STANDARDIZING ARC FLASH PPE LABELS

Similar documents
AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

REDUCING ARC FLASH HAZARD BY REMOTE SWITCHING

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Electrical Arc Hazards

Electrical Safety Policy Health and Safety FCX-HS03 Release 07/2018 Version 1

Arc Flash and NFPA 70E

2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation

Steve Kovach District Sales Engineer

Paul Dobrowsky Innovative Technology Services

DC ARC FLASH. THE IMPLICATIONS OF NFPA 70E 2012 ON BATTERY MAINTENANCE

ARC FLASH & PPE UPDATE. Michael Olivo, P.E. Aaron Ramirez, E.I.T.

Arc Flash Hazard and Mitigation 2 nd Workshop on Power Converters for Particle Accelerators June 14 16, 2010

Key factors to maintaining arc flash safety

First Draft Language

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

NOTICE ER Roland Flood Pumping Station Arc Flash Study

Arc Flash Analysis and Documentation SOP

Arc Flash Hazard Standards:

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

Arc Flash Calculation Methods

Cause, Effect & Mitigation Strategies

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Electrical Measurement Safety. Sponsored By:

Arc Flash Analysis Training

Electrical Overcurrent Studies

Electrical Severity Measurement Tool Revision 4

How does an Arc occur?

How does an Arc occur?

THE HISTORY OF FLICKER LIMITS

Education & Training

How OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

RMEL Safety Conference

{40C54206-A3BA D8-8D8CF }

COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS

Webinar: An Effective Arc Flash Safety Program

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

Selection of PPE Practical experience of different arc assessment methods and their comparison

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

NATIONAL ELECTRIC SAFETY CODE 2012 EDITION

Questions and Answers

Best Practice Reducing The Risk of Arc Flash Cross Over

C-Bus 8 Channel Low Voltage Relay

Ft Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems

SECTION POWER SYSTEMS STUDIES

DESIGN STANDARD DS 29

Environmental Health and Safety Office Hazardous Dust Control Guide

Pre-Installation Guide

2011 / Circuit Tracer

REVIEWED HES MANAGER

HIGH VOLTAGE RULES. Document Owner: HV Group. Authorised: Electrical Services Manager Liberty Primary Steel

Impact Wrench. 19 mm (3/4 ) MODEL 6906

COOPER POWER SERIES. External application of a motor start capacitor on a single-phase voltage regulator. Voltage Regulators MN225063EN

OWNER S MANUAL. RFC-14, RFC-23A, RFC-23AG, RFCS-23, And RFC-23GD25A

VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1

Installation Instructions

NORTHWEST FLORIDA STATE COLLEGE MONUMENT SIGNS WITH LED DISPLAYS

COOPER POWER SERIES. Upgrade instructions for CL-6 series control firmware. Voltage Regulators MN225071EN

FLUX CORE 90 WELDER ASSEMBLY & OPERATING INSTRUCTIONS

SHOP SAFETY AND TRAINING IN ACADEMIC DEPARTMENTS

PRODUCTIVELY SAFER LOCK-OUT TAG-OUT PROCEDURE

2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More

Digital Voltage Detector 0-999kV Operating Instructions VD1000PTM

Electrical testing safety Part 1: Preparing for absence of voltage testing

INTELLIMETER REGISTER

Earthing, HV Switching and Associated Operational Equipment. Approval: Chief Operating Officer

INDUSTRIAL WORK GARMENTS

S&C Scada-Mate Switching Systems Outdoor Distribution Interrupter Replacement 14.4 kv through 34.5 kv

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS

AT Advanced Wire Tracer. Users Manual

A53106 SERIES DC-TO-DC CONVERTER

PHASE ROTATION METER. Operating and Instruction Manual. a n d A C C E S S O R I E S

INSTRUCTION LEAFLET IL17537B F FRAME IQ ENERGY SENTINEL TM INSTALLATION INSTRUCTIONS FOR F FRAME IQ ENERGY SENTINEL TM

Analog Voltage Detector 1-450kV Operating Instructions VDAO450TM. Patent No. 6,275,022

