ABSTRACT 1 INTRODUCTION

Similar documents
Investigation on the Performance of Different Lightning Protection System Designs

Earthing of Electrical Devices and Safety

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Industrial and Commercial Power Systems Topic 7 EARTHING

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Electric Power Systems Research

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Ferroresonance Experience in UK: Simulations and Measurements

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Lightning transient analysis in wind turbine blades

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Lightning performance of a HV/MV substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Modeling insulation in high-voltage substations

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Analysis of lightning performance of 132KV transmission line by application of surge arresters

2 Grounding of power supply system neutral

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

2. Current interruption transients

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

SCIENCE & TECHNOLOGY

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Power Systems Modelling and Fault Analysis

Electric Stresses on Surge Arrester Insulation under Standard and

ABSTRACTS of SESSION 6

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

HV Substation Earthing Design for Mines

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

APPLICATION OF THE ELECTROMAGNETIC FIELD METHOD TO STUDY A COMMUNICATION SATELLITE SITE DAMAGED BY LIGHTNING

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Grounding for Power Quality

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

EPR Safety Mat Modelling & Field Testing Summary Report

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

Insulation Co-ordination For HVDC Station

HIGH VOLTAGE Insulation Coordination

A Guide to the DC Decay of Fault Current and X/R Ratios

Specialists in HV and MV test and diagnostics. Testing in Substations

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

3 Using AutoTransient to Carry Out a Simple Transient Study

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Lightning overvoltage and protection of power substations

Outdoor Installation 2: Lightning Protection and Grounding

Chapter 1. Overvoltage Surges and their Effects

Fatima Michael college of Engineering and Technology

7P Series - Surge Protection Device (SPD) Features 7P P P

EE 340 Transmission Lines. Spring 2012

Measurements for validation of high voltage underground cable modelling

FERRORESONANCE SIMULATION STUDIES USING EMTP

Power Quality and Reliablity Centre

The Lightning Event. White Paper

ELECTRICAL POWER ENGINEERING

System grounding of wind farm medium voltage cable grids

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Fig.1. Railway signal system

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

EE 740 Transmission Lines

CONTENTS. 1. Introduction Generating Stations 9 40

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

Research on State Estimation and Information Processing Method for Intelligent Substation

ET 40 - Electrician Theory Examination Marking Schedule

TECHNICAL REPORT. Insulation co-ordination

1. Introduction to Power Quality

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Grounding grid design for high voltage substations: An assessment of effectiveness for lightning currents

EE 741. Primary & Secondary Distribution Systems

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

Insulation Test System

Appendix D Fault Levels

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Transcription:

ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens, Greece ** The Manchester Centre for Electrical Energy, UMIST, PO Box 88, Manchester, M6 1QD ABSTRACT Lightning has been reported to cause a large number of wind turbine failures and the grounding system of the wind turbine plays an important part in protection against this lightning damage. The design of the grounding system serves two main purposes. Firstly, the safety of personnel who are in the vicinity of the grounding system at the time of a lightning strike or power system fault must be ensured. Secondly, the lightning or power system currents must be dispersed into the ground while preventing large overvoltages. In this paper the transient behaviour of wind turbine grounding systems are studied. The modelling and analysis capabilities of the general purpose program EMTP (Electro Magnetics Transient Program) have been investigated with necessary supporting calculations being developed. Simulation results are presented using both EMTP and a specialist grounding software, CDEGS (Current Distribution, Electromagnetic fields, Grounding and Soil structure analysis). Practical examples of grounding system designs are given. 1 INTRODUCTION A windfarm, as any other electrical system, must be grounded to provide a low impedance connection between the electrical equipment and the general mass of the ground. The grounding system should ensure the effective operation of protective devices, provide a reference potential for electrical equipment and prevent excessive overvoltages and potential gradients that may cause damage to equipment or threaten human life. Unlike conventional grounding systems that are relatively compact in size, the wide geographical area covered by a windfarm results in the windfarm grounding system spanning a considerable distance. This results in the inductive component of the grounding system impedance becoming large in relation to the resistive component. In addition, windfarms are often located in areas of high soil resistivity where a low impedance ground is difficult to obtain. Standard methods to determine the impedance of a grounding system based on simple formula are unsuitable for windfarms owing to their distributed nature. This paper examines the use of computer modelling to assess the suitability of windfarm grounding systems for protection against power system faults and lightning strikes. 2 TYPICAL WINDFARM ELECTRICAL DESIGN AND GROUNDING REQUIREMENTS A wind turbine typically contains an induction machine generator supplying a grounded star transformer winding at approximately 7V. The high voltage side of the local turbine transformer is wound in delta and is connected to the windfarm distribution cable. The windfarm cable system is then normally connected to a star transformer winding or equivalent at the windfarm substation. The star point is often grounded through a resistor to control the windfarm earth fault level. A number of grounding requirements exist within a windfarm to protect both equipment and human life. The windfarm electrical protection, in the form of fuses or ground-fault relays require a certain fault current to operate. The lower the grounding system impedance of the windfarm, the more likely the protection is to operate since the prospective fault current will be higher and the easier it is to detect fault conditions. Lightning strikes to a wind turbine will raise the local ground potential resulting in large differential voltages between the power cable phase conductors and armour/screen as well as the high voltage winding on the wind turbine transformer and the grounded case/low voltage winding. This differential voltage may be able to break down either the cable or transformer winding insulation and damage that piece of equipment. The lower the grounding impedance, the lower the voltage rise produced by the lightning strike leading to a lower likelihood of insulation breakdown. An injection of current into the ground from either a lightning strike or a power system fault will result in potential gradients along the soil surface. The magnitudes of these potential gradients will depend partially on the grounding system impedance. As humans and livestock could be killed by excessive potential gradients, the ground impedance should be low enough to minimise the danger of lethal step and touch voltages. 3 RESPONSE OF A GROUNDING SYSTEM TO POWER SYSTEM FAULTS AND LIGHTNING CURRENT Although the same grounding system is normally used for protection against both power system faults and lightning strikes, the response to either energisation source is dramatically different owing to the high frequency components contained in lightning current.

