DEIF A/S. TAS-311DG Selectable AC transducer J (UK) Installation and start up instructions

Similar documents
DATA SHEET Selectable AC transducer TAS-311DG

DATA SHEET AC current single function transducer TAC-311DG/TAC-321DG

Installation and start up instructions. Paralleling relay type HAS-111DG uni-line G (UK) Synchronisation of generator to busbar

Protection relays and controllers. Types TRANSAL DC-2TF, ACV-3TF, ACI-3TF, PFC-2TF TRANSAL DC-2TB, AVC- 3TB, ACI-3TB, PFC-2TB

Installation and start up instructions. Detection of vector shift. Detection of over- and underfrequency. Generator disconnection on mains failure

Transducers for AC measurement. Types TAP, TAQ, TMF, TAA, TAV, TAC. Measurement of: watt, var, frequency, phase angle, voltage, current

Installation and start up instructions. Synchroniser type FAS-115DG uni-line H (UK) Synchronisation of generator to busbar

Installation and start up instructions. Synchroniser type FAS-113DG uni-line F (UK) Synchronisation of generator to busbar

DATA SHEET. Voltmeters and Ammeters,

DATA SHEET. Switchboard instruments,

DATA SHEET Reverse power relays, RMP-121D ANSI code 32

RMV-122D, RMV-132D ANSI

DATA SHEET. CIO multi-inputs. CAN bus-based I/O module

DATA SHEET. Paralleling relays, HAS-111DG ANSI code 25

DATA SHEET Differential current relays, RMC-131D ANSI code 87

DEIF A/S. Insulation monitor. Type SIM-Q

Function. Adjustment. Extra functions included. Modes. Housing

TCM-2 Thyristor Control Module DATA SHEET

Automatic synchronising relay

DEIF A/S. User s manual. Read synchroscope type RSQ-3. Precision LED synchronoscope. High immunity to harmonic distortion F (UK)

Theta 20A / 20V. Technical Data Sheet. Special Features

400,440Vac Vdc V, A, W, VA, var, Hz, V, Avg. A cos phi, sin phi and phi measurement kwh, kvarh (via Pulse Output)

RISH Ducer E13 3 channel transducer for AC current and voltage

n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V)

RISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

Theta Hz. Technical Data Sheet. Special Features

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

Data Sheet 066.8e. Transducers for Active and Reactive Power EW+B 2.2 DGW+B 2.2 VGW+B 2.2 DUW+B 2.2 VUW+B 2.2

Installation/operation instructions. Insulation monitor type SIM-Q/SIM-Q LF D (UK) Measuring range 1...0Mohm or 10...

Universal measuring transducer

POWER TRANSDUCERS ACTIVE AND REACTIVE SERIES: T-W WATT T-V VAR

Angle position transmitter Type RT-2 Marine bridge instrumentation C (UK) Measuring output: DC current signal 0..20mA or 4..

RISH Ducer E13 Transducer For Ac Current Or Ac Voltage With Different Characteristics

XUA1 - AC Voltage and phase balance relay

SINEAX TV 808, 2 channels Isolating Amplifier Unipolar/Bipolar

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out.

Measuring current transformers of the W, W series

SINEAX U 553 Transducer for AC Voltage

Installation / Monitoring Technique

TRIO-PS/1AC/24DC/ 5. Extract from the online catalog. Order No.:

XP2-R Power and Reverse Power Relay

Power analyzers and Energy Meters. Multifunction indicator. Type WM12-DIN. Product Description. How to order WM12-DIN AV5 3 D X.

Paladin Transducers 250 Series Class 0.5 and Class 0.2

PRetrans Table of contents

POWER TRANSDUCERS FOR SINGLE-PHASE AND THREE-PHASE NETWORK ISO P11P, P13P and P13B mm SERVICE MANUAL

Switching power supplies CP range, Linear power supplies CP-L range. Content

Series P. Applications

Power supply CP-D 24/1.3

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

Energy Management Energy Meter Type EM110

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

Energy Management. Type WM12-DIN. Product Description. How to order WM12-DIN AV5 3 D X. Type Selection. Input specifications

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

Power supply CP-E 24/0.75

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC71, PPC71

SINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar

Power supply CP-E 24/2.5

XF2 Frequency Relay. Manual XF2 (Revision A)

EA16, EB16, EA17, EA19, EA12 MOVING-IRON METERS Ammeters and Voltmeters

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

Power analyzers and Energy Meters Power Analyzer Type WM14-DIN

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Power supply CP-D 12/2.1

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

Micro Contactors. Micro Contactor Relays 10. Micro Contactors 11. Micro Contactors With Solder Pins 12. Coil voltages 12. Micro Reversing Contactor 13

DEIF A/S. Application Notes. MDR-2 test procedures. Test of current measurement. Test of differential current measurement.

