7109C Median Nose and Island (Undivided to Divided Roadway) 7111J Installation of Catch Basin Castings (Concrete Curb and Gutter) 7112C Installation & Reinforcement of Catch Basin & Manhole Castings (Concrete Integrant Curbs) 7113A Concrete Approach Nose Detail 8000 SERIES -- BARRICADES, SIGNALS, MARKERS, ETC. 8000J 8002G 8106D 8107A 8110E 8111E 8112I 8117G 8118D 8119C 8120Q 8121H 8122F 8123G 8126L 8127E 8128E Channelizers Permanent Barricade Equipment Pad B RLF Equipment Pad Foundation Layout Traffic Signal Bracketing (Pole Mounted) Traffic Signal Bracketing (Pedestal Mounted) (3 Sheets) Pedestal Foundation (Traffic Control Signals) Precast Concrete HandHole With Vehicle Load Service Equipment & Pole Traffic Control Signals Ground Mounted Cabinet Foundation Pole Foundation (PA85) Transformer Base and Pole Base Plate (PA85, PA90 and PA100) (2 Sheets) Pedestal and Pedestal Base (For Traffic Control Signals Support) (2 Sheets) Pole and Mast Arm Luminaires and Traffic Lights Assembly (For All Pole Types) (2 Sheets) Pole Foundation (PA90 and PA100) Light Foundation - Design E, Precast/Cast-In-Place, 40 ft. Pole or Less (2 Sheets) Light Foundation - Design H, Precast/Cast-In-Place, 49 ft. Pole (2 Sheets) MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 3 of 4) August 28, 2017

PLATE NO. 8129A 8130E 8132B 8133A 8134C 8150C 8307S 8308B 8309B 8316C 8318C 8326D 8329I 8330G 8331B 8332D 8333B 8337C 8338D 8339A 8340A 8342B 8343A 8347A 8350A 8352A 8360A 8400E 8401C Shim and Washer (Traffic Control Signals and Roadway Lighting) Saw Cut Loop Detectors (3 Sheets) Preformed Rigid PVC Conduit Loop Detector (3 Sheets) Pole and Mast Arm - Type BA (9 Sheets) Pole Foundation - Type BA (4 Sheets) Installation of Culvert Markers W-Beam Guardrail & End Anchorages (Installation with Wood Posts) (4 Sheets) Reinforced Concrete Median Barrier Type F (Non-Glare Screen Type) Design 8308 (3 Sheets) Reinforced Concrete Median Barrier Type F & Glare Screen Design 8309 (3 Sheets) Post Seat for Anchorage on Footing or Box Culverts Guardrail Anchorage Plate for Bridges and BCT'S Flexible Plastic Glare Screen Eccentric Loader Breakaway Cable Terminal (ELT) (4 Sheets) 3-Cable Guardrail (With Wood Posts) (Assembly Details) (2 Sheets) 3-Cable Guardrail (With Steel Posts) (3 Sheets) Anchor Bolt Cluster and Base Plate for Light Poles 3-Cable Guardrail Anchor (Anchor Details) (4 Sheets) Temporary Portable Precast Concrete Barrier (Type F ) (3 Sheets) W-Beam Guardrail & End Anchorages (Installation with Steel Posts) (4 Sheets) 3-Cable (Steel Posts) to W Beam (Wood Posts) Guardrail Transition 3-Cable (Steel Posts) to W Beam (Steel Posts) Guardrail Transition High-Tension Cable Barrier Line Post Foundation (Concrete Design) High-Tension Cable Barrier Line Post Foundation (Steel Design) Portable Precast Concrete Barrier Anchors Thrie Beam Anchorage Plate Thrie Beam Wedge Plate for Single Slope Barrier Guardrail Post Length Marking Pipe Railing At Grade Pipe Railing (Adjacent to Sidewalk) 9000 SERIES--MISCELLANEOUS 9000E 9101B 9303B 9304A 9308A 9309G 9320G 9321E 9322K 9323D 9324C 9350A Approaches and Entrances - Recommended Standards Shaping and Sodding of Slopes at Box Culvert Ends Geodetic Survey Disks (Aluminum) (2 Sheets) Geodetic Survey Disks (Removable Type Disk) Survey Monument Cap (2 Sheets) PLS (Public Land Survey) Monument (2 Sheets) Woven Wire Fence (Wood Post) Woven Wire Fence (Steel Post) Chain Link Fence (2 Sheets) Barbed Wire Fence (Wood Post) Barbed Wire Fence (Steel Post) Mailbox Support (Swing-Away Type) MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 4 of 4) August 28, 2017

