XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

Similar documents
XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XF2 Frequency Relay. Manual XF2 (Revision A)

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

XP2-R Power and Reverse Power Relay

XUA1 - AC Voltage and phase balance relay

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XN2 - Mains decoupling relay. Manual XN2 (Revision C)

XN2 - Mains decoupling relay

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

XD1-T - Transformer differential protection relay

IRI1-ER - Stabilized Earth Fault Current Relay

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

MRS1 - Negative sequence relay. Manual MRS1 (Revision A)

DEIF A/S. Insulation monitor. Type SIM-Q

Overcurrent Protection / 7SJ45

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

Installation / Monitoring Technique

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

02/11/2015

Three-phase monitoring relays

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Electronic timers CT-S range Selection and ordering details

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

05/09/2012

02/11/2015

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

08/07/2015

RISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

QUINT-PS/ 3AC/24DC/10

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Electronic measuring and monitoring relays CM-range

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

02/11/2015

QUINT-PS/ 3AC/24DC/40

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out.

QUINT-PS-24DC/24DC/10

02/11/2015

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

08/07/2015

Type CP-S, CP-C & CP-A Switch mode

Three-phase monitoring relay

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

Thermistor motor protection relays

Analog signal converters CC-E I/I

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Electronic relays. Monitoring. Monitoring

SPAE 010, 011 High Impedance Protection Relay

ISOMETER IRDH575. Approvals

Installation- / Monitoring technique

Electronic timer CT-TGD.22

QUINT-PS AC/24DC/40

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

QUINT-PS/ 1AC/24DC/20

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

02/11/2015

Liquid level monitoring relay CM-ENS.2x

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

"Modular" versions designed for application-specific functions LCD with 4 lines of 18 characters and configurable backlighting

02/11/2015

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models

02/11/2015

Custom "Compact" range with display CD20 Custom Part number

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

MRQ1 Field failure relay. Manual MRQ1 (Revision A)

Electronic timer CT-MXS.22 Multifunctional with 2 c/o (SPDT) contacts

02/11/2015

Electronic timer CT-SDS.22

SINEAX TV 808, 2 channels Isolating Amplifier Unipolar/Bipolar

Operating Instruction

Electronic timer CT-SDD.22

Electronic timer CT-MFS.21

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

Switching power supplies CP range, Linear power supplies CP-L range. Content

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Transcription:

XR1 Rotor Earth Fault Relay Manual XR1 (Revision C)

Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken. Woodward 1994-2017 2 DOK-TD-XR1 Rev. C

Manual XR1 (EN) Woodward Content 1. Applications and Features... 4 2. Design... 5 3. Function... 6 4. Operation and Settings... 8 4.1 Setting of DIP-Switches... 9 4.2 Setting of the Tripping Values... 10 4.3 Communication via Serial Interface Adapter XRS1... 11 5. Relay Case and Technical Data... 12 5.1 Relay Case... 12 5.2 Technical Data... 13 DOK-TD-XR1 Rev. C 3

Woodward Manual XR1 (EN) 1. Applications and Features Protection relay XR1 of our PROFESSIONAL LINE is used for detection of rotor earth faults in synchronous machines. The earth fault element detects high and low impedance earth faults in rotor windings and is in two stage design (for alarm and trip). When compared to the conventional protection equipment all relays of the PROFESSIONAL LINE reflect the superiority of digital protection techniques with the following features: High measuring accuracy by digital data processing Fault indication via LEDs Extremely wide operating ranges of the supply volt-age by universal wide-range power supply Very fine graded wide setting ranges Data exchange with process management system by serial interface adapter XRS1 which can be retrofitted Extremely short response time Compact design by SMD-technology In addition to this, relay XR1 has the following special features: Detection of high impedance earth faults in rotor windings and is in two stage design. Short circuit and overvoltage proof measuring input for earth fault protection Separately setting of trip delay for R< and R<< 4 DOK-TD-XR1 Rev. C

Manual XR1 (EN) Woodward 2. Design Figure 2.1: Connections Measuring paths By using a measuring voltage, the protection relay ascertains the resistance of the test object via terminals U1 and U2. Auxiliary voltage supply Unit XR1 needs a separate auxiliary voltage supply. Therefore a dc or ac voltage must be used. Unit XR1 has an integrated wide range power supply. Voltages in the range from 19-390 Vdc or 36-275 Vac can be applied at connection terminals A1 and A2. Contact positions Figure 2.2: Contact positions of the output relays DOK-TD-XR1 Rev. C 5

