User Guide. AC/DC Mini Clamp Meter. Model

Similar documents
Model True RMS AC/DC 30A Mini Clamp-on Meter. User Guide

User Guide. AC/DC Mini Clamp Meter. Model Introduction. Large 3 3/4 digit LCD display with 40 segment bargraph

True RMS AC / DC Power Clamp Meter Model

USER MANUAL. Model MA A AC Mini Clamp-on Meter. Additional User Manual Translations available at

User s Guide. Model MA A AC Mini Clamp-on Meter

R/C SMD Tweezers Multimeter Model RC200

400Amp True RMS AC Clamp Meter + NCV

400Amp True RMS AC/DC Clamp Meter Model EX613

User s Guide. 400A AC/DC Clamp Meter. Model MA Washington Street Melrose, MA Phone Toll Free

User's Guide. 800 Amp AC/DC True RMS Clamp Meter. Model EX Washington Street Melrose, MA Phone Toll Free

User s Guide. Digital AC/DC Clamp Meter Model 38394

User Guide. Digital AC/DC Clamp Meter Model 38394

USER MANUAL 600A AC Clamp Meter + NCV Model MA610

User's Guide Extech EX Amp Clamp Meter with IR Thermometer

Model: Pro95 TRUE RMS MILLIAMP CLAMP METER

DL6508 User's Guide. 1500Amp True RMS AC/DC Clamp Meter

2,000 counts, 200 Amp ACA/DCA, 600 V ACV/DCV, True RMS, OHMS, Continuity, Hold, Peak Hold FORK CURRENT TESTER. Model : FT-9950

DC/AC CLAMP METER ISO-TECH 2000 USERS MANUAL

User Guide. EasyView Digital Light Meter. Model EA31

Instruction Manual ICM 3091N Digital AC Clampmeter EN FR IT DE ES

400Amp True RMS AC/DC Clamp Meter with IR Thermometer Model EX623

2000 A DCA/ACA CLAMP + DMM,

Compact MultiMeters + Voltage Detector

ACA LEAKAGE TESTER OPERATION MANUAL. auto range, true rms. Model : DL-9954

200Amp AC Clamp Meter + NCV Model MA250

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español

USER MANUAL. Mini Multimeter with Non-Contact Voltage Detector (NCV) Model EX330

ET-3888 True RMS Clamp Meter. User Manual

AC Clamp Meter + Phase Rotation Tester

USER GUIDE. IR Thermal Scanner. Model IRT500

USER MANUAL. Model MA A AC Clamp Meter DMM Model MA445 True RMS 400A AC/DC Clamp Meter DMM

User's Manual. Clamp-on Power Datalogger. Model

312, 316, 318. Clamp Meter. Users Manual

Model ST Instruction Manual. True RMS Autoranging Digital Multimeter. reedinstruments. www. com

USER GUIDE. Mini InfraRed Thermometer with Laser Pointer MODEL 42500

DM-46 Instruction Manual

User s Guide. 400A AC/DC Clamp Meter. Model MA220

True RMS. AUTO RANGE MULTIMETER CAT III-1000 V category, Auto range, REL, Capacitance Hz, Duty, ACV, ACA, DCV, DCA, Ohms

DM-46 Instruction Manual

User s Guide. MultiView Series Digital MultiMeters Models: MV110 MV120 MV130

Compact Autoranging Clamp Meters. Models (400 A AC), (400 A AC/DC)

USER'S MANUAL DMR-6700

Pen Multimeter. Model

EX350 Series USER GUIDE. True RMS Digital Multimeters. EX350 True RMS Digital Multimeter EX355 True RMS Digital Multimeter with Temperature

User's Guide Mini Multimeter with Non-Contact Voltage Detector (NCV) Model EX330

EX360 Series USER MANUAL. True RMS Digital Multimeters. EX360 True RMS Digital Multimeter EX363 True RMS DMM with Temperature and µa AC/DC

User's Guide. Extech 800 Series 1000 Amp Clamp Meters with IR Thermometer

User Manual 4 wire Earth Resistance Tester Model GRT300

Passive Component LCR Meter

Digital Clamp Meter. User Manual

User s Manual. MiniTec TM Series. Model MN26 (Model MN26T includes temperature probe) Mini Autoranging MultiMeter

NOTE: Fully read and understand this manual before using this Digital Multimeter.

