Series 700A Power Processor 5 25 SINGLE PHASE 10 500 THREE PHASE VOLTAGE REGULATION, ISOLATION, AND POWER DISTRIBUTION FOR CLEAN, SPIKE-FREE, STABLE VOLTAGE When Power Quaity Is A Must And Faiure Is Not An ion! Medica Faciities / Labs / Equipment Government / Commercia Buidings Broadcast Communications Teecommunications Audio-Visua Concert Has & Theaters Wastewater Treatment Pants Refineries & Chemica Pants HVAC Equipment Machine Toos / CNC Equipment Co-generation & Power Generation Manufacturing / Automation / Robotics UPS Bypass & Power Distribution Engineers and manufactures the industry s highest quaity power conditioning equipment, capitaizing on 3 decades of expertise. We have an enviabe reputation for quaity, which is refected in the design, workmanship, and performance of our products. We provide a wide range of performance-proven technoogies for the reguation, conditioning, isoation, and distribution of cean and stabe eectrica power. This product range aows us to optimize soutions that best fit the performance characteristics of our customers varied appications. As a resut, we don t have to fit a square peg soution into a round hoe probem! Our products protect sensitive eectronic systems from erratic operation and faiure due to power ine transients, noise, brownouts, sags, surges, and tota power outages. What is Power Conditioning? Basic power conditioning isoates the critica oad from the power source in a way that minimizes the ine impedance effects, inhibits the common ground noise, and produces a known cean power source for the oad. In some cases, a muti-shieded transformer with ow output impedance resoves most power quaity probems. However, for more sensitive equipment, adding a fast-acting Controed Power Company votage reguator accompanied by high-frequency fitering resoves a power-reated probems except power outages.
The Need For Power Conditioning Loca utiity companies generate cean, sinusoida eectrica waveforms, which is the technica phrase for good power. However, once the power is transmitted and goes through the distribution journey to the end-users, it is exposed to infuences that cause changes and distortions to the waveform. These infuences incude power gridswitching, power factor correction osciations, re-strikes, weather, auto accidents, and even anima damage. A of these factors, as we as industria, commercia, and residentia users contribute to the degradation of the power with non-inear oads, high cycic power demands, and periodic fauts. Characteristics Of A Power Line Conditioner Power quaity addresses ALL the power disturbances that affect your operation. Look for the foowing features of a first-cass system: Gavanic isoation with a minimum of 140 db common mode noise rejection Input operating range of at east +10% to -20% Low output impedance of <3% Votage correction within one cyce + 3% votage reguation Low operating temperature High efficiency 1000% system overoad Spike and transient protection Immunity to high harmonic content oads Abe to withstand and reguate to within specification, with oads of.5 eading to.5 agging power factor Performance Characteristics That Get The Job Done Reguation Automation, refineries, pup and paper, robotics, medica, computers, aerospace, aboratories, CNC, EDM, machine too, fight simuators, semiconductor fabrication a require correct and steady votage for secure operation. The 7-tap, microprocessor-controed Series 700A Power Processor, precisey maintains the correct votage to 3% within one cyce, and maintains reguation during extended brownouts. One Box Soution Fexibiity to convert standard U.S. votages to the equivaent European or Asian votages. Output Impedance Linear acceerators, X-ray, MRI, motor starts, and variabe speed drives a have enormous surge currents. The Power Processor s ow output impedance transformer minimizes votage distortion and sags commony associated with these high demand cycic oads. Typicay a surge/overoad of 600% imposed on the Power Processor, ony reduces the output votage by 6%; greaty minimizing the effects on associated oads. Common Mode Noise Sound and video production equipment are very susceptibe to eectrica interference and fuctuating votages. Ony a wereguated source of power that provides a noise-free ground, does not introduce harmonics, and is not affected by harmonic oads is suitabe for these appications. The Power Processor s tripe-shieded isoation transformer fufis this requirement, providing in excess of 140dB ground noise signa attenuation. Transient Protection Commercia and industria faciities, computer rooms, universities etc., are continuay subjected to votage transients and spikes; a eading cause of eectronic faiures. The Power Processor s high-eve spike suppression system protects your equipment by virtuay eiminating these transients.