Woodward Manual XR1 (EN) 3. Function A single earth fault on the field windings of a synchronous generator produces no immediate damaging effect. It must be detected and removed because of the possibility of a second earth fault that could short a part of the field winding and cause severe damage. XR1 provides an alarm and a trip element for the rotor earth fault protection. The insulation resistance measurement system of the XR1 can be used for synchronous generators of both types, with and without brushes. It works with a low frequency alternating test voltage (1 Hz, ±24V) which is connected via slip rings to the main exciter winding and to rotor earth (ref. to connection diagram). The low frequency of the test voltage is used to avoid malfunction due to the field-to-earth capacitance (CE) which can reach values up to 1 µf on large generators. Within the device, there is a current limiting resistor (RV) to prevent overcurrent in case of a fault. After all, the device measures the voltage at an (internal) resistor RMeas, and this voltage is directly related to the earth current to be supervised. Aux. Power Supply 19V... 390V DC or 36V... 275V AC A1 A2 Relay 1 11 12 13 U1 R V V Test Controller Relay 2 21 22 23 100 ko R E C E U2 R Meas 3.92 ko Rotor Earth Potential XR1 XR1_Z01 Figure 3.1: Measuring principle of the earth current. C E and R E are equivalent circuit symbols for the field-to-earth capacitance and resistance, respectively. The insulation resistance measurement is based on the subsequent measurement of the shunt resistor voltage of two consecutive half cycles, i.e. positive and negative test voltage. From the differential voltage between the positive and negative measuring voltage at the end of each half cycle the insulation resistance is calculated. This wav wrong measurement due to the earth capacitance and possible voltage offsets is avoided. 6 DOK-TD-XR1 Rev. C

Manual XR1 (EN) Woodward Figure 3.2 explains the measuring principle: V Test Test voltage V Meas Voltage at R Meas for R E=0 V Meas Voltage at R Meas for R E=infinite V Meas Voltage at R Meas E proportional 1/R E V Meas proportional 1/R E Voltage at R Meas (unsymmetrical fault with DC offset) XR1_Z02 Figure 3.2: Measuring principle DOK-TD-XR1 Rev. C 7

Woodward Manual XR1 (EN) 4. Operation and Settings All operating elements needed for setting parameters are located on the front plate of the XR1 as well as all display elements. Because of this all adjustments of the unit can be made or changed without disconnecting the unit off the DIN-rail. Figure 4.1: Front plate For adjustment of the unit the transparent cover has to be opened as illustrated. Do not use force! The trans-parent cover has two inserts for labels. Figure 4.2: How to open the transparent cover LEDs LED ON is used for display of the readiness for service (at applied auxiliary voltage Uv). LED R< and R<< signal pickup (flashing) or tripping (steady light) of the corresponding function. Test push button This push button is used for test tripping of the unit and when pressed for 5 s a check-up of the hardware takes place. Both output relays are tripped and all tripping LEDs light up. 8 DOK-TD-XR1 Rev. C

Manual XR1 (EN) Woodward 4.1 Setting of DIP-Switches The DIP-switch block on the front plate of the XR1 is used for adjustment of the nominal values and setting of function parameters: DIP-switch OFF ON Function 1 2 3 4 active blocked Rotor earth fault warning 5 active blocked Rotor earth fault tripping 6 7 x1 x2 Multiplier for tr< 8 x1 x2 Multiplier for tr<< Table 4.1: Functions of DIP-switches Blocking of rotor earth fault warning element When DIP-switch 4 is in ON position, the rotor earth fault warning element is blocked. Blocking of rotor earth fault trip element When DIP-switch 5 is in ON position, the rotor earth fault trip element is blocked. DOK-TD-XR1 Rev. C 9

Woodward Manual XR1 (EN) 4.2 Setting of the Tripping Values The PROFESSIONAL LINE units have the unique possibility of high accuracy fine adjustments. For this, two potentiometers are used. The coarse setting potentiometer can be set in discrete steps of 20 kω or 5 kω. A second fine adjustment potentiometer is then used for continuously variable setting of the final (0-20 kω or 0-5 kω). Adding of the two values results in the precise tripping value. Rotor earth fault alarm R< The rotor earth fault alarm can be set in the range from 20-140 kω with the aid of the potentiometer illustrated on the following diagram. Example: A tripping value of 92 kω is to be set. The set value of the right potentiometer is just added to the value of the coarse setting potentiometer. (The arrow of the coarse setting potentiometer must be inside of the marked bar, otherwise no defined setting value). Figure 4.3: Adjustment example Rotor earth fault tripping R<< The rotor earth fault tripping can be set in the range from 0-30 kω with the aid of the potentiometer illustrated on the following diagram (R<< min = 2 kω) Example: A tripping value of 18 kω is to be set. Figure 4.4: Adjustment example Time delay tr< With the aid of DIP-switch 7 the time delay at rotor earth fault alarm tr< can be adjusted continuously variable in the range from 0-25 s or 0-50 s. Time delay tr<< With the aid of DIP-switch 8 the time delay at rotor earth fault tripping tr<< can be adjusted continuously variable in the range from 0-10 s or 0-20 s. 10 DOK-TD-XR1 Rev. C

Manual XR1 (EN) Woodward 4.3 Communication via Serial Interface Adapter XRS1 Figure 4.5: Communication principle For communication of the units among each other and with a superior management system, the interface adapter XRS1 is available for data transmission, including operating software for our relays. This adapter can easily be retrofitted at the side of relay. Screw terminals simplify its installation. Optical transmission of this adapter makes galvanic isolation of the relay possible. Aided by the software, actual measured values can be processed, relay parameters set and protection functions programmed at the output relays. Information about unit XRS1 in detail can be taken from the description of this unit. DOK-TD-XR1 Rev. C 11