ARC FLASH HAZARD ANALYSIS AND MITIGATION

SEI Certification Program Manual


Arc Flash Study Principles & Procedures for below 15 kv AC Systems. Xuan Wu, Dennis Hoffman, Ronald Wellman, and Manish Thakur

High Voltage Testing. Team 5: Justin Bauer, Matt Clary, Zongheng Pu, DeAndre Dawson, Adam McHale

Analog Voltage Detector 0-40kV Operating Instructions VDA040CTM

SWITCHING SAFETY & RELIABILITY CONFERENCE

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

ULTRA CUTTER MINI SAW

INSTRUCTION MANUAL (ATEX / IECEx)

ULTRA CUTTER PRO OPERATORS INSTRUCTION MANUAL. This manual covers all models 9, 11 and 13 HP

Instruction Manual. Manual de instrucciones. Guide d utilisation ET PMET Rev 808

INSTRUCTION LEAFLET IL17553B IQ UNIVERSAL POWER SENTINEL TM INSTALLATION INSTRUCTIONS FOR THE IQ UNIVERSAL POWER SENTINEL TM INTERNAL CT

2014 NEC Changes Part 1

TAG5000 WIRELESS PHASER. Instruction Manual HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS U.S.A.

Field Instruction Switching Activities. Purpose. Scope. Objective. Safety

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

OPERATION AND MAINTENANCE MANUAL fervi.com Riveter for threaded inserts Art ORIGINAL INSTRUCTIONS

Model 4210-MMPC-L. Multi-measurement Prober Cable Kit. Overview. Quick start guide topics. Related documents

Transcription:

The Electrical Power Engineers Qual-Tech Engineers, Inc. 01 Johnson Road Building #1 Suite 03 Houston, PA 1534-1300 Phone 74-873-975 Fax 74-873-8910 www.qualtecheng.com STANDARDIZING ARC FLASH PPE LABELS 1.0 THE STRATEGY OF STANDARD PPE LABELS The labeling of electrical equipment with regard to arc flash PPE level is an important and essential part of the safety program at every industrial facility. Some of the details of what goes on the labels are specified in NFPA-70E. The 70E recommendations include arc flash information only, but commonly the labels are applied with both arc flash and shock hazard information. Two basic approaches to labeling are generally used. 1. Individual Labels - One approach is to calculate the arc flash parameters at each piece of equipment in the plant and to apply a label which specifically includes the incident energy and flash protection boundary at that piece of equipment, as well as the name of that piece of equipment.. Standard Labels - The second approach is to calculate the arc flash parameters at each piece of equipment, but then to group pieces of equipment in certain ranges of incident energy and then to use the same label on all of those pieces of equipment. This approach results in a limited number of Standard Labels and is an attempt to simplify the interpretation of the information for the electrical worker, while maintaining high levels of safety in the work environment. Another factor in the labeling strategy is that most industrial plants have taken the approach of using two or three PPE levels for their staff. Three common incident energy levels are 1. cal/cm, 8 cal/cm, and 40 cal/cm. (Some are using other levels such as 11 cal/cm and 65 cal/cm, since it is possible to obtain clothing rated at those levels.) In this document the levels of 1. cal/cm, 8 cal/cm, and 40 cal/cm are used, as these have become the most common levels, and they are referred to here as PPE Levels of 0,, and 4, respectively. (This designation comes from the historical use of these levels in NFPA 70E for use with the Arc Flash PPE Categories Method.) Based on the concept of using three PPE levels, the labeling can be simplified if the labels are also based on using only PPE Levels of 0,, and 4. For locations where the calculated incident energy is < 1. cal/cm, a PPE = 0 label would be used. For locations where the calculated incident energy is > 1. cal/cm and < 8 cal/cm, a PPE = label would be used. For locations where the values are > 8 cal/cm and < 40 cal/cm, a PPE = 4 label would be used. It should be noted that it is possible to use other PPE Level designations, such as A, B, C rather than 0,, 4. In summary, the advantages of using Standard Labels are the following: 1. The labels simplify the information for the electrical worker.. Small changes in system parameters in the future would not require a label change as long as the energy was still in the range. Standardizing Arc Flash PPE Labels Page 1 Qual-Tech Engineers, Inc.

