Transient Stability Improvement Of LFC And AVR Using Bacteria Foraging Optimization Algorithm

Similar documents
MATLAB Simulink Based Load Frequency Control Using Conventional Techniques

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

Load frequency control in Single area with traditional Ziegler-Nichols PID Tuning controller

PID Controller Tuning Optimization with BFO Algorithm in AVR System

Design of LFC and AVR for Single Area Power System with PID Controller Tuning By BFO and Ziegler Methods

Performance Analysis of Conventional Controllers for Automatic Voltage Regulator (AVR)

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET)

COMPARISON OF TUNING ALGORITHMS OF PI CONTROLLER FOR POWER ELECTRONIC CONVERTER

Automatic Voltage Control For Power System Stability Using Pid And Fuzzy Logic Controller

Control of Load Frequency of Power System by PID Controller using PSO

Performance Improvement Of AGC By ANFIS

Design Of PID Controller In Automatic Voltage Regulator (AVR) System Using PSO Technique

STABILITY IMPROVEMENT OF POWER SYSTEM BY USING PSS WITH PID AVR CONTROLLER IN THE HIGH DAM POWER STATION ASWAN EGYPT

COMPUTATION OF STABILIZING PI/PID CONTROLLER FOR LOAD FREQUENCY CONTROL

Available online Journal of Scientific and Engineering Research, 2014, 1(2): Research Article

Design of GA Tuned Two-degree Freedom of PID Controller for an Interconnected Three Area Automatic Generation Control System

OPTIMAL LOAD FREQUENCY CONTROL IN SINGLE AREA POWER SYSTEM USING PID CONTROLLER BASED ON BACTERIAL FORAGING & PARTICLE SWARM OPTIMIZATION

Performance Enhancement ofthree Phase Squirrel Cage Induction Motor using BFOA

Load Frequency Controller Design for Interconnected Electric Power System

Performance Analysis of PSO Optimized Fuzzy PI/PID Controller for a Interconnected Power System

CHAPTER 5 PSO AND ACO BASED PID CONTROLLER

TWO AREA CONTROL OF AGC USING PI & PID CONTROL BY FUZZY LOGIC

International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 ISSN

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

1. Governor with dynamics: Gg(s)= 1 2. Turbine with dynamics: Gt(s) = 1 3. Load and machine with dynamics: Gp(s) = 1

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Experiment 9. PID Controller

NEURAL NETWORK BASED LOAD FREQUENCY CONTROL FOR RESTRUCTURING POWER INDUSTRY

LOAD FREQUENCY CONTROL FOR TWO AREA POWER SYSTEM USING DIFFERENT CONTROLLERS

CHAPTER 1 INTRODUCTION

BFO-PSO optimized PID Controller design using Performance index parameter

INTELLIGENT PID POWER SYSTEM STABILIZER FOR A SYNCHRONOUS MACHINE IN SIMULINK ENVIRONMENT

Application Of Power System Stabilizer At Serir Power Plant

CHAPTER 4 LOAD FREQUENCY CONTROL OF INTERCONNECTED HYDRO-THERMAL SYSTEM

AUTOMATIC VOLTAGE REGULATOR AND AUTOMATIC LOAD FREQUENCY CONTROL IN TWO-AREA POWER SYSTEM

Chapter 2 An Optimum Setting of PID Controller for Boost Converter Using Bacterial Foraging Optimization Technique

ROBUST TECHNIQUE LFC OF TWO-AREA POWER SYSTEM WITH DYNAMIC PERFORMANCE OF COMBINED SMES AND SSSC CONTROL

COMPARISON OF TUNING METHODS OF PID CONTROLLER USING VARIOUS TUNING TECHNIQUES WITH GENETIC ALGORITHM

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Load Frequency Control in an Interconnected Hydro Hydro Power System with Superconducting Magnetic Energy Storage Units

Modeling and Simulation of Load Frequency Control for Three Area Power System Using Proportional Integral Derivative (PID) Controller