Woodward Manual XR1 (EN) 5. Relay Case and Technical Data 5.1 Relay Case Relay XR1 is designed to be fastened onto a DIN-rail acc. to DIN EN 50022, the same as all units of the PROFESSIONAL LINE. The front plate of the relay is protected with a sealable transparent cover (IP40). Figure 5.1: Dimensional drawing. (All dimensions in millimeters.) Connection terminals The connection of up to a maximum 2 x 2.5 mm 2 cross-section conductors is possible. For this the transparent cover of the unit has to be removed (see chapter 4). 12 DOK-TD-XR1 Rev. C

Manual XR1 (EN) Woodward 5.2 Technical Data Measuring input circuits Thermal withstand capability in measuring circuit: during 10 s Umax = 600 V continuous Umax = 140 VAC/DC Output voltage of measuring circuit: Auxiliary voltage Rated auxiliary voltage Uv/ Power consumption: UH = ±24 V (short circuit proof) fh = 1 Hz 19-390 V DC or 36-275 V AC (f = 40-70 Hz)/ 4 W (terminals A1 and A2) Maximum permissible interruption time of aux. voltage: UV = 24 Vdc: tu = 8 ms, UV = 48 V DC: tu = 35 ms UV > 60 Vdc: tu = 50 ms Common data Dropout to pickup ratio: 10 % Resetting time from pickup: <1 s Returning time from trip: 500 ms Minimum initialization time after supply voltage has applied: 1.1 s Minimum response time when supply voltage is available: 1 s Output relay Number of relays: 2 Contacts: 1 changeover contact for each trip relay Maximum breaking capacity: ohmic 1250 VA/AC resp. 120 W/DC inductive 500VA/AC resp. 75 W/DC Maximum rated voltage: 250 V AC 220 V DC ohmic load Imax = 0,2 A inductive load Imax = 0,1 A at L/R 50 ms 24 V DC inductive load Imax = 5 A Minimum load: 1 W / 1 VA bei Umin 10 Maximum rated current: 5 A Making current (16ms): 20 A Contact life span: 10 5 operations at max. breaking capacity Contact material: AgCdO System data Design standard: VDE 0435 T303; IEC 0801 part 1-4; VDE 0160; IEC 255-4; BS142; VDE 0871 Temperature range at storage and operation: - 25 C to + 70 C Constant climate class F acc. DIN 40040 and DIN IEC 68, part 2-3: more than 56 days at 40 C and 95 % relative humidity High voltage test acc. to VDE 0435, part 303 Voltage test: 2.5 kv (eff.)/50 Hz; 1 min Surge voltage test: 5 kv; 1.2/50 µs, 0.5 J High frequency test: 2.5 kv/1 MHz Electrostatic discharge (ESD) acc. to IEC 0801, part 2: 8 kv DOK-TD-XR1 Rev. C 13

Woodward Manual XR1 (EN) Radiated electromagnetic field test acc. to IEC 0801, part 3: Electrical fast transient (burst) acc. to IEC 0801, part 4: Radio interference suppression test as per DIN 57871 and VDE 0871: 10 V/m 4 kv/2.5khz, 15 ms limit value class A Accuracy of the specific rated values: 5 % or ±2 kω Repeat accuracy: 5 % Basic time delay accuracy: 3 % or ±100 ms 3 % or +0...2.2 s (R-measuring) Temperature effect: 0.1 % per K Mechanical test: Shock: class 1 acc. to DIN IEC 255-21-2 Vibration: class 1 acc. to DIN IEC 255-21-1 Degree of protection Front plate: Weight: Mounting position: Relay case material: IP40 at closed front cover approx. 0.5 kg any self-extinguishing Parameter Setting range Graduation R< 20-140 kω continuously R<< 0-30 kω continuously tr< 0-25 s / 0-50 s continuously tr<< 0-10 s / 0-20 s continuously Table 5.1: Setting ranges and graduation Technical data subject to change without notice! 14 DOK-TD-XR1 Rev. C

Manual XR1 (EN) Woodward Setting-list XR1 Project: Woodward job.-no.: Function group: = Location: + Relay code: - Relay functions: Date: Setting of parameters Function Unit Default settings Actual settings R< Rotor earth fault alarm kω 20 R<< Rotor earth fault tripping kω 2 tr< Time delay for R< s 0 tr<< Time delay for R<< s 0 DIP-switch setting DIP-switch Function Default settings Actual settings 1 2 3 4 Rotor earth fault alarm Active 5 Rotor earth fault tripping Active 6 7 Multiplier for tr< x1 8 Multiplier for tr<< x1 DOK-TD-XR1 Rev. C 15

Woodward Kempen GmbH Krefelder Weg 47 D 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet www.woodward.com Sales Phone: +49 (0) 21 52 145 216 or 342 Telefax: +49 (0) 21 52 145 354 e-mail: salesemea_pgd@woodward.com Service Phone: +49 (0) 21 52 145 614 Telefax: +49 (0) 21 52 145 455 e-mail: SupportEMEA_PGD@woodward.com