EasyView Light Meter with Memory

Pen Multimeter. Model

OPERATOR S INSTRUCTION MANUAL

Autoranging Multimeter Extech EX503

Not for Reproduction

Micro-Ohmmeter Model UM200

USER'S MANUAL ACDC-100 TRMS ACDC-100. Versatile AC/DC Clamp-on Multimeter Series

OPERATOR S INSTRUCTION MANUAL M-2625 AUTO RANGING DIGITAL MULTIMETER

OPERATOR S INSTRUCTION MANUAL

AC/DC CLAMP METER USER S MANUAL

1. SAFETY 1.1. SAFETY INFORMATION 1.2. SAFETY SYMBOLS

ATK Clamp Meter

DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL-860A OPERATION MANUAL

User Guide. 4 wire Earth Resistance Tester Model GRT Washington Street Melrose, MA Phone Toll Free

User's Manual. Model f/1f Power Clamp-on Meter

MS2030 CAT III 600 V A V AUTO RS232

USER'S MANUAL DMR-4350

MODEL: D03128 CLAMP METER

INSTRUCTION MANUAL. Model Autoranging DMM ProbeMeter TM. Measures voltage, resistance, frequency, capacitance, temperature, and duty cycle.

User Manual. All rights reserved. Specifications are subject to change without notice.

Non-contact Forehead IR Thermometer

OPERATING INSTRUCTION

Multifunction Digital

OWNER S MANUAL HH0308C. AUTO-RANGING DC/True RMS AC DIGITAL MULTIMETER

Digital Clamp Meter (TRMS) Model : 2727

CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL

Pen-type DIGITAL MULTITESTER

AMM-1022 Digital Multimeter USER`S MANUAL

POWER ANALYZER OPERATION MANUAL. Model : DW-6090A

PCMT20 PYLE C;",D J WWWPYLEAUDIO.COM

AC/DC DIGITAL CLAMP METER OPERATION MANUAL

EM420A/420B DIGITAL MULTIMETER OWNERS MANUAL Read this owners manual thoroughly before use

USER'S MANUAL DMR-2400

AM

USER MANUAL. FLIR CM72 and CM74 CLAMP METERS. CM74 600A True RMS AC/DC Clamp Meter

USER MANUAL. UV AB Light Meter. Model UV505. Additional User Manual Translations available at

Thank you again for choosing AstroAI, if you have any questions or concerns regarding your product, please contact us at

USER'S MANUAL DMR-4300

CONTENTS MS2033A. 1.Introduction Safety Information...01

USER'S MANUAL TBM061 TBM062 TBM063 TBM065

Model: &

Caution Symbol. AUTO RANGE MULTIMETER CAT III-1000 V category, Auto range, Peak hold Bar graph display, Max/Min, REL, Cap.

Model & MultiScope TM

1. SAFETY INFORMATION.1 2. DESCRIPTION SPECIFICATIONS.6 4. OPERATING INSTRUCTION Voltage measurement Current measurement 10

OPERATOR S INSTRUCTION MANUAL DIGITAL MULTIMETER

USER MANUAL. Extech EX850 True RMS 1000 Amp Clamp Meter. Bluetooth TM and Android TM ready. Patented

USER S MANUAL DMR-1500

Digital Clamp Meter Model: &

Transcription:

User Guide AC/DC Mini Clamp Meter Model 380941 P

Introduction Congratulations on your purchase of Extech s AC/DC Clamp Meter. This professional meter, with proper care, will provide years of safe reliable service. Front Panel Description 1. Current sense jaw 2. Measurement Trigger 3. Function switch 4. Data Hold key 5. Max Min key 6. One-touch DCA zero key 7. LCD Display 8. 40 segment bargraph display 9. Positive input terminal for V, HZ and 10. COM termin 1 2 5 6 7 8 9 P 3 4 10 International Symbols! Caution! Refer to the explanation in this Manual Caution! Risk of electric shock Earth (Ground) Safety This meter has been designed to be safe in use, but the operator must use caution in its operation. The rules listed below should be carefully followed for safe operation. 1. NEVER apply voltage or current to the meter that exceeds the specified maximum: 2. USE EXTREME CAUTION when working with high voltages. 3. DO NOT measure voltage if the voltage on the "COM" input jack exceeds 500V above earth ground. 4. NEVER connect the meter leads across a voltage source while the function switch is in the current, resistance or diode mode; doing so can damage the meter. 5. ALWAYS discharge filter capacitors in power supplies and disconnect the power when making resistance or diode tests. 6. ALWAYS turn off the power and disconnect the test leads before opening the back to replace the fuse or batteries. 7. NEVER operate the meter unless the back cover and the battery/fuse door are in place and fastened securely. 2

Operation AC Current Measurements WARNING: To avoid electric shock, disconnect the test leads from the meter before making current measurements. 1) Set the Function switch to the 40 or 200A AC range. 2) Press the jaw trigger and clamp around, fully enclosing a single conductor. Do not allow a gap between the two halves of the jaw. 3) Read the ACA value on the LCD. DC Current Measurements WARNING: To avoid electric shock, disconnect the test leads from the meter before making current measurements. 1) Set the Function switch to the 40 or 200A DC range. 2) Press the DCA zero key to null the meter display. 3) Press the Trigger to open the current sense Jaw. 4) Fully enclose the conductor to be measured. Do not allow a gap between the two halves of the jaw. 5) Read the DCA value on the LCD. AC Voltage Measurements WARNING: To avoid electric shock or damage to the meter, do not make any voltage measurements that exceed the maximum specified. 1) Set the Function switch to the VAC position. 2) Insert the test leads to the meter as follows: Red lead to V,Hz, terminal; Black lead to the 3) With the pointed end of the test leads measure voltage. Remember that voltage measurements are made in parallel with the device or circuit under test. 4) Read the ACV value on the LCD. DC Voltage Measurements WARNING: To avoid electric shock or damage to the meter, do not make any voltage measurements that exceed the maximum specified. 1) Set the Function switch to the VDC position. 2) Insert the test leads to the meter as follows: Red lead to V,Hz, terminal; Black lead to the 3) With the pointed end of the test leads measure voltage. Remember that voltage measurements are made in parallel with the device or circuit under test. 4) Read the DCV value on the LCD. 3