3. As more arc flash testing is done, it is likely that some of the equations will change for calculating the incident energy. If the changes are relatively minor resulting in energy values in the same range, the labels would not change. 4. The calculation of the incident energy is not accurate to within 0.1 calories, as is often implied by the values that are often given on the labels. 5. Using Standard Labels gives a uniformity of labeling for larger companies that have multiple plants. 6. The labels meet all of the requirements of NFPA 70E-018..0 EXAMPLES OF STANDARD LABELS The example labels given in this document are based on using Standard Labels. These labels are generally applicable to industrial power systems, but they do not include the specific detailed calculations for each particular location. The specific philosophy outlined here is based on implementing standard labels, which use only the PPE levels of 0,, and 4, as defined in Section 1.0. These standard labels provide a framework for developing similar labels for other standard operating practices, other system voltages, other working distances, and the use of remote switching or remote racking. These labels could be easily modified for variations in these parameters. In Table 1, typical parameters are given for some standard labels. Table 1 Summary of Standard XYZ Company PPE Labels Based on NFPA 70E-018 Nominal Working Min PPE Arc Flash PPE = Shock Boundaries Label Equipment Label System Distance PPE Rating Boundary Distance Glove Limited Restricted Size Metal Open Name Volts (Inches) Category (cal/cm ) (feet) (feet) Class Approach Approach (Inches) Enclosed Air Equipment Labels XYZ480-0 480 18 0 1. 1.5 0 3 ft 6 in 1 ft 4 x 3 X XYZ480-480 18 8.0 6.0 0 3 ft 6 in 1 ft 4 x 3 X XYZ480-4 480 18 4 40.0 17.0 5.0 0 3 ft 6 in 1 ft 4 x 3 X XYZ480>4 480 18 > 4 4 x 3 X XYZ4160-4,160 4 8.0 14.0 1 5 ft ft in 4 x 3 X XYZ4160-4 4,160 4 4 40.0 74.0 11.0 1 5 ft ft in 4 x 3 X XYZ13800-13,800 36 8.0.0 5 ft ft in 4 x 3 X XYZ13800-4 13,800 36 4 40.0 110.0 16.0 5 ft ft in 4 x 3 X XYZ-P PPE 4 x 6 XYZ-B Boundaries 7 x 4 In industrial facilities with metal enclosed switching devices, the following observations are often applicable, based on the standard labels in Table 1: 1. At MCC s and PDP s on 08V to 600V systems, the calculated incident energy at the incoming feed is frequently < 8 cal/cm. In those cases a PPE level of is adequate, and Example Label # could be appropriate for a 480V system.. At the main switchgear on 08V to 600V systems, the calculated incident energy at the main bus is frequently < 40 cal/cm. In those cases a PPE level of 4 is adequate for the feeder switches or breakers. Example Label #3 could be appropriate for a 480V system. Standardizing Arc Flash PPE Labels Page Qual-Tech Engineers, Inc.

3. For equipment that is down-line of MCC s and PDP s, the calculated incident energies are frequently in the categories of the PPE Levels of 0 and. Example Labels #1 and # could be appropriate for a 480V system. 4. For 4.16 kv systems, Example Labels #6 and #7 are given for metal enclosed equipment with PPE Levels of and 4. 5. For 13.8 kv systems, Example Labels #7 and #8 are given for metal enclosed equipment with PPE Levels of and 4. 6. At other voltage levels, similar labels can easily be derived from the example labels #1 thru #8. Example Label #9 provides a definition of what PPE is appropriate for each category level. This label could be placed at key points to provide the facility electrical workers with a reference for this information. Example Label #10 provides definitions of the various boundaries. This label could be placed at key points to provide the facility electrical workers with a reference for this information. Standardizing Arc Flash PPE Labels Page 3 Qual-Tech Engineers, Inc.