TUNING OF PID CONTROLLERS USING PARTICLE SWARM OPTIMIZATION

Cohen-coon PID Tuning Method; A Better Option to Ziegler Nichols-PID Tuning Method

AUTOMATIC GENERATION CONTROL OF REHEAT THERMAL GENERATING UNIT THROUGH CONVENTIONAL AND INTELLIGENT TECHNIQUE

Load Frequency Control of Multi-Area Power Systems Using PI, PID, and Fuzzy Logic Controlling Techniques

The Effect of Fuzzy Logic Controller on Power System Stability; a Comparison between Fuzzy Logic Gain Scheduling PID and Conventional PID Controller

TUNING OF PID CONTROLLER USING PSO AND ITS PERFORMANCES ON ELECTRO-HYDRAULIC SERVO SYSTEM

Modeling and Simulation of Automatic Generation Control System for Synchronous Generator with Model Predictive Controller

Load Frequency Control of Three Area System using FOPID Controller

DC Motor Speed Control: A Case between PID Controller and Fuzzy Logic Controller

Load frequency control of interconnected system

Load Frequency Control of Three Different Area Interconnected Power Station using Pi Controller

A Novel PSS Design for Single Machine Infinite Bus System Based on Artificial Bee Colony

Automatic Generation control of interconnected hydrothermal power plant Using classical and soft computing Technique

A new fuzzy self-tuning PD load frequency controller for micro-hydropower system

PID Tuning Using Genetic Algorithm For DC Motor Positional Control System

Load Frequency Control of Multi Area Hybrid Power System Using Intelligent Controller Based on Fuzzy Logic

International Journal of Advance Engineering and Research Development. Fuzzy Logic Based Automatic Generation Control of Interconnected Power System

Stability Control of an Interconnected Power System Using PID Controller

Artificial Intelligent and meta-heuristic Control Based DFIG model Considered Load Frequency Control for Multi-Area Power System

Automatic Generation Control of Two Area using Fuzzy Logic Controller

Research Article Multi-objective PID Optimization for Speed Control of an Isolated Steam Turbine using Gentic Algorithm

AGC in Five Area Interconnected Power System of Thermal Generating Unit Through Fuzzy Controller

A new approach for Tuning of PID Load Frequency Controller of an Interconnected Power System

Design of Model Based PID Controller Tuning for Pressure Process

EVALUATION ALGORITHM- BASED ON PID CONTROLLER DESIGN FOR THE UNSTABLE SYSTEMS

Relay Feedback based PID Controller for Nonlinear Process

PID TUNING WITH INPUT CONSTRAINT: APPLICATION ON FOOD PROCESSING

Non-Integer Order Controller Based Robust Performance Analysis of a Conical Tank System

Comparative Study of PID and Fuzzy Controllers for Speed Control of DC Motor

INTEGRATED PID BASED INTELLIGENT CONTROL FOR THREE TANK SYSTEM

Compare the results of Tuning of PID controller by using PSO and GA Technique for AVR system Anil Kumar 1,Dr. Rajeev Gupta 2

International Journal of Innovations in Engineering and Science

Improvement in Dynamic Response of Interconnected Hydrothermal System Using Fuzzy Controller

PID Controller Tuning using Soft Computing Methodologies for Industrial Process- A Comparative Approach

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN Volume 3, Issue 7, October 2014

Comparative Study of PID and FOPID Controller Response for Automatic Voltage Regulation

Design of PI controller for Positive Output Super- Lift LUO Converter

Design of Fractional Order Proportionalintegrator-derivative. Loop of Permanent Magnet Synchronous Motor

Neural Network Predictive Controller for Pressure Control

Load frequency control in two area multi units Interconnected Power System using Multi objective Genetic Algorithm

Comparison of Tuning Methods of PID Controllers for Non-Linear System

Load Frequency Control of Multi-Area Power System with PI Controller

Online Tuning of Two Conical Tank Interacting Level Process

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Temperature Control in HVAC Application using PID and Self-Tuning Adaptive Controller

