PARTIAL DISCHARGE MEASUREMENT ON RING MAIN UNIT

Similar documents
PARTIAL DISCHARGE MEASUREMENT ANALYSIS ON RING MAIN UNIT

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Why partial discharge testing makes good sense

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

EI HIGH VOLTAGE INSULATION TESTING POLICY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

The importance of partial discharge testing throughout the development and operation of power transformers

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Simulation Model of Partial Discharge in Power Equipment

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

High-voltage test techniques - Partial discharge measurements

CVVOZE Power Laboratories (CVVOZEPowerLab)

Software System for Finding the Incipient Faults in Power Transformers

Prepared by Mick Maytum

Investigation of PD Detection on XLPE Cables

Testing of 400 kv GIS

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

INTERNATIONAL. High-voltage test techniques Partial discharge measurements

Specialists in HV and MV test and diagnostics. Testing in Substations

ECP HV INSULATION TESTING

Field Measurement of Transmission Cable Dissipation Factor

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

1. Introduction to Power Quality

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

PD Diagnostic Applications and TechImp solutions

ELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables

LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY. This instruction of a general nature and does not relate to specific standards.

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

ECP HV INSULATION TESTING

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

Disclosure to Promote the Right To Information

Electrical Equipment Condition Assessment

Error vs. Uncertainty Historical Perspective

7P Series - Surge Protection Device (SPD) Features 7P P P

Earthing of Electrical Devices and Safety

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

RCTrms Technical Notes

Comparison of measurement methods for partial discharge measurement in power cables

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

INTERNATIONAL STANDARD

(2) New Standard IEEE P (3) Core : (4) Windings :

High-Voltage Test and

Coherence and time-frequency analysis of impulse voltage and current measurements

PARTIAL DISCHARGE MEASUREMENT

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

EE 1402 HIGH VOLTAGE ENGINEERING

Simulation of Partial Discharge in High Voltage Power Equipment

Partial Discharge Patterns in High Voltage Insulation

Low voltage products in high altitudes

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Partial Discharge, Survey or Monitor?

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

GIS Disconnector Switching Operation VFTO Study

MEDIUM & HIGH VOLTAGE

Insulation Co-ordination For HVDC Station

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Test Specification for Type Approval

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

MAHALAKSHMI ENGINEERING COLLEGE

ALLOWABLE LIMITS TO SHORT TIME VOLTAGE DROPS IN HV WITHSTAND TESTS

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

The Reflective Wave Phenomena

L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849

Diagnostic testing of cast resin transformers

INTERNATIONAL STANDARD NORME INTERNATIONALE

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

7. INSPECTION AND TEST PROCEDURES

3MElectrical Markets Division

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

Australian Standard. High-voltage test techniques. Part 3: Definitions and requirements for on-site testing AS IEC , Ed.

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

GUJARAT TECHNOLOGICAL UNIVERSITY

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

High Field Electrical Conduction and Breakdown in Solid Dielectrics

)454 / 03/0(/-%4%2 &/2 53% /. 4%,%0(/.%490% #)2#5)43 30%#)&)#!4)/.3 &/2 -%!352).' %15)0-%.4 %15)0-%.4 &/2 4(% -%!352%-%.4 /&!.!,/'5% 0!2!

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

KP 376 KP/MMKP 376. AC and pulse metallized polypropylene film capacitors. Fig.1 Simplified outlines.