Lightning current is considered to have an average rise time of 5.5µs and a time to half value of 75µs with a peak current of 3kA [1]. This fast rise time results in high frequency components being injected into the grounding system. The grounding system inductance, significant in relation to the resistance for a large grounding system, causes these high frequency components to increase the total grounding impedance owing to the change in inductive reactance. This effect means that the grounding system resistance is not valid in the determination of the voltages expected to result from a lightning strike since the inductive reactance is not accounted for. Power system faults where the frequency of the injected current is much lower than that in a lightning wave may also see some effect of the grounding system inductance although this will not be as exaggerated at this 5/6Hz. 4 USE OF ELECTROMAGNETIC FIELD MODELLING TO ASSESS THE RESPONSE OF AN GROUNDING SYSTEM The fact that the grounding resistance, a commonly measured and calculated value, cannot be used to calculate the response of large grounding systems means that other approaches must be investigated. Such approaches include the use of electromagnetic field theory to model grounding systems and calculate their response to both low and high frequency excitation. Large grounding systems in soils of varying resistivity with current injection from a power system fault or a lightning strike can then be examined. Two commercial software packages, EMTP and CDEGS, have been used to apply electromagnetic models to windfarm grounding systems. Both programs can simulate the response of a windfarm grounding system to low frequency, high frequency and transient current injections. CDEGS is designed to analyse the response of a grounding system under both high and low frequency excitations. To analyse the response of the grounding system to a time domain transient, a fourier transform must be carried out to obtain the frequency spectrum. Once the grounding system response to these frequencies has been computed, an inverse fourier transform can be used to obtain the time domain response of the grounding system to this transient. This approach is detailed by Dawalibi [2]. CDEGS calculations involve an accurate representation of a grounding systems by the use of elementary segments. Various electromagnetic algorithms describe the electromagnetic fields in the surrounding area, complex mathematical expressions being translated in an effective computational algorithm. Transmission line models, are widely used to effectively simulate grounding system behaviour especially when examining high transient conditions. By extending the capabilities of EMTP, the response of a grounding system to transient phenomena can be computed using transmission line models. The software package is able to model an extensive grounding systems. It is used by modelling the grounding system using a lumped parameter model with high shunt conductance or a frequency dependant distributed parameter transmission line model. The mutual coupling between grounding system components is accounted for by treating them as different phases of a transmission line. The application of both of these two models of grounding systems is based on numerical methods. The trapezoidal rule of integration is used, due to stability and accuracy properties. 5 TYPICAL WINDFARM GROUNDING SYSTEM The grounding of a single wind turbine is normally achieved by placing a ring electrode around the foundation and bonding it through the foundation to the turbine tower. The foundation reinforcement bar is also connected directly or via the turbine tower to the ring electrode and will be effective in acting as an ground electrode since the surrounding concrete can be considered to have a resistivity equal to that of the surrounding soil [3]. However, it is normally ignored to provide a worst case analysis of the Vertical rods or strip electrodes (horizontal electrodes) are often used in conjunction with this ring electrode to achieve a certain value of ground resistance. A resistance of 1Ω or less (before it is connected to any other system) is stated in the appropriate British Standard [4] as being suitable for lightning protection purposes and a similar value can be found in other international standards/recommendations. The individual wind turbine grounds are usually connected by the metallic screen or armour of the main power cable running between the turbines. This has the effect of reducing the overall site ground impedance to a low value, often 1-2Ω. Where the windfarm is sited in an area of high soil resistivity, each turbine ground may be connected by a strip electrode in addition to the connection provided by the power cable screen/armour. 6 SAFETY CRITERIA AND EQUIPMENT OVERVOLTAGE RATINGS Criteria to ensure the safety of humans during power system faults are well defined in various standards and should be applied by the designer of an Similar criteria to assess the hazard to humans during lightning strikes are not as well defined but can be inferred from the IEC standard detailing the effects of current on the human body [5]. The vulnerability of equipment to lightning overvoltages should be established for a particular grounding system design. A 33kV/7V transformer may, for example, have a rated lightning withstand voltage of 17kV [6] and it is possible to assess the likelihood of a lightning strike producing an overvoltage above this level. This can be performed for all electrical equipment installed on a windfarm including power cables, transformers, circuit breakers, surge arresters etc.