Example Label #1 Example Label # ARC FLASH PPE LEVEL 0: Working Distance 18" Minimum PPE Rating = 1. cal/cm Arc Flash Boundary = 1 ft 6 in SHOCK PROTECTION - 480 VAC 0 0 3 ft 6 in 1 ft XYZ480-0 ARC FLASH PPE LEVEL : Working Distance 18" Minimum PPE Rating = 8 cal/cm Arc Flash Boundary = 6 ft SHOCK PROTECTION - 480 VAC 0 3 ft 6 in 1 ft XYZ480- Example Label #3 Example Label #4 ARC FLASH PPE LEVEL 4: 4 Working Distance 18" Minimum PPE Rating = 40 cal/cm Arc Flash Boundary = 17 ft Note: PPE = at a working distance of 5 ft. SHOCK PROTECTION - 480 VAC 0 3 ft 6 in 1 ft XYZ480-4 ARC FLASH PPE LEVEL >4: >4 The potential arc flash incident energy is greater than 40 cal/cm for a working distance of 18. Operation or insertion/removal (racking) of switching device is not to be done unless the equipment is deenergized and confirmed to be deenergized. No work is to be done on energized electrical conductors. SHOCK PROTECTION - 480 VAC Energized parts are not to be exposed. XYZ480>4 Standardizing Arc Flash PPE Labels Page 4 Qual-Tech Engineers, Inc.

Example Label #5 Example Label #6 ARC FLASH PPE LEVEL : Working Distance 4" Minimum PPE Rating = 8 cal/cm Arc Flash Boundary = 14 ft SHOCK PROTECTION 4160 VAC 1 5 ft ft in XYZ4160- ARC FLASH PPE LEVEL 4: 4 Working Distance 4" Minimum PPE Rating = 40 cal/cm Arc Flash Boundary = 74 ft Note: PPE = at a working distance of 11 ft. SHOCK PROTECTION 4160 VAC 1 5 ft ft in XYZ4160-4 Example Label #7 Example Label #8 ARC FLASH PPE LEVEL : Working Distance 36" Minimum PPE Rating = 8 cal/cm Arc Flash Boundary = ft SHOCK PROTECTION 13,800 VAC 5 ft ft in XYZ13800- ARC FLASH PPE LEVEL 4: 4 Working Distance 36" Minimum PPE Rating = 40 cal/cm Arc Flash Boundary = 110 ft Note: PPE = at a working distance of 16 ft. SHOCK PROTECTION 13,800 VAC 5 ft ft in XYZ13800-4 Standardizing Arc Flash PPE Labels Page 5 Qual-Tech Engineers, Inc.

Example Label #9 This label is to provide a definition of what PPE is appropriate for each category level. PROTECTIVE CLOTHING AND PERSONAL PROTECTIVE EQUIPMENT PPE ARC FLASH PPE LEVEL 0 (For Tasks < 1. cal/cm ) Nonmelting fiber underlayers (e.g. cotton) Nonmelting fiber long sleeve shirt & pants (e.g. cotton) Arc Flash PPE Level is required if any part of the body or clothing is exposed to energized circuit parts within the defined working distance. ARC FLASH PPE LEVEL (For Tasks < 8 cal/cm ) Nonmelting fiber underlayers (e.g. cotton) Arc-rated long sleeve shirt & pants or coverall (> 8 cal/cm ) Safety glasses or safety goggles Hard hat, arc-rated face shield, and arc-rated balaclava ARC FLASH PPE LEVEL 4 (For Tasks < 40 cal/cm ) Nonmelting fiber underlayers (e.g. cotton) Arc-rated long sleeve shirt & pants or coverall Arc-rated arc flash suit and hood (system > 40 cal/cm ) Safety glasses or safety goggles Hard hat Safety glasses or safety goggles Hearing protection (ear canal inserts) Leather gloves Insulating gloves and tools as needed Hearing protection (ear canal inserts) Insulating gloves with leather protectors Heavy-duty leather shoes Insulated tools Hearing protection (ear canal inserts) Arc-rated gloves Heavy-duty leather shoes Insulated tools XYZ-P Standardizing Arc Flash PPE Labels Page 6 Qual-Tech Engineers, Inc.