Automatic Load Frequency Control of Two Area Power System Using Proportional Integral Derivative Tuning Through Internal Model Control

ANALYSIS OF V/f CONTROL OF INDUCTION MOTOR USING CONVENTIONAL CONTROLLERS AND FUZZY LOGIC CONTROLLER

Design of Fractional Order PID Controller for SMIB Power System with UPFC Tuned by Multi-Objectives Genetic Algorithm. Abstract:

Design and Simulation of Gain Scheduled Adaptive Controller using PI Controller for Conical Tank Process

Development of Dynamic Test Cases in OPAL-RT Real-time Power System Simulator

Some Tuning Methods of PID Controller For Different Processes

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

LOAD FREQUENCY CONTROL FOR A TWO-AREA INTERCONNECTED POWER SYSTEM BY USING SLIDING MODE CONTROLLER

Pareto Optimal Solution for PID Controller by Multi-Objective GA

Enhancement of Voltage Stability by SVC and TCSC Using Genetic Algorithm

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

THE general rules of the sampling period selection in

Simulation and Analysis of Cascaded PID Controller Design for Boiler Pressure Control System

Optimized Tuning of PI Controller for a Spherical Tank Level System Using New Modified Repetitive Control Strategy

Transcription:

ISSN (Online) : 2319-8753 ISSN (Print) : 2347-6710 International Journal of Innovative Research in Science, Engineering and Technology Volume 3, Special Issue 3, March 2014 2014 International Conference on Innovations in Engineering and Technology (ICIET 14) On 21 st &22 nd March Organized by K.L.N. College of Engineering, Madurai, Tamil Nadu, India Transient Stability Improvement Of LFC And AVR Using Bacteria Foraging Optimization Algorithm Anbarasi S #1, Muralidharan S *2 #1 Department of EEE, MepcoSchlenk Engineering College, Sivakasi, Tamilnadu, India *2 Department of EEE, MepcoSchlenk Engineering College, Sivakasi, Tamilnadu, India ABSTRACT This paper deals with an optimal tuning of Proportional Integral Derivative (PID) controller for both Load Frequency Control (LFC) and Automatic Voltage Regulation (AVR) of interconnected power system using Bacteria Foraging Optimization Algorithm (BFOA). As constancy of frequency and voltage are important factors in determining the quality of power supply, the control of active power and reactive power is vital to the satisfactory performance of power system. The real power and frequency is controlled by LFC and the reactive power and voltage is controlled by AVR. Minimization of Integral Time Square Error (ITSE) is taken as the objective function for both LFC and AVR. Various measuring indices like maximum peak, peak time, settling time and the final settling state error are considered as the performance measures for analyzing the transient characteristics of LFC and AVR. The robustness of the system is also examined by applying variable load changes to a system instead of fixed step change in load. The simulation results of the proposed BFOA tuned PID controller is compared with Non Controller System (NCS), Ziegler-Nichols tuned Proportional Integral (ZN- PI) controller, Ziegler-Nichols tuned PID controller (ZN- PID) and Integral controller. The comparative analysis clearly reveals that the transient performances and the robustness are much improved with the proposed approach over others. KEYWORDS Automatic voltage regulation, Bacteria foraging optimization algorithm, Integral controller, Load frequency control, PID controller, Ziegler-Nichols continuous cycling method. I. INTRODUCTION Nowadays, voltage and frequency control has gained more importance with the growth of interconnected power system. The real power is sensitive to frequency variations and it is regulated with LFC loop and the reactive power is sensitive to the voltage variations and it is regulated with AVR loop. This LFC and AVR control loops together are known as Automatic generation control (AGC) [1]. During the last decades the researchers have more attention to LFC over AVR although the main objective of the control strategy in an interconnected power system is, to generate both voltage and frequency within permissible limits. Recently, lot of research works were documented with an improved transient response by designing proper coupling effects between LFC and AVR and hence proves the necessity of AVR along with LFC [2, 3]. The flows of active power and reactive power in a transmission network are fairly independent of each other and hence this paper deals with individual control mechanism for LFC and AVR in order to improve the transient stability of power system. The PI controllers are commonly used in AGC. But the selection of high gain parameters of such controllers may deteriorate system performance having large oscillations and in most cases it causes system instability. The essential selection criteria of a controller are its proper control performance, maximum speed and its robustness towards the non linearity, time varying dynamics, disturbances and other factors. The PID controller has been recommended as a reputed controller in this accord and it also can be used for higher order systems. The ZN classic tuning method is normally used to predict the gain parameters of PID controller. These types of fixed gain controllers are designed for nominal operating conditions and they cannot provide a proper control action over a Copyright to IJIRSET www.ijirset.com 124

