P revolution passing from agriculture country to a

Similar documents
POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Electric Power Quality: Voltage Sags Momentary Interruptions

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9

Fundamentals of Power Quality

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

Introduction to Harmonics and Power Quality

T-68 Protecting Your Equipment through Power Quality Solutions

Power Quality Monitoring and Power Metering Tutorial

Emicon Engineering Consultants L.L.C.

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Fluke 40/41 Power Harmonics Analysers

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Thyristorised Automatic Power Factor

1. Introduction to Power Quality

Understanding Harmonics

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Fluke MDA-510 and MDA-550 Motor Drive Analyzer

An Introduction to Power Quality

UNIT-4 POWER QUALITY MONITORING

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

Thermal Imaging, Power Quality and Harmonics

POWER QUALITY AND SAFETY

QUESTION BANK PART - A

Power Analysis Summary

Power Quality Starts At the Load

Power Quality Basics. Presented by. Scott Peele PE

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motor Transformers and Distribution Systems

Tripping of circuit breakers in PV installations due to zero sequence field impedance

VOLTAGE WAVE QUALITY IN LOW VOLTAGE POWER SYSTEMS

ECET Modern Power

Earthing of Electrical Devices and Safety

Catastrophic Relay Misoperations and Successful Relay Operation

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

22.0 Harmonics in Industrial Power Systems

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Presents. Harmonics Years

IDEAL Test and Measurement THE BASICS OF POWER QUALITY

Fatima Michael College of Engineering & Technology

Although shunt capacitors

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

BALLAST HANDBOOK. Basic Reference Manual. Integral Ballast Characteristics and Performance Data High Pressure Sodium Metal Halide HL-301 5/03

Control Cable installation: Best Practice

Roadmap For Power Quality Standards Development

SureTest Model ST-1THD & ST-1THDC Instructions

SECTION PANELBOARDS

PRODUCT FEATURES TYPICAL APPLICATIONS

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

ULTRA-K Series 600K - he

Electrical Measurement Safety. Sponsored By:

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

THE TRADITIONAL general-purpose motor drive (or

Troubleshooting accelerometer installations

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

TEAMS Competition 2014

7. INSPECTION AND TEST PROCEDURES

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Substation Testing and Commissioning: Power Transformer Through Fault Test

Reliable Power Meters Multipoint Power Recorder

1C.6.1 Voltage Disturbances

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Harmonic Analysis to Improve Power Quality

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

Power Quality Evaluation of Electrical Distribution Networks

79/26 Series III Multimeter

Outline. Power Quality in Electrical Systems. Alexander Kusko, Sc.D., P.E. Marc T. Thompson, Ph.D.

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

Active Harmonic Filter (AF3)

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

EE 2028 POWER QUALITY

BED INTERCONNECTION TECHNICAL REQUIREMENTS

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

VALLIAMMAI ENGINEERING COLLEGE

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

PowerMonitor 5000 Family Advanced Metering Functionality

User's Guide. AC Circuit Load Tester. Model CT70

Power Quality Analysers

1C.4.1 Harmonic Distortion

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

GLOSSARY. PdMA MCEGold PRODUCT SUPPORT MANUAL. Active Filter sophisticated power electronic device for eliminating harmonic distortion.

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER,

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

OVERVIEW OF IEEE STD GUIDE FOR VOLTAGE SAG INDICES

A FUZZY EXPERT SYSTEM FOR QUANTIFYING VOLTAGE QUALITY IN ELECTRICAL DISTRIBUTION SYSTEMS

Transcription:

2004 EEE ntemational Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong Study of Power Quality: Problems in Commercial Buildings in Puerto Rico Eduardo. Ortiz-Rivera, Student Member, EEE Abstract- This paper describe studies of power quality done in Puerto Rico. A literature review will be done about different studies made in the past related to power quality problems in P.R. Data, from Lord Electric will be used to analyze some cases worked by this company in industrial buildings in Puerto Rico. Similarities and differences between existing problems will also be identified. To complete the objective, the software MATLAB was used where a program was developed to give the calculations of indices like THD, TF, DN, C-Message, and other indices, and also the spectrum of the signal sampling using Fourier analysis. Also, the use of digital filters is required for the elimination of noise and inter-harmonics to determine the indices and compare with the original results. The problem where was studied in Case 1 was that the Main Breaker was tripping for unknown reasons. n case 2 data transferring communication to U.S. was lost every Sunday in Home Depot at Bayamh, P.R. For the third case, hot spots, failed torque and methods are presented in Citibank Center at Cupey, P.R. to save money. Finally, this paper has a lot importance, because the problems of power quality as technology progresses will be more common in Puerto Rico and other places. This study will help to document answers about different problems of power quality in Puerto Rico and at the same time problems that could be common in other companies across the United States and the rest of the world. ndex Terms- Buildings, Grounding, Conductors. cases the initial conditions, the harmonics, the events, the Voltage, Current and Frequency, (VF), and the power are presented with their graphics and data. Also the paper will present the infrared method and examples of how the hot points can affect a power system. Before Power Quality is defined, it must be understand that there are different definitions from the point of view of utility and the customer. First, the utility definition is the quality of electric service necessary to provide reliable electric energy to the user at a satisfactory level so as not to disturb, harm, or affect the performance of electrical loads. But the customer definition is hassle-free power [l], P. The problems in Power Quality appeared for first time in the beginning of the 80's with the introduction of nonlinear loads like computers, power electronics, internet, etc [3], [4]. The principal Power Quality areas are transitory type interactions like electrical noise, lighting, switching surges, swell/sag/surge conditions and non-transitory type interactions like harmonics. To measure these types of problems, the CBEMA Curve. This curve was designed in the 80's from Computer & Business Equipment Manufacturers Association (CBEMA) to measure effects of the events of voltage in computers and at the same time is used as a data logger, a meter to register the different events caused by the electrical disturbances. Those electrical disturbances could be caused by the normal utility service like circuit breaker operations and automatic closers creating momentary switching problems and outages [3]. Devices like computer components can cause electrical disturbances, which produce high frequency noise and changes in the fundamental waveforms. This noise is known as distortion [5]. Other electrical disturbances are lightning strikes, motor starting & stopping, trees, welding, copy or printing machines, etc [41.. NTRODUCTON UERTO Rico, after 1950, experienced an economic P revolution passing from agriculture country to a country where the industrialization to high technology is one of the most important parts of the national economy Generally, for high technology industry the highest conditions of security and quality are required to develop products. For example, the cost to produce a kilogram of a medicine commercially is $200,000. Any problems in production can cause millions of dollars in losses. Problems like voltage sags, or other variations in the voltage, can produce losses of many millions of dollars. f the problems aren't fixed on time. For this power quality study are presented three cases in '. OF STUDY MA" BREAKER Puerto Rico, two of them in the Home Depot Area at Bayambn, P.R. The other case of study will be an infrared A. Date of study: October 1, 1999 until October 4, 1999 study in the Citibank at Cupey, P.R. For the first two Problem: The Home Depot of Bayambn, Main Breaker This work was supported in part by LORD Electric Co. EGG (Cat. No. CRD316T36W) 1600A 480/277V, at the 38KV Division. Rio Piedras, PR. 00936-3408 Substation was tripping for unknown reasons. E.. Ortiz-Rivera is with Department of Electrical Engineering. Michigan State U,,iversity, East Lansing, M, USA (e-mail: 'lace the Power Quality 38KV Substation ortizedu @egr.msu.edu). Main Breaker. 0-7803-8237-4/04/$17.0002004EEE 30 1

