Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Similar documents
Harmonic Filtering. Compact, fast response harmonic mitigation solution. POWER QUALITY. NHP Electrical Engineering Products Pty Ltd

Power Factor. Power Factor Correction.

POWER FACTOR CORRECTION AND ITS PITFALLS

How Harmonics have led to 6 Power Factor Misconceptions

Thyristorised Automatic Power Factor

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Economical Solutions to Meet Harmonic Distortion Limits[4]

Harmonic control devices

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Design and Simulation of Passive Filter

Power Factor & Harmonics

7/15/2002 PP.AFD.08 1 of 28

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Harmonic Filtering in Variable Speed Drives

Power Quality Solutions

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

Active Harmonic Filter (AF3)

Compensation of Reactive Power Case Study

APPLICATION NOTE. Applying Type DD60 Capacitors in Harmonic Filter Applications. Total Power Factor PF = cosine ɸ

TECHNICAL NEWS CABLE CONSIDERATIONS [ISSUE 46] DECEMBER 05 FEATURES:

DC Traction and bar contactors

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Harmonic Distortion and Variable Frequency Drives

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Analysis of Harmonic Distortion in Non-linear Loads

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Understanding Input Harmonics and Techniques to Mitigate Them

CHAPTER 4 HARMONICS AND POWER FACTOR

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

McGill Power Sales & Engineering, INC.

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

High Technology Control

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Application Guidance Notes: Technical Information from Cummins Generator Technologies

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with Matrix AP Harmonic Filter vs. AFE Drive

Study of Power Factor Correction in Single Phase AC-DC Converter

DATA SHEET POWER CAPACITOR

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

POWER FACTOR CORRECTION USING BOOST CONVERTER

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

ISSN Vol.03,Issue.07, August-2015, Pages:

Power Factor and Power Factor Correction

MIRUS International Inc.

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES.

How adjustable speed drives affect power distribution

22.0 Harmonics in Industrial Power Systems

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

LINEATOR. Advanced Universal Harmonic Filter

Power Quality Monitoring and Power Metering Tutorial

Understanding Power Quality

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Active Harmonic Filter (AHF)

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Simulation & Hardware Implementation of APFC Meter to Boost Up Power Factor Maintain by Industry.

Question Paper Profile

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Introduction to Rectifiers and their Performance Parameters

Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost Regulator

Reducing Total Harmonic Distortion with Variable Frequency Drives

Power Quality Analysis in Power System with Non Linear Load

NJWA - Harmonics and Drives Proper System Design

Technical Paper. Harmonic Distortion in Data Centers

Low Pass Harmonic Filters

Dynamic Harmonic Mitigation and Power Factor Correction

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Chapter 2. The Fundamentals of Electronics: A Review

Harmonics White Paper

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Impedance, Resonance, and Filters. Al Penney VO1NO

LCR Parallel Circuits

BAKISS HIYANA BT ABU BAKAR JKE,POLISAS

Effective Harmonic Mitigation with Active Filters

Topologies for Optimizing Efficiency, EMC and Time to Market

ATYPICAL high-power gate-turn-off (GTO) currentsource

Improve Power Factor and Reduce the Harmonics Distortion of the System

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

Welcome SUMMARY SERVICE AND SUPPORT WHEN IT REALLY MATTERS. n Introduction. n Service and Support when it really matters

TUNED AMPLIFIERS 5.1 Introduction: Coil Losses:

Influence of Switching Elements on Harmonics and Power Factor Improvement

Harmonic Analysis and Its Mitigation Using Different Passive Filters

PFC Lite. How it works OMNIVERTER. OMNIVERTER November 14, 2015 Slide 1

A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

Principles for Controlling Harmonics

Transcription:

Issue #65 - December 2012 Technical News Industrial Electrical and Automation Products, Systems and Solutions Part 2: Harmonics The link between harmonics and power factor Written by Justin Charlot Product Manager Power Quality nhp.com.au nhp-nz.com