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Type CP-S, CP-C & CP-A Switch mode

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Differential pressure sensors

MINI MCR-SL-UI-I-LP-NC

Primary winding current transformer, type WSK

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

LED Driver Constant voltage

Installation- / Monitoring technique

Energy Management Three-phase energy meter with output modules Type EM4-DIN

Power supply CP-D 24/4.2 Primary switch mode power supply

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Programmable AC Voltage Transducer MT416

LED Driver Constant voltage

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

Programmable AC Current Transducer MT418

Positive-guided relay outputs: 8 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6

Universal-Transducer Multi-E11-MU

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description

Transcription:

Installation and start up instructions TAS-311DG Selectable AC transducer Voltage, current, frequency or phase angle transducer Supply voltage up to 690V DEIF A/S Configuration via PC-interface possible 35 mm DIN rail or base mounting DEIF A/S Tel.: (+45) 9614 9614 Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615 Denmark E-mail: deif@deif.com

Description TAS-311DG is a micro controller based AC-transducer with 1 analog output for measurement of RMS-voltage, RMS-current, frequency or phase angle on an ACnetwork. Label The configured transducer is provided with a label with the following data (the example is for a voltage transducer): Coupling Type designation DEIF s order ack. No. to be stated when contacting DEIF Measuring range Primary values Measuring range Secundary values Condition of external voltage transformer Condition of external current transformer Output range Output limited to 4mA and 21.5mA Auxiliary voltage Max output load current output Min output load voltage output Distributor s ID Other information If. Special product The un-configured transducer is provided with a label with the following data: DEIF s order ack no can be found on a paper label on the transducerbox. About configuration see special manual. Page 2 of 9 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions, TAS-311DG Mounting instructions TAS-311DG is designed for panel mounting, being mounted on a 35 mm DIN rail, or by means of two 4-mm screws. Weight: Approx. 0.600 kg The design of the transducer makes mounting of it close to similar equipment possible, however make sure there is min. 50 mm between the top and bottom of the transducer and other equipment. The DIN rail must always be placed horizontally when several transducers are mounted on the same rail.

Connection diagram VOLTAGE/FREQUENCY CURRENT * With voltages above 480V phase-phase. The secondary side of the current transformer must be connected to earth. Alternatively a double insulated current transformer can be used. PHASE ANGLE * COUPLING 17 19 23/24 WC3 I WC3 II WC3 III L1 L2 L2 L3 L3 L1 L1 L1 L1 It is not necessary to protect the measuring voltage inputs. But it is recommended to use a 2A fuse for the supply input (terminals 1 and 3). The transducer is protected against ESD (electrostatic electricity), and further special protection against this during the mounting of the transducer is not necessary. Page 4 of 9 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions, TAS-311DG Connection/set up The transducer is equipped with a red LED for indication of errors in the calibration or the configuration. This LED is placed under the front plate. The function of the LED is as follows: Fast pulse 5Hz. The calibration data are corrupted. Contact DEIF. Slow pulse 1Hz. The configuration data are wrong or corrupted. Make a reconfiguration or contact DEIF. About configuration see special manual.

Opening of the unit The front panel is removed by means of a screwdriver. The front panel may be loosened in the right side first and is then totally demounted by moving the screwdriver towards left. Mounting of the front panel Press with a screwdriver as indicated by the arrow and press the front panel down with your thumb, simultaneously. It is recommended that one side of the front panel snaps into place before the other. Page 6 of 9 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions, TAS-311DG General technical specifications Accuracy: Voltage/current: Class 0.5 (-10 15 30 55 C) according to IEC 688 Frequency: Class 0.2 of f max. (-10 15 30 55 C) according to IEC 688 Phase angle: Class 1.0 (-10 15 30 55 C) according to IEC 688 Meas. current (In): 0.75/1.5/3.0/6.0A Meas. range (In): 0 200% Overload, currents: Load: Meas. voltage (Un): Overload, voltages: Load: Frequency range: Indication: Output: 20A max., continuously 75A max. for 10 s 240A max. for 1 s Max. 0.5VA 73/140/254/400V phase to neutral Meas. range (Un): 1 120% 127/240/440/690V phase to phase Meas. range(un): 1 120% U n can be set between 57.7 690V 1.2 x U n max., continuously 2 x U n max. for 10 s Min. 480k 30 45 65 80Hz Red LED function: (The LED is located behind the front plate) Calibration error = flash frequency 5Hz Configuration error = flash frequency 1Hz 1 analogue output Standard range: Output (0...100%): 0...1mA, 0 5mA, 0...10mA, 0...20mA, 0...1V, 0...5V, 0...10V Output (10...100%): 0.1...1mA, 0.5...5mA, 1...10mA, 2...20mA, 0.1...1V, 0.5...5V, 1...10V Output (20...100%): 0.2...1mA, 1...5mA, 2...10mA, 4...20mA, 0.2...1V, 1...5V, 2...10V Output (-100...0...100%): -1...0...1mA, -5...0...5mA, -10...0...10mA, -20...0...20mA, -1...0..1V, -5...0...5V, -10...0...10V Other ranges possible

