EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

Similar documents
IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

Chapter 2-1 Transformers

148 Electric Machines

Walchand Institute of Technology. Basic Electrical and Electronics Engineering. Transformer

CHAPTER 2. Transformers. Dr Gamal Sowilam

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

86 chapter 2 Transformers

Transformers. gpmacademics.weebly.com

WELCOME TO THE LECTURE

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

The power transformer

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary.

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Spring 2000 EE361: MIDTERM EXAM 1

By Gill ( ) PDF created with FinePrint pdffactory trial version

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Module 1. Introduction. Version 2 EE IIT, Kharagpur

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

Code No: R Set No. 1

UNIT 4 TRANSFORMER 4.1 INTRODUCTION. Structure. 4.1 Introduction. 4.2 Basics of Transformer. 4.3 Equivalent Circuit of Transformer

Module 7. Transformer. Version 2 EE IIT, Kharagpur

CHAPTER 4. Distribution Transformers

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

ELECTRICAL ENGINEERING ESE TOPIC WISE OBJECTIVE SOLVED PAPER-II

Electrical Machines I : Transformers

Module 7. Transformer. Version 2 EE IIT, Kharagpur

ECE 3600 Transformers b

Hours / 100 Marks Seat No.

~=E.i!=h. Pre-certification Transformers

Engineering Science OUTCOME 4 - TUTORIAL 3 CONTENTS. 1. Transformers

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

TRANSFORMER THEORY. Mutual Induction

El-Hawary, M.E. The Transformer Electrical Energy Systems. Series Ed. Leo Grigsby Boca Raton: CRC Press LLC, 2000

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

SYNCHRONOUS MACHINES

EE2022 Electrical Energy Systems

VALLIAMMAI ENGINEERING COLLEGE

Transformer & Induction M/C

PROBLEMS on Transformers

Practical Transformer on Load

Transformers. Department of Physics & Astronomy Texas Christian University, Fort Worth, TX. April 23, 2013

Table of Contents. Table of Figures. Table of Tables

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014

PHYS 1441 Section 001 Lecture #22 Wednesday, Nov. 29, 2017

UNIT II MEASUREMENT OF POWER & ENERGY

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM I (EE, EN, EC, CE)] QUIZ TEST-3 (Session: ) Time: 1 Hour ELECTRICAL ENGINEE

Chapter 16: Mutual Inductance

Trade of Electrician. The Transformer

PHYS 1444 Section 501 Lecture #20

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

Chapter 33. Alternating Current Circuits

PART A. 1. List the types of DC Motors. Give any difference between them. BTL 1 Remembering

TRANSFORMER OPERATION

EE 221 Circuits II. Chapter 13 Magnetically Coupled Circuits

3.1.Introduction. Synchronous Machines

THE UNIVERSITY OF BRITISH COLUMBIA. Department of Electrical and Computer Engineering. EECE 365: Applied Electronics and Electromechanics

HPS Universal BUCK-BOOST TRANSFORMERS

Power systems 2: Transformation

Unit Transformers

A Practical Guide to Free Energy Devices

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Department of Electrical and Computer Engineering Lab 6: Transformers

EQUIVALENT CIRCUIT OF A SINGLE-PHASE TRANSFORMER

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Introduction : Design detailed: DC Machines Calculation of Armature main Dimensions and flux for pole. Design of Armature Winding & Core.

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

VOLTECHNOTES. Transformer Basics VPN /1

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

ELECTRICAL MACHINES - II COURSEFILE

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

PESIT Bangalore South Campus Hosur road, 1km before Electronic City, Bengaluru -100 Department of Electronics & Communication Engineering

PHYS 1444 Section 003 Lecture #19

Code No: R Set No. 1

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101)

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

Power. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt

EE 340 Power Transformers

Review 6. unlike poles cause the magnets to attract. like poles cause the magnets to repel.

PRACTICAL WORK BOOK. Basic Electrical & Electronics Engineering BE-104

EN Assignment No.1 - TRANSFORMERS

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Review: Lecture 9. Instantaneous and Average Power. Effective or RMS Value. Apparent Power and Power Factor. Complex Power. Conservation of AC Power

APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS


APPLICATION NOTE - 018

Transformers 21.1 INTRODUCTION 21.2 MUTUAL INDUCTANCE

Downloaded From All JNTU World

PHYS 1442 Section 004 Lecture #15

ECE 241L Fundamentals of Electrical Engineering. Experiment 8 A-C Transformer, Magnetization & Hysteresis

TRANSFORMERS INTRODUCTION

Units. In the following formulae all lengths are expressed in centimeters. The inductance calculated will be in micro-henries = 10-6 henry.