INTRODUCTION A significant shift between linear inductive loads to non-linear loads is taking place. The benefits of these non-linear loads in terms of overall efficiency, flexibility and control have contributed to the growth in this market. Direct online (DOL) motors and soft starters are being replaced with variable speed drives, incandescent lights replaced by fluorescent and LED lighting, and the sustained growth in the automation industry has resulted in more data centres, switched mode power supplies and UPS systems being installed. The generation of harmonics by these non-linear loads and the problems they cause is discussed in detail in the previous NHP Technical News Edition (Issue #64 Harmonics: Part 1 - Where they come from, the problems they cause and how to reduce their effects). One very important aspect of this shift is the impact harmonics is having on power factor. In this edition, we explain the link between harmonics and power factor and what this means for power factor correction and harmonic mitigation solutions. The electrical power (apparent power) that is delivered through the power mains by an electricity supplier is comprised of active power (kw), which actually does the work, as well as reactive power (kvar) and distortion power. Reactive power is the power required to produce a magnetic field to enable real work to be done. This reactive power is necessary to operate equipment that requires a magnetic field to function. For example, linear inductive loads such as induction motors require a combination of active power (kw) from the supply and reactive power (kvar) to maintain the electromagnetic field required by the windings. Only real power (kw) is delivered at the fundamental frequency i.e. 50Hz. Since non-linear loads draw current at the fundamental frequency as well as harmonic frequencies, the current drawn at harmonic frequencies contribute to the overall power consumption or apparent power (kva). Distortion power is the result of current harmonics drawn from the network by non-linear loads. Examples of nonlinear loads include equipment that operates via a rectifier circuit such as variable speed drives, switched mode power supplies, UPS systems, data centres and electronic ballasts used in fluorescent lighting. Power factor refers to the ratio of real power to apparent power or Real Power (kw) Apparent Power (kva) The power factor is desired to be kept as close to unity as possible. As the power factor decreases, the apparent power draw increases. As a result the size of the transformer and installation power wiring may need to be increased to allow for the increase in current. Many supply authorities charge for the base load (kw) and a maximum demand tariff. If this tariff is measured in kva, then improving the power factor will reduce power costs. It is important to note that total or true power factor is influenced by two factors; displacement power factor and distortion power factor. 2

Displacement Power Factor Displacement power factor is defined as the ratio between apparent power (at the fundamental frequency) and real power. Or, in other words PFdisplacement =cos(θ), where θ is the phase shift between voltage and current at the fundamental frequency (refer to Figure 2). Therefore, inductive loads such as induction motors will affect the displacement power factor. When the load is inductive, the inductance tends to oppose the flow of current, storing energy then releasing it later in the cycle. The current waveform lags behind the voltage waveform. When the load is capacitive, the opposite occurs, and the current waveform leads the voltage waveform. So, lagging versus leading is another way of saying the net reactance is either inductive or capacitive. Total Power Factor The relationship between displacement power factor and distortion power factor is further highlighted in Figure 3: Figure 3: Total Power Factor Therefore: S 2 = P 2 + Q1 2 + D 2 and Q 2 = Q1 2 + D 2 Figure 2: Phase shift between voltage and current at the fundamental frequency Distortion Power Factor Distortion power factor is the ratio between the current at the fundamental frequency and the total current. As shown in the following derivation, distortion power factor can be shown to be a function of total harmonic current distortion (THID): Therefore what we can decipher from Figure 3 is that displacement and distortion power factor contributes to the total power factor. To improve total power factor means that both the total harmonic current distortion and reactive power at the fundamental must be compensated. Prime examples of how different equipment influence total power factor are illustrated below: Direct online (DOL) motors are an inductive source with a typical total power factor of around 0.8-0.85i. The harmonic content is low to non-existent for a DOL motor, and hence the total power factor of 0.85i is influenced primarily by the displacement power factor of the load. To improve the total power factor, we must improve the displacement power factor. Power factor correction systems consisting of capacitor banks provide an alternative reactive power source. Hence, the introduction of power factor correction improves the displacement power factor and total power factor. A 6 pulse variable speed drive (VSD) exhibits good displacement power factor, typically around 0.95i. However, VSDs produce harmonics, which influence the total power factor and as a consequence, the total power factor of a 6 pulse VSD may actually be around 0.87i. This means that a traditional power factor correction system is not a suitable solution to correct the total power factor since the VSD already has good displacement power factor. Rather, we must mitigate the harmonics produced by the VSD. There are a few common methods available to mitigate the harmonics associated with a 6 pulse VSD. These include: Equation 1: Distortion Power Factor [1] As evident in Equation 1, distortion power factor can be improved by reducing the current harmonic distortion. There are many different ways of mitigating harmonics, which will be application dependent. For example, passive harmonic filters (PHF) are specifically designed to mitigate harmonics produced by a 6 pulse variable speed drive (VSD), while active harmonic filters (AHF) can compensate any type of non-linear load connected to a three phase power network. AC line choke / DC link choke Passive Harmonic Filter (PHF) Active Harmonic Filter (AHF) Therefore, by mitigating the harmonics produced by the VSD, we are improving the distortion power factor component and consequently improving the total power factor. 3