wide range of operating conditions [4]. The adaptability of such controllers on the varying load demand and uncertainties are also difficult and thereby quite often impractical for implementation. In response to these challenges so many intelligent approaches are also introduced now-a-days for optimal tuning of controllers in AGC [5, 6 and 7]. In this paper, an identical approach titled BFOA algorithm, is suggested for optimal tuning of PID controllers in single area LFC and AVR. The adequacy of the proposed BFOA algorithm is confirmed by comparing the results with a NCS and some of the conventionally tuned controllers. The robustness of the proposed algorithm also verified, by applying variable load changes instead of a fixed step change in load. The complete system model is simulated using Matlab /Simulink. The simulated output results confirm that the proposed technique improves the transient stability and robustness of the system. speed governor alone and the supplementary control originating at central control center allocated generation. The common nominal system parameters quoted in most of the references [8] are used in this paper. They are P r = 1000 MW; T g = 0.2 s; T t = 0.3s; T p = 20 s; K p = 120 Hz/ pu; R = 2.4 Hz /pumw; f = 60 Hz; B. Automatic Voltage Regulation The main objective of AVR is to contribute for the effective control of voltage and enhancement of system stability. Generally, the role of AVR is to hold the terminal voltage magnitude of synchronous generator at a specifiedlevel. II. AUTOMATIC GENERATION CONTROL A. Load Frequency Control For the satisfactory operation of power system the frequency should be maintained constant. The considerable drop in frequency in any electrical network could result in high magnetizing currents in induction motors and transformers. Fig. 1 Schematic block diagram of single area LFC So it is essential to regulate the frequency which is a common factor throughout the system. Moreover, the change in active power depends on frequency deviations and hence, the change in frequency in any point of the interconnected power system may affect the active power throughout the system. As a consequence the LFC is installed in power network to meet out the following objectives Maintain the frequency to its nominal value Maintain optimal power flow between control areas Maintain economical power generation in individual generating units Fig. 1 shows the LFC in single area thermal power system. Primary control action here is provided by the Fig. 2 Schematic block diagram of AVR In addition, the AVR must be able to respond to a transient disturbance with field forcing consistent with the generator instantaneous and short term capabilities. It should also be capable of responding to disturbance so as to enhance transient stability and of modulating generator field so as to enhance small signal stability. Fig. 2 shows the functional block diagram of typical AVR loop. The primary means of generator reactive power control in this AVR loop is done with the excitation control and the supplementary control action is provided with a PID controller. The interaction between voltage and frequency control is generally weak. So in this paper the analysis of LFC and AVR are carried out separately. The nominal system parameters of AVR investigated in this paper are same as the parameter commonly quoted in most of the research papers [9]. They are: K A = 10; K E = K G = K R = 1; T A = 0.1s T E = 0.4s; T G = 1s; T R = 0.01s III. TUNING OF PID CONTROLLER A. Ziegler-Nichols continuous cycling method The PID type controller remains the most popular in industry. Studies even indicate approximately 90% of all industrial controllers is of PID type. However, finding approximate gain parameters for this controller is still a difficult task. ZN continuous cycling method is the most excellent conventional tuning method used to predict the gain parameters of PID controllers. The procedural Copyright to IJIRSET www.ijirset.com 125