Electromagnetic Induction

COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ACADEMIC YEAR / EVEN SEMESTER QUESTION BANK

Transformer Factory Testing

Lecture 4 Power System Instrumentation. Course map

Transcription:

Department of Electrical Engineering Lecture Basic Operating Principles of Transformers

In this Lecture Basic operating principles of following transformers are introduced Single-phase Transformers Three-phase transformers Auto-transformers Instrument transformers

Introduction Transformer is a machine that has no moving parts but is able to transform alternating voltages and currents from high to low (step-up transformer ) and vice versa (step-down transformer). Transformers are used extensively in all branches of electrical engineering from the large power transformer employed in the T&D network to the small transformer of an electronic amplifier. 3

45VA -Ø Transformer 4

Single-phase transformer A simple single-phase transformer consists of two coils wound on a closed iron core as shown: Primary winding Secondary winding 5

Construction of Single-phase transformer Basically, a transformer has two windings: primary winding Secondary winding Each winding consists of many turns and are wound on a laminated iron core. The iron core is insulated with the windings. The core itself forms a closed iron magnetic circuit. Consequently, the windings encircle the core and the core encircles the windings. 6

Core type windings are wound around two legs of a magnetic core. Shell type windings are wound around the center leg of a threelegged magnetic core 7

Transformer action - Ideal Transformer Assumptions:. The winding resistances are negligible (R = 0). All fluxes are confined to the core and link both windings (leakage flux = 0) 3. Permeability of the core is infinite (I φ = 0) 4. o eddy current and hysteresis losses 8

Transformer action - Ideal Transformer (cont) When an A.C. voltage v applied to the primary winding: dφ v = e = () dt The core flux also links the secondary winding, then: dφ v = e = () dt From equations () and (): v v = = a 9

Transformer action - Ideal Transformer (cont) when a load is connected to the secondary winding, i will flow and will provide an mmf i for the core. i would immediately flow to establish another mmf i to oppose i since no mmf is required to establish a flux in the ideal core i i = 0 i = i Then: i i = = a 0

Transformer action - Ideal Transformer (cont) If the supply voltage is sinusoidal, then in rms values: Since V V = = a and I I = = a V = I V I input VA = output VA

Transformer action - Ideal Transformer (cont) Emf Equation of a Transformer (/) Φ = Φ m sinπft instantaneous value of induced emf/turn = dφ/dt volts = πfφ m cosπft volts = πfφ m sin(πft π/) volts

Transformer action - Ideal Transformer (cont) Emf Equation of a Transformer (/) rms value of induced emf / turn = 0.707 x πfφ m volts = 4.44 x fφ m volts Hence E = 4.44 fφ m volts E = 4.44 fφ m volts E = E 3

Phasor Diagram of Ideal Transformer action under o-load EEE344 Electrical Machines V = E I m Φ E E =( / ) x E 4

Example A 00kVA, 6600/400V, 50 Hz single-phase transformer has 80 turns on the secondary. Calculate: a) the approximate values of the primary and secondary currents; b) the approximate number of primary turns; and c) the maximum value of the flux. Ans: 30.3A, 500A; 30; 0.05Wb 5

Features of Practical Transformer the windings have resistances not all windings link the same flux permeability of the core material is not infinite, and core losses occur when the core material is subjected to time-varying flux Losses in Practical Transformer Copper losses ( I R losses ) Iron losses ( Core losses ) 6

Transformer Losses Copper losses ( I R losses ) Power losses due to the resistances in the primary and secondary windings P C = I R + I R Iron losses ( Core losses ) a. Hysteresis loss Power loss due to the alignment of magnetic dipoles in the iron core b. Eddy current loss Power loss due to the induced eddy current circulating in the iron core 7

Parameters of Transformer In order to analyze transformer at different loading conditions, based on the principles of transformer action, equivalent circuit of practical transformer is worked out for calculation. R eq X eq R C X m Equivalent Circuit of Transformer The four essential parameters of the transformer equivalent circuit are then measured by Open-circuited test, and Short-circuited test on transformer 8

Three-Phase Transformer A set of three similar single phase transformers may be connected to form a three-phase transformer (three-phase transformer bank). The primary and secondary windings may be connected in either star or delta configurations. 9

Characteristics of Three-phase Transformer Bank Ease of transportation Inefficient magnetic circuit, less efficient Higher capital cost than a single one -phase of the transformer at fault, the other two are not affected 0

Construction of Three-phase Transformer Usually 3-limb core structure 5-limb core may be used to reduce the overall height of a 3-limb core Magnetic flux shares the magnetic circuit Fault on one-phase very likely affects the other two phases

Three-phase Transformer 3 limb core structure 3- phase transformer

Three-phaseTransformers in T&D System 5kV Alternator Customers 3

3-Ø kv/380v Tx LV Side HV Side 4

Pole-mounted 3-Ø kv/380v Tx kv/380v 3-phase transformer fixed at a wooden pole 5

Turn ratio/voltage ratio/current ratio of 3-phase transformer (/4). STAR/delta ( Yd ) EEE344 Electrical Machines V V = 3.a = 3. ; I I = 3.a = 3. 6