Traditional Power Factor Correction Systems Traditional Power Factor Correction Systems consisting of capacitor banks (refer to Figure 4) are designed to improve lagging (or inductive) displacement power factor by providing an alternative source of reactive power and reducing the amount of reactive power sourced from the electricity supplier. There is no escaping the fact that the inductive loads require reactive power but you can choose where the bulk of the reactive power is sourced from. The impedance of the inductor increases as the frequency increases as highlighted by Equation 3 hence a tuning frequency of 189Hz serves the purpose of blocking the 5th order harmonics and above. Equation 3 Where XL is the inductive reactance (kvar) f is the system frequency (Hz) L is the inductance (mh) Figure 4: Capacitor bank used in traditional PFC systems The impedance of the capacitor decreases as the frequency increases, as highlighted by Equation 2. Equation 2 where: Xc is the capacitor reactance (kvar) f is the system frequency (Hz) C is the capacitance of the capacitor (µh) Hence, harmonics lead to a higher capacitor current, which can result in premature depletion of capacitors. The implementation of a detuned arrangement, where a reactor is connected in series with the capacitor is designed to force the resonant frequency of the network below the frequency of the lowest harmonic present, hence ensuring no resonant circuit and amplification of harmonic current. The reactor also serves the purpose of limiting inrush current, preventing interference with supply authority signals and blocking harmonics from the capacitor, which as previously mentioned prevents premature depletion of the capacitor. Figure 5 showcases the overall impedance of a capacitor bank. The impedance is capacitive at the fundamental frequency. As the frequency increases the nett impedance curve moves towards inductive. At a given frequency, the overall reactance is 0 and this is the series resonant point, also referred to as the tuning frequency of the capacitor bank. This tuning frequency should be selected to be below the lowest order harmonic present on the network. The standard tuning frequency is 189 Hz. Above 189Hz the reactance of the capacitor bank is inductive. Figure 5: Impedance curve of a traditional capacitor bank vs. inductive and capacitive impedance curves As the capacitor depletes (normal course of action over a period of time), the tuning frequency moves. In Figure 5, this tuning frequency will move towards the 5th harmonic and hence, the importance of maintenance of a PFC system. Some PFC systems are now available with a detuned arrangement at 134Hz i.e. designed to block 3rd harmonics and above. All of the above points bring to a head a few very important points regarding harmonics and traditional Power Factor Correction Systems 1. The PFC system is not designed to reduce harmonic current distortion. 2. The PFC system is not immune to the adverse effects of harmonic distortion simply because it has reactors installed on each step. A high presence of current harmonic distortion will contribute to premature capacitor failure with or without harmonic blocking reactors installed. Hence, following a power audit, NHP advises whether a harmonic mitigation solution is required prior to the installation of a PFC system to ensure the safe and reliable operation of the Power Factor Correction System. 4

Advanced PFC solutions More advanced PFC technologies in the form of active harmonic filters are now readily available on the market. The Schaffner ECOsine Active harmonic filter (as pictured in Figure 6) can perform both power factor correction and harmonic mitigation simultaneously and therefore improve both components of total power factor displacement power factor and distortion power factor. Hybrid solutions consisting of both traditional power factor correction systems and harmonic filters is a solution where both poor displacement power factor and high level of harmonic distortion is required to be addressed. Hybrid PFC and harmonics solution A hybrid solution will consist of both a traditional PFC system to address displacement power factor and a harmonic mitigation solution which will vary depending upon the non-linear loads installed (i.e. line chokes, PHFs, AHFs etc.). A hybrid solution will usually be a cost effective solution when both poor displacement power factor and high level of harmonics are an issue due to the combination of linear and non-linear loads installed on the network. There are important installation considerations, including the location of the PFC, AHF and external CTs. Ideally, the AHF would be compensating non-linear loads downstream of the PFC system (refer to Figure 7). Passive Harmonic Filter Power Factor Correction System Variable Speed Drive Active Harmonic Filter Motor Non-linear Loads Figure 6: Schaffner ECOsine active harmonic filters can perform dynamic reactive power compensation Figure 7: An example of a hybrid PFC and harmonics solution Harmonic Filtering Compact, fast response harmonic mitigation solution. power QUALITY Scan the QR code to download the Harmonic Filtering Brochure. NHP Electrical Engineering Products Pty Ltd Sales 1300 NHP NHP nhp.com.au Sales 0800 NHP NHP nhp-nz.com 5