analysis to design the PID gain parameters using ZN continuous cycling method is as follows G s H s = G s H s = The polynomial characteristic equation of LFC and AVR are designed as shown in (1) and (2). K cr K p R T p s + 1 T g s + 1 T t s + 1 (1 ) K cr K A K E K G K R T A s + 1 T E s + 1 T G s + 1 T R s + 1 ( 2) The critical gain constant ( K cr ) and the time constant (T cr ) are obtained by solving (1 and 2) with Routh Hurwitz stability criterion without violating the stability margin. The constants K cr and T cr are substituted in Table I and the following gain parameters are evaluated as For LFC- K P =3.872428, K I =8.031838, K D =0.466758. For AVR -K P =1.021006, K I =1.87429, K D =0.139046. TABLE I CALCULATIONOF PID PARAMETERS Control type K P T I 1 T D 2 P 0.5K cr 0 PI 0.45K cr T cr 1.2 0 Reproduction helps to keep the swarm size constant in a search space by omitting the least healthy bacteria and by splitting the healthiest bacteria in to two. Similar to which the solutions yields low objective functions in minimization problems is reproduced and the solutions with maximum value of objective are discarded from the search space. Both LFC and AVR in this paper using a minimization objective function as shown in (3 and 4). J 1 = ITSE = 0 t sim f 2. t. dt (3) J 2 = 1 v β M p + E ss + v β T s T r (4) where, f and v are deviation in frequency and voltage correspondingly, the value of constant β is taken as 0.5, t sim in the maximum simulation time and it is taken as 20s in this paper, M p is the maximum peak of the output wave form, E ss is the steady state error and T s, T r are settling time and rise time respectively. Elimination and Dispersal is happened due to the occurrence of sudden environmental changes or attack. A group of bacteria may liquidate randomly with a very small probability and some new one will be introduced to swarm of concern. This process helps in reducing the behavior of stagnation often seen in parallel search algorithms. PID 0.6K cr T cr 2 T cr 8 IV. RESULTS AND DISCUSSIONS The disadvantages of conventional PID controller are already being discussed in Section I. Hence, an idea of using artificial intelligent techniques got strengthened. This paper proposed one of the swarm based artificial intelligent technique named BFOA for the effective tuning of PID controller. B. BFOA Tuned PID Controller The BFOA is one of the swarm based optimization algorithm which is built with a key idea of foraging strategy of E. coli bacteria [10]. On this accord BFOA mimics four principle mechanisms in real bacterial system. They are Chemotaxissimulated the movement of E. coli through swimming and tumbling via flagella similar to which the randomly assigned solutions are moved in a search space. Swarming is the interesting grouping behavior of the motile species. In this mechanism the E. coli cells are arranged themselves in a travelling ring and moving towards the nutrient. The cells when stimulated by a high level of succinate will release an attractant aspartate which helps them to align in a group. In optimization problem this phenomenon is used to move the solutions towards an optimal point. A. Transient analysis of LFC with BFOA tuned PID controller for step change in load The single area thermal power system [8] shown in Fig. 1 is considered as a test system in this section for the proposed approach. Fig. 3 Comparative transient performances of LFC for P D = 1% Copyright to IJIRSET www.ijirset.com 126