Turn ratio/voltage ratio/current ratio of 3-phase transformer (/4). DELTA/star ( Dy ) EEE344 Electrical Machines V V = a 3 = 3. ; I I = 3 a = 3. 7

Turn ratio/voltage ratio/current ratio of 3-phase transformer (3/4) 3. DELTA/delta ( Dd ) EEE344 Electrical Machines V V = a = ; I I = a = 8

Turn ratio/voltage ratio/current ratio of 3-phase transformer (4/4) 4. STAR/star ( Yy ) EEE344 Electrical Machines V V = a = ; I I = a = 9

Auto-transformer transformer having a part of its windings common to the primary and secondary when a load is connected across b and c, then a current I will flow through the load. The current I will produce an m.m.f. in the core which will be balanced by a current I flowing in the complete winding 30

Auto-transformer The voltages and currents are related by the same turns ratio as in a two-winding transformer: V V = = a I I = = a 3

Single-phase Auto-transformer 3

Three-phase Auto-transformer 33

Example EEE344 Electrical Machines A φ, 00 kva, 000/00 V two-winding transformer is connected as an autotransformer as shown such that more than 000 V is obtained at the secondary. The portion ab is the 00 V winding, and the portion bc is the 000 V winding. Compute the kva rating as an autotransformer. 34

Example (cont) The current rating of the winding are: 00,000 I ab = = 500A 00 00,000 I bc = = 50A,000 Therefore, for full-load operation of the autotransformer, the terminal currents are: I H = 500A I L = 500 + 50 = 550A 35

Example (cont) ow, V L = 000V and V H = 00V Therefore, 000 550 kva L = = 00 000 00 500 kva H = = 00 000 (ans) (ans) ote: A φ, 00 kva, two-winding transformer when connected as an autotransformer can deliver 00 kva. 36

Advantages of Auto-transformer It effects a saving in winding material (copper or aluminum), since the secondary winding is part of the primary current. Lower copper loss, therefore efficiency is higher than in the two winding transformer. Lower leakage reactances, lower exciting current. Variable output voltage can be obtained. 37

Disadvantage of Auto-Transformer There is a direct connection between the primary and secondary sides. Should an open-circuit develop between points b and c, the full mains voltage would be applied to the secondary. The short-circuit current is much larger than for normal two-winding transformer 38

Application of Auto-transformer Boosting or bucking of a supply voltage by a small amount. (The smaller difference voltage between the output and input voltages the greater is the saving of winding material.) Starting of a.c. machines, e.g. induction motor, where the voltage is raised in two or more steps from a small value to the full supply voltage. Continuously variable a.c. supply voltages, normally connected between a low voltage supply in and a high voltage supply out. Production of very high voltages, e.g. 75kV and 400kV grid system 39

Instrument Transformers Instrument transformers are used to reduce the voltage or current magnitudes so that the measuring ranges of measuring instruments can be extended. Measuring Instruments are connected to the secondary of the transformers. The measured values should then be multiplied by the appropriate turns ratio to get the actual primary values.. Voltage Transformer VT (or PT) / is large and standard 0 V at the secondary.. Current Transformer CT / is small and standard 5 A or A at the secondary. 40

Voltage Transformer (VT) Fundamentally similar in principle to power transformers but with rated outputs in VA rather than kva or MVA. Operating at full supply voltage, the secondary current is very small so that the transformers may be regarded in the same way as a power transformer on no load. Current Transformer (CT) Transforms large primary current value in terms of its magnitude and phase to a smaller secondary current value. the secondary value is directly proportional to the primary value. ominal CT ratio (60~3000A/5A, 30~000A/A) 4

Protection CT ominal CT ratio (000/5, 00/5) Required to operate at many times full load current. Linearity under these conditions is not of great importance. The essential point is that saturation must be high enough to drive the magnetizing current and the secondary current under fault condition. P Primary Insulatio n S Iron area S P Ring type CT terminal Markings Ring type CT Secondary 4

Metering CT For non-protection purpose Metering CTs need perform very accurately but only over the normal range of load up to about 0% full load current. 43

Reasons for using Instrument Transformer Do not require special designed instruments for h.v. or heavy current measurements (the instrument ranges could be standardized) Electrical isolation from the primary (h.v. side) is achievable For safety reason, one terminal of the secondary winding can be earthed 44

About the Use of Instrument Transformer may have turns ratio error phase shift may exist between primary and secondary measuring quantities. CT is actually a step-up transformer with very large turns ratio (eg 500/), excessive voltage will exist between the secondary terminals if they were left open. EVER LET THE SECODARY OF A C.T. OPE-CIRCUITED 45

Department of Electrical Engineering ED of Lecture Basic Operating Principles of Transformers