DEVELOPING TESTING PROCEDURES FOR HIGH VOLTAGE INNOVATION TECHNOLOGIES

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Transcription:

PARTIAL DISCHARGE MEASUREMENT ON RING MAIN UNIT Chaudhari Prashant P.*1, R. K. Jha *2 *1 (M.E Student SND College Of Engineering Yeola) *2 (Asst. Prof., S.N.D.C.O.E & RC, Yeola) Abstract As per IEC Standard 62271-200 we carried out testing on ring main unit or disconnector cum earthing switch (AC metal-enclosed switchgear and controlgear), The measurement of partial discharges may be appropriate as a routine test to detect possible material and manufacturing defects especially if organic insulating materials are used therein and is recommended for fluid-filled compartments. PDs are thus localized electrical discharges within any insulation system as applied in electrical apparatus, components or systems. In general PDs are restricted to a part of the dielectric materials used, and thus only partially bridging the electrodes between which the voltage is applied. The insulation may consist of solid, liquid or gaseous materials, or any combination of these. The term partial discharge includes a wide group of discharge phenomena: (i) internal discharges occurring in voids or cavities within solid or liquid dielectrics; (ii) surface discharges appearing at the boundary of different insulation materials; (iii) corona discharges occurring in gaseous dielectrics in the presence of inhomogeneous fields; (iv) continuous impact of discharges in solid dielectrics forming discharge channels (treeing).so to avoid the economical losses, and better life cycle of component or product in transmission system, SF6 Gas type ring main unit system having the DIN type of bushing and fuse holder (as an insulation) to protect the system in crucial condition and to withstand the High voltage stress, So to avoid the economical losses, and better life cycle of component or product in transmission system, Partial discharge is very important as an electrical aspects, so this paper deals with the partial discharge measurement effect on Ring main unit after power frequencies test; having protective parts of Fuse holder at cable end termination and Bushing Keywords: RMU, Type test Partial discharge test 1. Introduction 1.1 What is a partial discharge? Partial discharge (PD) is a localized electrical discharge that only partially bridges the insulation between conductors and which may or may not occur adjacent to a conductor. Partial discharges are in general a consequence of local electrical stress concentrations in the insulation or on the surface of the insulation. Generally such discharges appear as pulses of duration of much less than 1µs Corona is a form of partial discharge that occurs in gaseous media around conductors which are remote from solid or liquid insulation. The significance of partial discharges on the life of insulation has long been recognized. Every discharge event causes a deterioration of the material by the energy impact of high energy electrons or accelerated ions, causing 1

Chemical transformations of many types. The number of discharge events during a chosen time interval is strongly dependent on the kind of voltage applied and will be largest for a.c. voltages. It is also obvious that the actual deterioration is dependent upon the material used. Corona discharges in air will have no influence on the life expectancy of an overhead line PD measurements have nevertheless gained great importance during the last four decades and a large number publications are concerned either with the measuring techniques involved or with the deterioration effects of the insulation. The detection and measurement of discharges is based on the exchange of energy taking place during the discharge. These exchanges are manifested as: (i) electrical pulse currents (with some exceptions, i.e. some types of glow discharges); (ii) dielectric losses; (iii)e.m. radiation (light); (iv) sound (noise); (v) increased gas pressure; (vi) chemical reactions. Therefore, discharge detection and measuring techniques may be based on the observation of any of the above phenomena. The oldest and simplest method relies on listening to the acoustic noise from the discharge, the hissing test. The sensitivity is, however, often low and difficulties arise in distinguishing between discharges and extraneous noise sources, particularly when tests are carried out on factory premises. It is also well known that the energy released by PD will increase the dissipation factor; a measurement of tan υ in dependency of voltage applied displays an ionization knee, a bending of the otherwise straight dependency. This knee, however, is blurred and not pronounced, even with an appreciable amount of PD, as the additional losses generated in very localized sections can be very small in comparison to the volume losses resulting from polarization processes. The most frequently used and successful detection methods are the electrical ones, to which the new IEC Standard is also related. These methods aim to separate the impulse currents linked with partial discharges from any other phenomena. The adequate application of different PD detectors which became now quite well defined and standardized within reference 31, presupposes a fundamental knowledge about the electrical phenomena within the test samples and the test circuits. Thus an attempt is made to introduce the reader to the basics of these techniques without full treatment, which would be too extensive. Not treated here, however, are non-electrical methods for PD detection 2. The basic PD test circuit Electrical PD detection methods are based on the appearance of a PD (current or voltage) pulse at the terminals of a test object, which may be either a simple dielectric test specimen for fundamental investigations or even a large h.v. apparatus which has to undergo a PD test. For the evaluation of the fundamental quantities related to a PD pulse we simulate the test object, as usual, by the simple capacitor arrangement as shown in Fig. (2.1), comprising solid or fluid dielectric materials between the two electrodes or terminals A and B, and a Gasfilled cavity. This void will become the origin of a PD if the applied voltage is increased, as the field gradients in the void are strongly enhanced by the difference in permittivity s as well as by the shape of the cavity. For an increasing value of an a.c. voltage the first discharge will appear at the crest or rising part of a half-cycle. This discharge is a gas discharge creating electrons as well as negative and positive 2