7 EXAMPLE OF WINDFARM GROUNDING 7.1 Single Turbine The grounding arrangement of a wind turbine situated on the Greek island on Lemnos, as shown in Figure 1, can be used as an example of grounding system behaviour during lightning strikes, or power system frequency faults. 6 5 4 3 2 1 5 1 15 2 25 3 35 4 45 5 Four 12.5m Strip Electrodes One 5m Strip Electrode Figure 2 - Effect of short strip electrodes (lower plot) in comparison to longer lengths (upper plot) on reducing the maximum lightning voltage rise 7.2 Two Turbines Connected With Strip Electrode Figure 1 - Grounding Arrangement at Lemnos Generally, the response of a small grounding system such as the one described, will be as if it was purely resistive. However, if long strip electrodes are used to reduce the grounding system impedance, the relatively high inductance means that the performance of the system subject to a lightning strike containing many high frequency components cannot be clearly defined. The computed ground resistance of the arrangement described is 5.8Ω when the grounding system is situated in 1Ωm soil (a low soil resistivity). An energisation current of 1kA at 5Hz results in a maximum voltage of 5.8kV as expected. Similarly, the injection of a 5.5/7µs lightning wave with a peak current of 3kA results in a peak voltage of 174kV, the value expected for a purely resistive When a 5m long conductor is attached to the turbine base, the resistance is now calculated as 1.2Ω. The same injection of 3kA peak lightning current as before results, however, in a peak voltage of 54kV. This would suggest a grounding resistance of 1.8Ω. The reality is that this difference is caused by the high inductive reactance seen by the high frequency components of the lightning wave. This has been produced by the inductance present in such a distributed If the 5m electrode had been split into four 12.5m sections and attached to the four corners of the grounding system a lower ratio of inductance to resistance is achieved. The resistance of this arrangement is.98ω and the peak lightning voltage is 29kV, the value expected when injecting the current into a pure resistance. By using four short strip electrodes as opposed to one long strip electrode, the grounding design has been improved. This is shown in Figure 2. The computation for a single wind turbine grounded with a 5m strip electrode showed the effect that the electrode inductance has on the response to an injection of lightning current. As a result, the use of the earthing system resistance to estimate the GPR at a point following a lightning strike is inaccurate. As a further example of this consider a system in 1Ωm resistivity soil consisting of two turbine bases identical to the one used in 7.1 situated a distance of 1m apart with the grounding systems connected by strip electrode as shown in Figure 3. The computed resistance of the network is 18.59Ω and the maximum voltage rise for an injection of 1A at 5Hz is 18.59V. Turbine One 1m Turbine Two Figure 3 - Turbine Layout (not to scale) An injection of a lightning current with peak current of 3kA results in a maximum voltage of 868kV at the injection point. This can be compared to a voltage of 558kV that would be expected if the same current has been injected into the 18.59Ω resistance. The voltage waveform produced at the base of the first wind turbine is shown in Figure 4 along with the waveform expected had the injected current flowed into a pure resistance. Note that the inductance increases the peak voltage and changes the time to peak. 9 8 7 6 5 4 3 2 1. 5. 1. 15. 2. 25. 3. 35. 4. 45. 5. Actual Voltage Predicted Voltage Figure 4 - Predicted voltage waveform following lightning current injection into the measured resistance (lower plot) compared with computed result taking system inductance into account (upper plot) If the windfarm substation is assumed to be at a remote point and the high voltage system is grounded there, an overvoltage of 868kV will be present between the high