Example Label #10 This label is to provide definitions of the various boundaries. APPROACH BOUNDARIES FOR SHOCK & FLASH PROTECTION As Defined in NFPA 70E-018 DEFINITIONS OF APPROACH BOUNDARIES: LIMITED APPROACH BOUNDARY An approach limit at a distance from an exposed energized electrical conductor or circuit part within which a shock hazard exists. (It is the closest distance an unqualified person can approach, unless accompanied by a qualified person.) RESTRICTED APPROACH BOUNDARY An approach limit at a distance from an exposed energized electrical conductor or circuit part within which there is an increased likelihood of electric shock, due to electrical arc-over combined with inadvertent movement, for personnel working in close proximity to the energized electrical conductor or circuit part. (It is the closest distance to exposed energized electrical conductor or circuit part a qualified person can approach without proper PPE and tools.) ARC FLASH BOUNDARY - When an arc flash hazard exists, an approach limit at a distance from an arc source at which incident energy equals 1. cal/cm (5 J/cm ). BOUNDARY REQUIREMENTS WHEN THERE IS AN EXPOSED ENERGIZED ELECTRICAL CONDUCTOR OR CIRCUIT PART: UNQUALIFIED PERSONS must stay beyond the limited approach boundary and/or the arc flash boundary, as dictated by the tasks being performed. QUALIFIED PERSONS must stay beyond the restricted approach boundary and/or the arc flash boundary, unless equipped with the proper PPE and tools, as dictated by the tasks being performed. XYZ-B Standardizing Arc Flash PPE Labels Page 7 Qual-Tech Engineers, Inc.

3.0 CAUTIONS The following items are noted here: 1. Equipment Maintenance The PPE labels are based on the proper operation of the up-line protective equipment. The protective equipment must be maintained and working properly for the PPE recommendation on the label to be appropriate for that location. a. Consequently, the proper maintenance of all equipment is a basic requirement for a good safety program. b. There is a note at the bottom of each label that emphasizes this point.. Switching As described in NFPA 70E-015 Table 130.7(C)(15)(A)(a), the normal operation of a circuit breaker, switch, contactor, or starter does not require arc flash PPE if all of the following are true: a. The equipment is properly installed. b. The equipment is properly maintained. c. The equipment is used in accordance with instructions included in the listing and labeling and in accordance with manufacturer s instructions. d. All equipment doors are closed and secured. e. All equipment covers are in place and secured. f. There is no evidence of impending failure. If any one or more of these items is not true, arc flash PPE is generally required. This guidance is part of NFPA 70E-018, Section 130.5, Arc Flash Risk Assessment, Table 130.5(C). A common policy is that the PPE Level determined for a given location is to be used for the switching of that device unless a Risk Assessment has determined that it is not required. 3. PPE = 0 In this document PPE = 0 corresponds to a maximum incident energy of 1. cal/cm at the defined working distance. If any part of the body or clothing is exposed to energized circuit parts within the defined working distance, then PPE = is required. For example, if the qualified person is working on energized equipment with exposed energized circuit parts, the person must wear the appropriate PPE. If the working distance is 18, the PPE level is 0, and the person is wearing cotton clothing (which is permissible) and leather gloves, it is essential that the parts of the body with exposed cotton clothing be beyond the 18 working distance. If the person is wearing leather and rubber gloves (as needed) and is working directly on the energized equipment, there may be a part of the arms that is covered with cotton sleeves but is within the 18. If that is the case, PPE = is required. This issue is significant, because the cotton clothing is flammable and as the working distance is reduced the incident energy increases exponentially. Consequently, if cotton clothing is exposed within the working distance, it could catch on fire during an arcing event. Qual-Tech Engineers, Inc. QT-610-0618 01 Johnson Road Building #1. Suite 03 Houston, PA 1534-1300 74-873-975 FAX 74-873-8910 www.qualtecheng.com Standardizing Arc Flash PPE Labels Page 8 Qual-Tech Engineers, Inc.