2004 EEE nternational Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong nstruments to perform the analysis: Power Meter, to record any event. Preliminary recommendations: Power Quality Analysis on the 38KV Substation Main Breaker Operational test on the Cutler Hammer equipment model STK2. Preliminary results: Possibility of high inrush current when power is re-established. nrush current (Flicker Effect) may exceed current rating of the Main Breaker Fig. 3. Final results: The time of delay on the breakers was changed. Originally, the Delay Setting was set at 2 s and the Short Delay Time was set on 1 s. Now, the Delay Setting is 4 s and for the Short Time Delay is 0.3 s. This is a temporary solution to solve the inrush current problem. 375v t 125V - Voltage interruption by the nrush Current Fig. 1. Voltage Phase A Spikes 11.00 Od04. 1% B. Discussion and analysis for Case 1 The problems with the inrush current occurred because the use of electric loads drastically increased creating overshoot for short time. The spike was faster than the operation of the breaker; hence, the substation breaker tends to trip. But this type of spike does not represent any danger to the system. Using Fourier analysis of the voltage phase A, the current phase A, and the ground currents, the analysis reflects that there are a lot of harmonics, due to noise created for the loads Fig 1-Fig 3. These harmonics are the result of the interaction of the environment noise and magnetic nonlinear loads. For this system, the production of harmonics could also be due to the size of the neutral line. The event with the inrush current was directly related with the tripping of the breakers. This event occurred when the Air Conditioner was starting. f the inrush current of the HVAC is more than the current rating of the breakers, the result is that the breakers will trip. The creation of this inrush current is because the HVAC consumes approximately a quarter of the total real power [6]-[8]. When the HVAC is quickly tumed off or turn on, the quantity of electrons in a small segment of the wire will change from a small quantity of electrons to a huge quantity of electrons or vice-versa producing inrush current [5]. The noise produced could be produced by interactions of telephone lines with power lines. The effects of the interactions of the harmonics and the inrush current are shown in Fig. 4 for Phase C. t shows a voltage interruption created by the inrush current when the Main Breaker trips. A voltage interruption will affect the power factor creating distortion. The distortion creates power losses leading to additional money that companies need to pay to the Electric Service Utility. Permanent implemented solutions for these types of problems are Shielded solation Transformers with K- factor protection; the ST'S are very useful for a 60Hz and high frequency grounding system bonded together, or, if 5 P" 25Pu 0 P" 750* 500A 250A 0Al 426 667 mllsecands/dlv Fig. 2. Phase A Percent of Overshoot (OO*Pu) 426W millisscrddh. Fig. 3. Phase A nrush Current i 00 OdW. asq the electric loads are very sensitive, it should be connect an G Receptacle to reject the noise to the loads. Another solution is to resize the neutral conductor reducing the current density [7], [9]. 302

2004 EEE nternational Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong 111. CASE 2 - UPS N THE COMPUTER ROOM A. Date of study: February 6, 2000 starting at 10:30 PM until February 7, 2000 500v The on Phase ( Problem: The Home Depot of Bayamh was losing the data transferring communication to U.S. every Sunday between 12:OO AM and 2:00 AM. Place of the Power Quality Analysis: The electric circuits for the UPS and the EMS system nstruments to perform the analysis: Power Meter, to record any event Preliminary recommendations: Direct study on the UPS and telephone lines. Also, the implementation of a Signal Reference Grid (SRG) can be considered for the ground terminal. A SRG is a mesh of all the grounds in one terminal. Preliminary results: Using a tracer for the electric circuits for the UPS, it was found that the Branch Circuit Panel that supplies power to the UPS was not connected to the EMS system. On January 16, 2000 starting at 1 1 :00 PM a small outage was observed but the UPS continued working normally. The UPS was on bypass mode. The solution was to change the position of switch from bypass mode to UPS mode to serve the loads. Final results: Used a Power Meter on the Branch Circuit Panel that supplies power to the UPS to record the different events. At 12:45 AM, the emergency generator started to run because the emergency generator was on exercise mode with duration of 30 minutes every Sunday at that time. Originally, the UPS was on bypass, which it did not offer any protection to the computers and when the Automatic Transfer Switch (ATS) performed the transfer to the emergency generator, it had created a problem with the change of voltage on the computers every Sunday. A loose neutral was found which it could cause possible voltage spikes and inefficiencies. Also these systems must have a dedicated ground line to avoid voltage spikes by other connected loads. After the implantation of the solutions, the system worked without problems. av 250V OV.250V '11' 426 667 m1ksecondrldiv Ov 516 667 mdliseconcft duration Fig. 4. Voltage Phase C after nrush Current Home Depot Bayamon (Computer Room) Phase A Voltage Wavefmm Feb 06 2000 23 32 12 13 333 millisecondrldiv 115 15V RMS CF = 1 39 Fig. 5. Voltages in the UPS on Computer Room Home Depd Bayamon (Computer Room) Gro.na CJrrern Harmon cz Fe0 C6 2000 23 32 12 Fourier Analysis Percent of voltage in each harmonic (3 B. Discussion and analysis for Case 2 Fig. 5 shows the Voltages A, B, C and Neutral in the UPS in the Computer Room. The Neutral Voltage is zero for a symmetric balanced three-phase system [6], but in Fig. 5, it is shown that the Neutral Voltage has oscillations resulting in an unbalanced system and the harmonics injection in the ground current and losing the data transferred. f the ground current is not zero, the power losses are created in the form of harmonics. The Fourier analysis is shown in Fig. 6. The harmonics will interrupt the data transferring communication. The voltage in the neutral, which it is very typical in commercial buildings where there are computers, nternet, Fig. 6. Ground Current Harmonics in the UPS telephone lines and other elements interacting between them creating noise, it looks with oscillations. These oscillations are created by the mutual inductance and resonance between the UPS, telephone lines and the computers. Finally with the use of the CBEMA Curve, Fig. 7 presents the events that affect the transfer data can be identified, in this case when the emergency generator 303