SPECIFICATIONS The Series 700A Power Processor consists of an acopper, mutipe-tapped, tripe-shieded isoation transformer. In conjunction with the eectrostatic shieds, the ow output impedance of the transformer assures computer-grade performance with exceent noise and transient attenuation. For each of the 7 taps per phase, independenty-controed inverse parae eectronic switches provide tight reguation. Load Reguation The output is maintained to within 3%. Output Status Lights Status indicator for each phase. Aert Light Indicates that the output has been disabed by one of the foowing conditions: Transformer over-temperature and SCR therma over-temperature. Noise Attenuation Common mode: Typicay 140 db Transverse mode: 3 db down at 1000 Hertz, 40 db down per decade to beow 50 db with resistive oad. Linear devices are used for ine synchronization, which prevents phase shift errors normay associated with simpe current transformer zero current crossing acquisition circuits. The microprocessor-contro accuratey seects the correct tap to maintain the output, typicay at 2.5% of nomina, and corrects for votage disturbances within one cyce. Digita processing provides fast and accurate reguation without over- or under-shoot. Shieding The transformer has 3 copper shieds to minimize inner winding capacitance, transients, and noise couping between primary and secondary windings. Inner winding capacitance is imited to.001 pf or ess. Device Overoad Rating 200% for 10 seconds. 1000% for 1 cyce. Correction Time The output votage is corrected within 1 cyce Efficiency 97% typica Harmonic Distortion Less than 1% THD added to the output waveform Line Votage Reguation Input Line Votage: +10%, -20% Output Line Votage: ±2.5% typica (±3% maximum) +15% +10% INPUT Industry Standard Wide Range Protection Extended Line Votage Reguation iona Extended Range for Intermittent Duty ony: Input Line Votage: +10%, -40% Output Line Votage: ±5.5% typica (±6% maximum) +13% +10% INPUT Industry Standard Extended Range Protection -20% -30% Extended Input Range Protection -40% Extended Input Range Protection +8% +3% -3% -13% +8% +5% -6% -13%
SELECTION GUIDE Singe Phase STANDARD VOLTAGES MODEL NUMBER 5**X-5K-7D 5**X-8K-7D RATING 5 8 INPUT VOLTAGE VOLTAGE DISTRIBUTION See Beow(1) See Beow(1) CABINET ENCLOSURE (INCHES) WEIGHT (LBS) 344 364 BTU 510 810 5**X-10K-7D 10 See Beow(1) 438 1020 5**X-15K-7D 15 See Beow(1) 501 1540 5**X-20K-7D 20 See Beow(1) 554 2050 5**X-25K-7D 25 See Beow(1) 634 2560 Three Phase STANDARD VOLTAGES MODEL NUMBER 8**X-10K-7A RATING 10 INPUT VOLTAGE VOLTAGE DISTRIBUTION See Beow(1) CABINET ENCLOSURE (INCHES) WEIGHT (LBS) 440 BTU 1025 8**X-15K-7A 15 See Beow(1) 520 1540 8**X-25K-7A 25 See Beow(1) 21.5W x 29D x 44H 700 2560 8**X-30K-7A 30 See Beow(1) 21.5W x 29D x 44H 720 3090 8**X-45K-7A 45 950 4600 8**X-50K-7A 50 970 5110 8**X-75K-7A 75 1100 7670 8**X-100K-7A 100 1660 10250 8**X-125K-7A 125 1980 12790 8**X-150K-7A 150 2200 15400 8**X-225K-7A 225 56W x 41.5D x 77H 3300 23000 8**X-300K-7A 300 56W x 41.5D x 77H 4000 30750 8**X-500K-7A 500 72W x 48.5D x 77H 5500 51250 (3) Distribution Pane ions (1) The Distribution Pane for a 5-30 is 14"W x 10.5"H. Patch pates are avaiabe in 2"W x 10.5"H and 3"W x 10.5"H sizes. Consut factory for Fush Mounted Receptace and Output Breaker Combinations. Other configurations and pate sizes are avaiabe, pease contact factory for detais. Distribution Pane ions for 45-500 are avaiabe, consut factory for detais. ion ERR1040 and certain votage seections and options may change the cabinet size. (3) Consut factory for agency verification. Consut factory for prices on non-standard sizes or votages not shown. Listings - UL Listed. CSA. ESA. Mode Number Position: 1st 2nd 3rd 4th 5th 6th Meaning: Phase Input Output Frequency Series 5= Singe B=208 L=208/120 X=60Hz 1ph=7D 8= Three C=240 G=240/120 W=50Hz 3ph=7A D=480 N=480/277 E=600 E=600/346 I=220 P=380/220 Q=380