3 " R. 1 4'' " R. 1 7 ƒ" D DESIGN NO. GUTTER WIDTH W CONCRETE CU. YDS. LIN. FT. PER PER LIN. FT. CU. YD. D412 12'' 0.0505 19.8 D418 18'' 0.0613 16.3 7'' 12" D424 D436 24'' 36'' 0.0721 13.9 0.0937 10.7 2 HORIZONTAL LINE W GUTTER WIDTH DESIGN D 9" R. 1 4" " R. 1 5'' S DESIGN NO. S512 CONCRETE GUTTER CU. YDS. LIN. FT. WIDTH PER PER W LIN. FT. CU. YD. 12-1/2'' 0.0541 18.5 " R. 1 3" R. 7 " S518 18-1/2'' 0.0649 15.4 S524 S530 S536 24-1/2'' 30-1/2'' 36-1/2'' 0.0757 0.0865 0.0973 13.2 11.6 10.3 7'' 11- " 2 HORIZONTAL LINE W GUTTER WIDTH DESIGN S 6" R. " R. 16" R. 4'' " R. 7'' 1 1" 9 " 7 œ" 2 ƒ " R DESIGN NO. R412 R418 R424 R436 GUTTER WIDTH W 12'' 18'' 24'' 36'' CONCRETE CU. YDS. LIN. FT. PER PER LIN. FT. CU. YD. 0.0492 20.3 0.0600 16.7 0.0708 14.1 0.0924 10.8 2 HORIZONTAL LINE W GUTTER WIDTH 12" FLOW LINE NOTES: DESIGN R 1 SLOPE ƒ " PER FOOT NORMAL UNLESS OTHERWISE SPECIFIED. IF A DIFFERENT GUTTER SLOPE IS SPECIFIED, THE FORM MAY BE TILTED. 2 LONGITUDINAL JOINT WHEN ADJACENT TO RIGID PAVEMENT OR BASE. SEE STANDARD PLANS MANUAL FOR JOINT INFORMATION. APPROVED AUGUST 28, 2017 STATE OF MINNESOTA DEPARTMENT OF TRANSPORTATION SPECIFICATION REFERENCE STANDARD PLATE STATE DESIGN ENGINEER CONCRETE CURB AND GUTTER DESIGN D, DESIGN S AND DESIGN R 2531 NO. 7102K

THIS PAGE INTENTIONALLY LEFT BLANK

TOP VIEW TOP VIEW MARKING (INDICATING POST LENGTH IN FEET) MARKING (INDICATING POST LENGTH IN FEET) 4" MIN. 10" MAX. 4" MIN. 10" MAX. 9 6.5 MARKING HEIGHT 1 " MIN. MARKING HEIGHT 1 " MIN. STEEL POST WOOD POST VAR. VAR. SIDE VIEW SIDE VIEW STEEL GUARDRAIL POST WOOD GUARDRAIL POST NOTES: POST MARKING REQUIRED ON ALL NON STANDARD LENGTH STANDARD POSTS ON BOTH PRORIETARY AND NON-PROPRIETARY SYSTEMS. STANDARD 6' POSTS DO NOT REQUIRE MARKING. POSTS SHALL BE MARKED ON ONE SIDE TO INDICATE POST LENGTH IN FEET. STEEL POSTS SHALL BE DIE IMPRINTED (DEBOSSED). WOOD POSTS SHALL BE BRANDED OR IMPRINTED. MARKING SHALL BE SUCH AS TO RESIST OBLITERATION DURING STORAGE, TRANSPORTATION, AND PLACEMENT, AND SHALL BE VISIBLE AFTER PLACEMENT AND AFTER THE ATTACHMENT OF DELINEATOR. MANUFACTURER SHALL MARK POST PRIOR TO DELIVERY. APPROVED AUGUST 28, 2017 STATE DESIGN ENGINEER STATE OF MINNESOTA SPECIFICATION DEPARTMENT OF TRANSPORTATION REFERENCE 3306 GUARDRAIL POST LENGTH MARKING 3394 STANDARD PLATE NO. 8360A

THIS PAGE INTENTIONALLY LEFT BLANK