2004 TEEE nternational Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong runs on exercise mode. The stable region represents the maximum and minimum tolerance for the voltage allowed after turn on power across the time. The unstable events represent when the emergency generator starts to run on exercise mode. Each event is a voltage drop or increase of the nominal voltage. For the solution to resize neutral, it needs to be 1.73 times the phase conductor ampacity in a 208/120V shared neutral system [9]. t \ Unstable Region V. CASE 3 - ELECTRCAL SYSTEM ANALYSS FOR CTBANK CENTER A. Date of study February 2, 1999 Problem: Failed torque in the breaker panel, hot spots, and method to save money. Place for the nfrared Study: Breaker Panel nstruments to perform the analysis: nfrared Thermograph Camera. Preliminary recommendations: nfrared inspection and Thermographic maging Analysis Preliminary results for different panels: Many of the breakers in the panels were with hot spots. Many breaker lugs were hot. Creating a voltage drop of more than 100 mv. Breaker terminals were hot. Connections on the on the transformer bushing was hot. mproper torqued connections. Arcs produced between knots, see Fig. 8. Some Fins were not operating correctly. Neutral was hot. Final results: Replaced the hot breakers, cleaned connections of the transformer bushing and retorqued. The breaker lugs were hot because the circuit was working near full load. One recommendation was to create specialized panel for a better redistribution of the loads. Shutdown was required. Performed a preventive deenergize maintenance. B. Discussion and Anal.ysis for Case 3 The Citibank Center is one of the more important buildings for the Citibank Corporation in Puerto Rico. The main reasons are that it is the headquarters of Citibank Puerto Rico and it is where all the information is received and transmitted to the rest of the world. The last study in Citibank was performed without shutdown, in other words the study was performed when the Citibank was in full operation without affecting any work for the day. A lot of problems were identified using Thermographic maging Analysis. Problems found were hot spots in the breakers, hot terminals, hot transformer bushing, neutral hot, a voltage drop more than 100 mv, etc. A Thermographic maging Analysis for the Neutral Conductor is shown in the Fig. 9.The thermal problems are produced by the electric arc thermal energy between the knots. The solutions in some cases were simple like 0% Stable Events 10 YS 100 us 1 ms 8 33 ms Fig. 7. CBEMA Curve nstable Fig. 8. Properly torqued connection A vs. poor torqued connection B, between the knots Fig. 9. nfrared nspection for the Neutral Conductor changing the breaker, but in other cases the solution was maintenance and retorquing. n other cases the solution was to resize the conductors like the neutral, or to perform a preventive de-energized maintenance. The importance to eliminate the hot spots is to reduce the risk to create severe problems in the loads. With the infrared testing, loose connections, current overload, and defective insulators that cause safety hazards and outages when the building is in operations were detected. But how a simple retorque of the connections save money? n the case of Citibank, the following data was obtained for one electric switchboard and the screws with their additional power consumption. Proper Torqued Characteristics Proper Torqued Resistance =.06 Ohm 2400 Watts per Hour Resistance (W=12R) Poor Torqued Characteristics ncorrect Torqued Resistance =.6 Ohm V 304