TABLE II COMPARATIVE TRANSIENT ANALYSIS OF LFC Measuring Parameters for Frequency Deviation Methods Settling Maximum Peak Error Time Peak Time (Hz) (s) (Hz) (s) NCS 10 0.01625 0.40491 0.00251 Integral 4.46243 0.02834 0.76303 6.09638 10-4 ZN- PID 1.93634 0.00641 0.18364 2.36978 10-6 BFOA 1.49416 0.00586 0.15285 1.52200 10-6 Initially, the transient performances of the single area LFC for 1% load perturbation is obtained by way of BFOA tuned PID controller with J 1. The BFOA parameters used for both LFC and AVR are Number of bacteria =10; Number of Chemotactic steps =10; Length of swim=4; Number of reproduction steps = 2; Probability of elimination and dispersal = 0.25; Number of elimination and dispersal events = 2. The PID parameters evaluated by this method are K P =3.1851, K I =4.6725, K D =0.6556. Then to show the effectiveness of the proposed approach, the results of proposed algorithm are compared with NCS, integral controller and ZN -PID enforced to the same power system. Fig. 3 illustrates the comparative analysis made between the transient performances of LFC with different approaches. The measuring parameters affiliated to this figure are scheduled in Table II and it clearly reveals that the total error evaluated using J 1 in the proposed approach is considerably reduced to 64.225% compared to ZN tuned PID controller. Similarly, the Maximum peak reduced to 91.42% and 20.677% compared to ZN method and Integral controller respectively. Compared with same controllers, the settling time of the proposed method is improved by 0.4422s and 2.968s respectively. Hence, it is distinctly demonstrated from the above analysis that, the transient characteristics of single area LFC are enhanced with the proposed approach comparing to other conventional approaches. B. Transient analysis of AVR with BFOA tuned PID controller for step change in V ref The AVR system [9] shown in Fig. 2 is considered as a test system in this section for the proposed approach. TABLE II COMPARATIVE TRANSIENT ANALYSISOF AVR Measuring Parameters for Voltage Deviation Methods Settling Maximum Peak Error (V) Time (s) Peak (V) Time (s) NCS 10 0.01505 0.76384 8.8106 10-4 ZN- PI 9.96854 0.01786 0.85966 1.6901 10-4 ZN- PID 3.64848 0.01529 0.64652 2.9709 10-8 BFOA 1.10280 0.01073 0.41146 2.4597 10-8 Similar to LFC, the transient performances of the AVR test system for 1% load perturbation is obtained by way of BFOA tuned PID controller with J 2 objective function. The PID parameters evaluated by this method are K P =0.7886, K I =0.6085, K D =0.3357. To show the effectiveness of the proposed approach, the results are compared with Non Controller System (NCS), ZN tuned PID controller (ZN- PID) and ZN tuned PI controller (ZN- PI). The transient performances of AVR with different approaches are exemplified in Fig. 4 and the measuring parameters affiliated to this figure are scheduled in Table III. It is clear from the table that the total error reduced to 82.79% compared to ZN-PID controller. The Maximum peak also reduced to 60.08% and 70.16% compared to ZN tuned PI controller (ZN-PI) and ZN-PID controller respectively. Compared with same controllers, the settling time of the proposed method is improved by 8.866s and 2.545s respectively. The above analysis clearly reveals the superiority of the proposed BFOA tuned PID controller for AVR compared to other approaches. C. Transient analysis of LFC and AVR with BFOA tuned PID controller for variable load changes To scrutinize the non linear behavior and practical adaptability of the LFC and AVR test system, instead of fixed step change in load, the variable load ranges between (0-100s) as indicated in Fig. 5a are applied to both the systems. At first, the frequency control effects of LFC test system for different approaches such as NCS, ZN-PID controller, integral controller and BFOA tuned PID controller are explored under this variable load condition and the output response for frequency deviations for all these approaches are plotted as shown in Fig. 5b. For clear and detailed empathetic some of the random portions are enlarged in the time ranges of (30-50s) and (90-100s) which can be visualized in Fig. 5c and Fig. 5d. Both these figures ratify the incredible performanceof the proposed BFOA tuned PID controller over other approaches. Fig. 4 Comparative transient performances of AVR for V ref =1% Copyright to IJIRSET www.ijirset.com 127