Resistance and Continuity Measurements WARNING: To avoid electric shock or damage to the meter, remove power to the circuit under test and discharge all capacitors. 1) Set the Function switch to the position. 2) Insert the test leads to the meter as follows: Red lead to V,Hz, terminal; Black lead to the 3) With the pointed end of the test leads measure resistance. Remember that resistance measurements are made in parallel with the device or circuit under test. 4) Read the resistance value on the LCD. 5) If the resistance is less than 40, the continuity beeper will sound. Frequency Measurements 1) Ensure that at least 0.1A AC is detectable with an ACA measurement before measuring Frequency. 2) Set the Function switch to the Hz position. 3) Insert the test leads to the meter as follows: Red lead to V,Hz, terminal; Black lead to the 4) With the pointed end of the test leads measure frequency 5) Read the Frequency measurement on the LCD in Hz. Additional Features Relative Measurements 1) Press the Zero key and the present measurement will Zero. 2) All subsequent measurements are displayed with respect to the zeroed reading. For example, if a 20A reading is zeroed and a 30A reading is subsequently measured, the LCD will display 10A. 3) To return to normal operation, press the zero key one more time. 4) Note that Relative mode is not available if the MIN/MAX mode is enabled. 5) Relative mode is not available in continuity or Hz mode. 6) Note that the Zero button is disabled if ohm and continuity or Hz functions are selected. 7) LCD displays relative numerical value without bargraph. Data Hold To freeze a reading on the LCD, press the Data Hold key. The HOLD icon will appear and the measurement will be held on the meter s LCD. To release the Data Hold function and return the meter to normal operation, press the Data Hold key again. Data Hold is disabled if ohm and continuity function are selected. MIN/MAX Reading Mode Pressing the MIN/MAX key allows the meter to display ONLY the highest and the lowest readings encountered. Press the MIN/MAX key once to view the minimum reading, press it again to view the maximum reading. The LCD will toggle between the MIN and MAX values. Press and hold MIN/MAX button for more than 2 seconds to return to normal operating mode. Zero function will be disabled when MIN/MAX is enabled. MIN/MAX is not available in continuity or Hz mode. 4

Specifications General Specifications Display Functions Polarity Current sensor Overload indication DCA zero adjust Display rate Battery 3-3/4 (4032 count) Digit LCD with 40 segment bargraph ACA, DCA, ACV, DCV, Resistance, Frequency, Continuity - indicates negative polarity Hall effect sensor type OL One touch zero key 3 readings/second (30 readings/second for bargraph) Two 1.5V AA batteries Operating temperature -10 o C to 50 o C (4 o F to 122 o F) Operating humidity Power consumption Sampling time Weight Dimensions < 85% RH Jaw opening 23mm (0.9 ) Standards Range Specifications Approximately 17mA DC 3 times/sec (display); 30 times/sec (bargraph) 225g (8 oz.) including battery 183 x 63.6 x 35.6mm (7.2 x 2.5 x 1.4 ) (HWD) IEC 1010 Category III 300V, Category II 600V Function Range Resolution. Accuracy Overload protect DC Current 40A 10mA ±(1.0% +2dgts) 400A DC 0 to 150A 100mA ±(1.0% +2dgts) 400A DC 150 to 200A 100mA ±(2.2% +2dgts) 400A DC AC Current 50/60Hz 40 to 400Hz 40A 10mA ±(1.0% +3dgts) ±(1.5% +4dgts) 400A AC 0 to 150A 100mA ±(1.0% +3dgts) ±(1.5% +4dgts) 400A AC 150 to 200A 100mA ±(2.2% +3dgts) ±(2.5% ±4dgts) 400A AC DC Voltage 400V 0.1V ±(1.0% +2dgts) 1000VDC AC Voltage 50/60Hz 40 to 400Hz 400V 0.1V ±(1.5% +2dgts) ±(2.0% +4dgts) 800V AC Resistance 40 to 400 0.1 ±(1.0% +2dgts) Beeper <approx 38 600V AC Frequency 1 to 100k 0.001-100 ±0.5% ±2dgts Sensitivity; 600V AC 10VAC 5

Maintenance Battery Replacement 1) When the low battery symbol appears on the LCD the batteries must be replaced. 2) Turn the meter off and remove the rear battery compartment screw. 3) Remove the battery compartment cover and replace the two 1.5V AA cells. 4) Replace the compartment cover and secure the screw. You, as the end user, are legally bound (Battery ordinance) to return all used batteries and accumulators; disposal in the household garbage is prohibited! You can hand over your used batteries / accumulators at collection points in your community or wherever batteries / accumulators are sold! Disposal: Follow the valid legal stipulations in respect of the disposal of the device at the end of its lifecycle Cleaning Caution: Use only a dry cloth to clean the plastic case. Copyright 2014 FLIR Systems, Inc. All rights reserved including the right of reproduction in whole or in part in any form www.extech.com 6