voltage transformer winding and the locally grounded case/low voltage winding possibly leading to damage. The ground potential at the second wind turbine, 1m away will also rise due to the injection of lightning current and is shown in Figure 5. 25 2 15 1 6 5 5 4 3 2 1. 5. 1. 15. 2. 25. 3. 35. 4. 45. 5. Figure 5 - Voltage at turbine two (remote from the injection point) Even though the second turbine is 1m away from the first, a peak voltage of over 5kV is still developed at the local ground, a value that would again potentially damage the transformer and other equipment. The slower time to peak and smoother waveform than that seen at turbine one is another consequence of the relatively high level of inductive reactance present in the system. 7.3 Five Turbines Connected With Strip Electrode. 5. 1. 15. 2. 25. 3. 35. 4. 45. 5. Short Strip Electrodes Strip Electrodes Joining Turbine Earths Figure 6 - Voltages at injection point of a wind turbine connected to short pieces of strip electrode or to the adjacent turbines with strip electrode The small oscillations seen in Figure 6 are caused by travelling waves propagating back and forth along the grounding electrodes and are common in any large 8 CONCLUSIONS Owing to the complex and distributed nature of a windfarm grounding system it is preferable to obtain the grounding design partially through the use of computational software. A windfarm grounding system must be designed to take account of human safety, power system protection and equipment overvoltage ratings. Modern wind turbines are rated at 1MW and are situated a considerable distance apart, often hundreds of metres, when installed on a windfarm. Consider five such turbines with a 6.5m radius ring electrode at the base, separated by 4m and situated in 5Ωm soil. The individual turbine ground electrodes are to be joined by the armour of a power cable but must, firstly be given a ground resistance of 1Ω to meet the relevant British Standard. Two strip electrodes of 35m are joined to opposite sides of the turbine grounding systems to achieve this 1Ω resistance and the overall windfarm impedance at 5Hz is calculated to be 1.9Ω. This arrangement of grounding system, although adhering to the British Standard, is not normal with most windfarm grounding system designers choosing to run strip electrode the full distance between two turbines. The addition of this extra strip electrode to run from one turbine base to the next would result in a extra 1.3km of electrode being needed for the whole windfarm. This would have the result of reducing the overall windfarm impedance at 5Hz to.9ω but the effect on the lightning performance of the grounding system is less clear. The plot of the voltage resulting from an injection of 3kA peak lightning current to the middle wind turbine of the five is shown in Figure 6 for both cases. The peak lightning voltage is the same in both cases but the voltage decays at a higher speed in the case of the turbines joined by strip electrodes. If one of the goals of the grounding system is to reduce peak overvoltages, the 1.3km of extra strip electrode used could be better employed locally to the wind turbine resulting in a system with a lower inductive reactance during a lightning strike. Examples have been given that show how such computational software based on electromagnetic field theory can be used to analyse a windfarm grounding system design. In particular, the difference in response of the grounding system to a power system fault and lightning fault has been examined. 9 ACKNOWLEDGEMENTS The work was partially supported by the European Commission, under DG XII Non-nuclear energy Programme, contract nr. JOR3-CT95-52 1 REFERENCES [1] M A Uman, The Lightning Discharge, Academic Press, 1987 [2]F P Dawalibi et al, Transient Performance of Substation Structures and Associated Grounding Systems, IEEE Trans. on Industry Applications, Vol. 31, No. 3, May/June, 1995 [3] E. K. Saraoja, Lightning Grounds, Chapter 18 of Lightning - Volume 2 edited by R H Golde, Academic Press, 1977 [4] BS6651 : 1992 - Lightning Protection of Structures [5] IEC 479 : Effect Of Current On The Human Body [6] H M Ryan, High Voltage Engineering and Testing, Peter Peregrinus on behalf of IEE, 1994 [7]F P Dawalibi et al, Transient Performance of Substation Structures and Associated Grounding Systems, IEEE Trans. on Industry Applications, Vol. 31, No. 3, May/June, 1995 1

1 M A Uman, The Lightning Discharge, Academic Press, 1987 2 F P Dawalibi et al, Transient Performance of Substation Structures and Associated Grounding Systems, IEEE Trans. on Industry Applications, Vol. 31, No. 3, May/June, 1995 3 E. K. Saraoja, Lightning Grounds, Chapter 18 of Lightning - Volume 2 edited by R H Golde, Academic Press, 1977 4 BS6651 : 1992 - Lightning Protection of Structures 5 IEC 479 : Effect Of Current On The Human Body 6 H M Ryan, High Voltage Engineering and Testing, Peter Peregrinus on behalf of IEE, 1994 /