Case Study - Waste Water Treatment Plant In this case study, NHP had conducted a site power audit at a waste water treatment facility. The objective behind this site audit was to assess the possibility of installing a PFC system to further improve the end users power factor and reduce kva tariffs. The data shown in Figure 8 shows displacement power factor (Average DPF) consistently around 0.99 to 1.0 and harmonic distortion power factor (HDPF) averaging around 0.93. Total power factor ranged around 0.88 to 0.94 and the total current harmonic distortion (THID) onsite ranged between 25-40% under load conditions (refer to Figure 9). There are a few events captured during this recording period which highlight the relationship between distortion power factor and the corresponding THDI level and displacement power factor. At approximately 1:48pm, the THDI% level dropped and this is reflected in an improvement in distortion power factor. However total power factor remained the same? This is due to a change in displacement power factor, which had dropped during this same period. This indicates the operation of linear inductive load(s) and possibly a reduction in the operation of non-linear load(s). This also appears to be the case early in the recording between 00:00 1:00am, however there was minimal load operating at this time (refer to Figure 8). For the majority of the recording period, total power factor was influenced primarily by the distortion power factor. In this instance, a traditional power factor correction system is not ideally suited for this application due to the high levels of current harmonic distortion and inherent good displacement power factor averaging 0.99 for the majority of the recording. A harmonic mitigation solution would reduce THID levels and improve the distortion power factor, hence improving total power factor and reducing kva tariffs and improving power quality on-site. IB THD IC THID Figure 8: Power Factor (Displacement, Distortion and Total) and kw load Figure 9: Harmonic Current distortion 6

SUMMARY The link between power factor and harmonics is commonly neglected and/or misunderstood but is fast becoming a topical issue that impacts the application of traditional power factor correction systems. With the growing presence of non-linear loads on the network, distortion power factor is an important aspect when considering solutions to improve power quality, facility capacity and tariff billing. The value of a power quality audit is increasingly more valuable as additional information such as distortion power factor along with current and voltage harmonic levels, displacement and total power factor and other power, voltage and current measurements, assist greatly in identifying the most appropriate solution. Traditional power factor correction systems are not typically designed to improve distortion power factor and advanced harmonic solutions, which also incorporate reactive power compensation is emerging more frequently in the global market. Scan the QR code to view the Power Factor Concept explained with a live demonstration Scan the QR code to view a live demonstration of the Schaffner ECOsine Active Harmonic Filter 7

SOURCES [1] Harmonics and how they relate to power factor, Grady W. M, Gilleskie, R. J, San Diego, CA November 1993 If you would like previous copies of Technical News, please complete the following form and fax to NHP on (03) 9429 1075. Name:... Title:... Company:... Please post to: address...... Telephone: ( )... Fax: ( )... Please email to:... Issue number:... To find out what issue number you require or to download all previous editions of NHP s Technical News, simply visit www.nhp.com.au/media and navigate to Catalogues & Literature Editorial content: Please address all enquiries to marketing@nhp.com.au. NTNL65 12 12 NHP Electrical Engineering Products Pty Ltd A.B.N. 84 004 304 812 Copyright NHP 2012 * Rockwell Automation products not available from these locations AUSTRALIA nhp.com.au Victoria Melbourne +61 3 9429 2999 Laverton +61 3 9368 2901 Albury/Wodonga +61 2 6049 0600 Dandenong +61 3 8773 6400 Tasmania Hobart +61 3 6228 9575 Launceston +61 3 6345 2600 New South Wales Sydney * +61 2 9748 3444 SALES Newcastle * +61 7 4779 0700 1300 NHP NHP Western Auckland +61 2 4960 2220 Australia Wollongong * Perth + 61 1300 NHP NHP +61 8 9277 1777 Act Canberra +61 2 6280 9888 Queensland Brisbane * +61 7 3909 4999 Townsville Rockhampton +61 7 4927 2277 Toowoomba * +61 7 4634 4799 Cairns +61 7 4035 6888 South Australia Adelaide +61 8 8297 9055 Northern Territory Darwin +61 8 8947 2666 NEW ZEALAND nhp-nz.com SALES 0800 NHP NHP +64 9 276 1967 Hamilton +64 7 849 0257 Napier +64 6 843 6928 New Plymouth +64 800 NHP NHP Wellington +64 4 570 0634 Christchurch +64 3 377 4407 Dunedin 0800 NHP NHP