2004 EEE nternational Conference on Electric Utility Deregulation, Restructuring and Power Technologies (DRPT2004) April 2004 Hong Kong 6400 Watts per Hour Resistance (W=12R) The Bus Bar was under a 200 amp constant load, hence the difference in Watts between proper and incorrect torque was 4000 Watts. Taking that the average price per Kilowatt-Hour in Puerto Rico is $0.035 for commercial buildings; the cost of energy wasted was $1,226 per year for only one connection. n this electric switchboard, they had around eight improper torque connections. A simple retorque of the connections saved a lot of money to the Citibank. Also, the study was doing when the bank was in normal operations. V. CONCLUSONS Three different cases of study about Power Quality in Commercial Buildings have been shown. n some cases, problems appear like waveshape, flicker effect, triplens, voltage sags and outages. All of these problems were found in commercial buildings in Puerto Rico. The most interesting is that some problems where common in the three cases like poor wiring connections or energy waste. The solutions were dependent on the problem. n some cases the solution was replace the breaker or change the time delay in the Automatic Transfer Switch but in other cases the solution was more expensive like preventive deenergize maintenance or a resize of the wires. This report proves that in Puerto Rico, many companies are interested in the topic of power quality because they can save a lot of money and prevent future problems to the loads. Also, this report shows that in Puerto Rico, we are working with the problems of power quality and finding solutions for the different problems. At the same time these power quality problems are typical problems that they can occur not only in Puerto Rico. These problems can occur in any commercial building around the world taking in consideration the changes in the technology and the increment of nonlinear loads like computers, fluorescent lights, internet, etc. t is expected that this paper will be used as a future reference in the area of Power Quality for commercial buildings. V. ACKNOWLEDGMENT The author gratefully acknowledge the contributions of Francesco Bernardo, Ronald Hopgood, RenC Mulero, Efrain O Neill and all the staff of LORD Electric Co., for all their help in this project and the opportunity to work with them. V. REFEFERENCES Heydt. G.T.; Electric Power Qualig, Second Edition, 1991, 5 Stars in a Circle Publications Anderson. L.M.; Bowes: K.B.; The Effects of Power-Line Disturbances on Consumer Electronic Equipment, EEE Trans. Power Delivery, vol. 5. pp. 1062-1065. Apr. 1990 Harvey. G.; Power Quality: what every electrical contractor needs to know, CEE NEWS.. Feb. 1. 1998. NTERTEClPRMEDlA Publication. Available: http://ceenews.com/ar/electric-power-quality-eve~/index.htm Miller-Woodall, L.; s your Power Dirty? Miron Zucker nc. Mar. 1988 Daley. J.; Load Transfer Strategies for Machine and Other inrush Loads. EEE Trans. ndustry Applications. vol. 34, pp. 1404-1410. Nov.-Dec. 1998 Stundurd Haiidbook for Electricol Eirgiiieers. 1 Oh Edition. 1969. Mc Graw-Hill Williams, N.: The NEC of Power Quality. CEE NEWS.. Mar.. 1998, NTERTEC/PRMEDA Publication. Available: h ttp://ceenews.com/ar/electric-nec_power-quality/index.htm Bingham. R. P.: The Power Quality Survey do it right the First Time. NETA World by Products/Technology Dranetz-BM. Edison. NJ, Available: http://www.dranetz-bmi.com/pdf/pqstartsload.pdf Nutioiiul Electric Code 1999. Section GroundinE. Article 250 [O] Borloo. G.: De Jaeger, E.; Dussart. M.: Robert. A., Practical mplementation of EC publications 1000-3-6 and 1000-3-7. Experiences in Belgium, Proc. 1998 EEE Hurmoiiics und QualiQ ofpower Coig, vol. 1. pp. 449-455. 11 ] Michaels. K.: Fundamentals of Harmonics, Bell South Corp. Electrical Construction & Maintenance. June 1. 1999. Available: http://www.ecmweb.com/ar/electric-fundamentals_harmonics/ 1121 Heydt. G. T.: Jewell, W. T.: Pitfalls of Electric Power Quality ndices. EEE Trans. Power Delivery. vol. 13. pp. 570-578. Apr. 1998 1131 Shen E.; Power Quality Troubleshooting at Service Panel. Fluke Corporation, 2002. Available: www. fluke.com [ 141 Sabin. D.D.: Brooks. D.L.: Sundaram. A.: ndices for Assessing Harmonic Distortion from Power Quality Measurements: Definitions and Benchmark Data. EEE Trans. Power Delivery. vol. 14, pp. 489-496. Apr. 1999 V. BOGRAPHY Eduardo. Ortiz-Rivera was born in Barranquitas. Puerto RCO n May 30, 1977 He received the BSEE degree (Magnd Cum Laude) from the University of Puerto Rico-Mayaguez in 2000 and the MSEE from Michigan State University in 2002 Currently. he is a Ph. D. candidate in Electncal Engineenng in the area of power electronics at MSU His research interests include power electronics for utihty applications. electnc motors. distributed power generauon. robotics and mathematical modeling tor dynamic systems Mr. Ortiz-Rivera has received the national GEM Doctoral Fellowship. Alfred Sloan Fellowship. Competitive Doctoral Engineering Fellowship and he is a Future Faculty Member of the University of Puerto Rico, Mayagiiez Campus. He has worked for Fermi National Accelerator Laboratory in the Physical Particles Division and LORD Electric Co. in the Transmission Lines Division. Mr. Ortiz-Rivera is a registered Engineer n Training in Puerto Rico. member EEE Power Systems Society. Society of Hispanic Professional Engineers. Tau Beta Pi and Golden Key nternational Honor Society. 305