Fig. 5 Comparative transient responces of LFC for variable load changes Further, the voltage control effects of different methods such as NCS, ZN-PI controller, ZN-PID controller and BFOA tuned PID controller for the AVR test system are comparatively investigated under the time varying load shown in Fig. 6a. The output response for voltage deviations for all these approaches is obtained as shown in Fig. 6b. For clear illustration randomly selected portions of the Fig. 6b in the time ranges of (10-30s) and (70-90s) are enlarged as shown in Fig. 6c and Fig. 6d respectively. Both these figures clearly demonstrate that the number of oscillations, maximum overshoot, steady state error and settling time are considerably reduced with the proposed approach over others and hence makes the controller more versatile to the practical environment. Fig. 6 Comparative transient responces of AVR for variable load changes V. CONCLUSIONS This paper represents BFOA, one of the optimization techniques for the effective tuning of PID controller gains for both LFC and AVR with off-line, as well as, nominal input conditions. As because of weak interaction between the voltage and frequency controls in this paper separate objective functions are used to demonstrate the transient responses of LFC and AVR. The predominance optimal response of the proposed approach over other conventional techniques is proved by analyzing the transient responses of LFC and AVR for fixed load perturbations. Addition to a fixed value of loadchange, in this paper wide range of load variationsare also applied to exemplify the robustness and non-linearity of the proposed method in both LFC and AVR over other conventional approaches. Hence all the investigations made in this proposed approach confirm that the BFOA based tuning of PID controller assuredly overcome the Copyright to IJIRSET www.ijirset.com 128

difficulties faced by the practitioners while using conventional fixed gain PID controller. P r Rated power (MW) NOMENCLATURE T g Steam governor time constant (s) T t Steam turbine time constant (s) K p Power system gain constant (Hz/ pu) T p Power system time constant (s) R K A T A K E T E K G T G K R T R Governor speed regulation (Hz/ pu MW) Amplifier gain constant Amplifier time constant (s) Exciter gain constant Exciter time constant (s) Generator gain constant Generator time constant (s) Sensor gain constant Sensor time constant (s) REFERENCES [1] P. Kundur, Power system stability and control, 8th ed., McGraw- Hill: New York, 1994, pp.581-622. [2] M. Nagendra, M.S. Krishnarayalu, AGC and AVR of multi area power systems with and without GRC nonlinearity, International journal of advanced research in electrical electronics and instrumentation engineering, vol. 2, issue 6, pp. 2117-2126, June 2013. [3] Ahmad M. Hamza, Mohamed S. Saad, Ahmed Bahgat, Design of LFC and AVR for single area power system with PID controller tuning by BFO and Ziegler Methods, International Journal of Computer Science and Telecommunications, vol. 9, issue 5, pp. 12-17, May 2013. [4] K. J. Astrom, T. Hagglund, Ahmed Bahgat, The future of PID control, Control engineering practice, vol. 9, pp. 1163-1175, April 2001. [5] H. Golpîra, H. Bevrani, H. Golpîra, Application of GA optimization for automatic generation control design in an interconnected power system, Energy Conversion and Management, vol. 52, pp. 2247-2255, 2011. [6] Hamed Shabani, Behrooz Vahidi, Majid Ebrahimpour, A robust PID controller based on imperialist competitive algorithm for loadfrequency control of power systems, ISA Transactions, vol. 52, pp. 88-95, 2013. [7] V. Mukherjee, S.P. Ghoshal, Intelligent particle swarm optimized fuzzy PID controller for AVR system, Electric power system research, vol. 77, pp. 1689-1698, Jan 2007. [8] Saumya Kr. Gautam, Nakul Goyal, Improved particle swarm optimization based load frequency control in a single area power system, Annual IEEE India conference (INDICON 2010), Kolkata, Dec 2010. [9] Z.L. Gaing, A particle swarm optimization approach for optimum design of PID controller in AVR system, IEEE Trans. Energy conversion, vol. 19, pp. 384-391, June 2004. [10] E.S. Ali, S. M. Abd-Elazim, Bacteria foraging optimization algorithm based load frequency controller for interconnected power system, Electrical power and energy systems, vol. 32, pp. 633-638, Jan 2011. Copyright to IJIRSET www.ijirset.com 129