Limit: Output load: Output cable: ±120% of nominal output Burden if current output: Max. 10 V (max. 1k ) Burden if voltage output: Max. 20 ma Max. length 30 m Ambient temperature: -10 55 o C (nominal) -25 70 o C (operating) -40 70 o C (storage) Temp. coefficient: Max. ±0.2% of full scale per 10 C Response time: Ripple: Galvanic separation: Current/voltage: <105 ms in the range 0...90 % of nominal input acc. to IEC 688 <300 ms in the range 0...30 % of nominal input <85 ms in the range 30...100 % of nominal input Frequency: <75 ms, typical value 50 ms Phase angle: <275 ms, typical value 200 ms Twice the class index (peak to peak measurement) according to IEC 688 AC aux. supply models: Between inputs, output and aux. supply: 3750V-50Hz-1 min. DC aux. supply models: Between inputs and outputs: 3750 V-50 Hz-1 min. Between inputs and supply: 3750 V-50 Hz-1 min. Between supply and outputs: 1500 V-50 Hz-1 min. Aux. supply voltage: 57.7-63.5-100-110-127-200-220-230-240-380-400-415-440- 450-480-660-690V AC ±20% 24-48-110-220V DC -25/+30% Consumption: (Aux. supply) 3.5VA/2W Climate: HSE, to DIN 40040 EMC: According to EN 61000-6-1/2/3/4 Protection: Housing: IP40. Terminals: IP20 to IEC 529 and EN 60529 Connections: Materials: Weight: Page 8 of 9 Max. 2.5mm² multi-stranded Max. 4.0mm² single-stranded All plastic parts are self-extinguishing to UL94 (V1) 0.600kg Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions, TAS-311DG Specific technical specifications Voltage: Meas. voltage: 57...690V AC Start value: 0 67% of end value End value: 100 120% of measuring voltage Connection: Star connection (UL1-N): 57V 400V AC Delta connection (UL1-L2): 100V 690V AC Current: Meas. current: 0.5...8A Start value: 0...67% of end value End value: 100% of measuring current Frequency: Meas. range: 20Hz...80Hz Start value: 20Hz...76Hz End value: 40Hz...80Hz Meas. range: 4Hz <end value - start value Connection: Star connection (UL1-N): 57V 400V AC Measuring range (Un): 30...120% Delta connection (UL1-L2): 100V 690V AC Measuring range (Un): 30...120% Phase angle: Reference: Delta phi = 180, sine wave Unom and Inom (Inom = 1A or 5A) Voltage influence 1.5% between 50 120% Unom Current influence 1.5% between 50 150% Inom 2.5% between 20 50% Inom Meas. range: 0 60 / 360 electrical degrees Start value: -359.9 360 End value: -359.9 360 Meas. span: 60 <difference between start and end values <360 Connection: WC1: (IL1 and UL1-N) or (IL2 and UL2-N) or (IL3 and UL3-N): 57 400V AC WC3 I: (IL1 and UL1-L2): 100 690V AC WC3 II: (IL1 and UL2-L3): 100 690V AC WC3 III: (IL1 and UL3-L1): 100 690V AC Measuring range (Un): 30...120% If the current transformer is placed in another phase than L1, the voltage is connected in accordance with the tables below. CT in phase L1 standard CT in phase L2 CT in phase L3 COUPLING 17 19 COUPLING 17 19 COUPLING 17 19 WC3 I L1 L2 WC3 I L2 L3 WC3 I L3 L1 WC3 II L2 L3 WC3 II L3 L1 WC3 II L1 L2 WC3 III L3 L1 WC3 III L1 L2 WC3 III L2 L3