OPTIONS Any of the foowing options can be incuded in the Series 700A Power Processor: PM2020 Three Phase Output Monitor Digitay dispays the output votages and output currents. It aso incudes the neutra current and ine-to-ine votages. Minimum and maximum vaues are recorded in EPROM. Aarm faut detection is programmabe on a readings. AOM2020 Three Phase Advanced Output Monitor Digitay dispays the output votages and output currents. It aso incudes the neutra current, ine-to-ine votages, watts, VARS, VA, PF, frequency, watt/hour, VA/hour, and VAR/hour. Minimum and maximum vaues are recorded in EPROM. Aarm faut detection is programmabe on a readings. iona on AMO2020: K-factor and %THD; measuring harmonics to the 31st order. iona Communications Capabiity on AMO2020: RS232 RS485 Ethernet TCP / IP Modbus Pus Modbus RTU / ASCII DNP 3.0 NOTE: PM2020 and AOM2020 avaiabe ony on 30 and above RBS2020 Reguator Bypass Switch If the eectronic votage reguator fais, this option bypasses the reguator, eaving the main isoation transformer active. Therefore, power conditioning is not affected. ERR1040 Extended Reguator Range Provides +10%, -40% input votage reguation range. Output reguation is +5%, -6%. Note: Loads beow 60% permit continuous operation at -40% input. UOV2020 Under / Over Votage Shutoff When the output votage goes above or beow the preset vaue, the unit eectronicay shuts off. The system must be reset by cycing the input breaker. The preset votages can be set from 75% of nomina, up to 115% of nomina. STC2020 Shunt Trip Consists of a 120v AC shunt trip coi soenoid, which is added to the main circuit breaker. When the shunt trip coi is energized, the main input circuit breaker shuts off. A manua reset is required. 120v AC power is suppied by the customer. PARAMETERS DISPLAYED Vots L-N, L-L Amps Phase-Neutra Phase Reversa Votage Imbaance F p kw R Frequency H kwh RH Limit Condition Reays %THD (Harmonics) K-Factor RS232 RS485 MODBUS Pus Up to 10 channe anaog outputs ADVANCED (AMO2020) STANDARD (PM2020) True RMS accuracy ± 2%, vots & amps. A minimum and maximum readings are stored. Fuy programmabe aarm settings for a parameters. = Standard = iona PSO2020 Under / Over Votage Shutdown And Loss Of Power Shutoff When the output votage goes above or beow the preset vaue or detects a oss of power, the shunt trip coi is energized, which in turn shuts off the main breaker. The preset votages can be set from 75% of nomina, up to 115% of nomina. To turn on the system, manuay reset the main circuit breaker. Incudes the STC2020 Shunt Trip option. REP2020 Remote Emergency Power Off (REPO) Consists of a guarded Emergency OFF button which when depressed, trips the Power Processor s input circuit breaker. The REPO station is equipped with a 50-foot cabe, and can be remotey ocated. To turn on the system, manuay reset the main circuit breaker. Incudes the Shunt Trip STC2020 option. AMO2020 Advanced Monitor PM2020 Standard Monitor