ions, which are driven to the surfaces of the void thus forming dipoles or additional polarization of the test object. This physical effect reduces the voltage across the void significantly. Within our model, this effect is causing the cavity capacitance Cc to discharge to a large extent. If the voltage is still increasing or decreasing by the negative slope of an a.c. voltage, new field lines are built up and hence the discharge phenomena are repeated during each cycle. If increasing d.c. voltages are applied, one or only a few partial discharges will occur during the rising part of the voltage. But if the voltage remains constant, the discharges will stop as long as the surface charges as deposited on the walls of the void do not recombine or diffuse into the surrounding dielectric. 3. Condition to be measured 1) The coupling capacitor Ck shall be of low inductance design and should exhibit a sufficiently low level of partial discharges at the specified test voltage to allow the measurement of the specified partial discharge magnitude. A higher level of partial discharges can be tolerated if the measuring system is capable of separating the discharges from the test object and the coupling capacitor and measuring them separately; 2) The high-voltage supply shall have sufficiently low level of background noise to allow the specified Partial discharge magnitude to be measured at the specified test voltage 3) Impedance or a filter may be introduced at high voltage to reduce background noise from the power supply. 4) Shield room provided for better PD observed Fig.2.1 The PD test object Ct within a PD test circuit According to IEC Standard 60270 apparent charge q of a PD pulse is that unipolar charge which, if injected Within a very short time between the terminals of the test object in a specified test circuit, would give the same reading on the measuring instrument as the PD current pulse itself. The apparent charge is usually expressed in picocoulombs. The apparent charge is not equal to the amount of charge locally involved at the site of the discharge and which cannot be measured directly. 5) The surface of the external insulation of test objects shall be clean and dry because moisture or contamination on insulating surfaces can cause partial discharges; 6) The test object should be at ambient temperature during the test 7) Mechanical, thermal and electrical stressing just before the test can affect the result of partial discharge tests. To ensure good reproducibility, a rest interval after previous stressing may be necessary before making partial discharge tests. The main difference between these two types of PD detection circuits is related to the way the measuring 3

system is inserted into the circuit. In Fig.3.1, the CD is at ground potential and in series to the coupling capacitor Ck as it is usually done in praxis. In Fig.3.2, CD is in series with the test object Ca. Here the stray capacitances of all elements of the highvoltage side to ground potential will increase the value of Ck providing a somewhat higher sensitivity for this circuit according to theoretical calculations. The disadvantage is the possibility of damage to the PD measuring system, if the test object fails. The new IEC Standard defines and quantifies the measuring system characteristics. The most essential ones will again be cited and further explained below: Ca test object Ck coupling capacitor CD coupling device MI measuring instrument Z filter The transfer impedance Zf is the ratio of the output voltage amplitude to constant input current amplitude, as a function of frequency f, when the input is sinusoidal. This definition is due to the fact that any kind of output signal of a measuring instrument (MI) as used for monitoring PD signals is controlled by a voltage, whereas the input at the CD is a current. The lower and upper limit frequencies f1 and f2 are the frequencies at which the transfer impedance Z(f) has fallen by 6 db from the peak passband value. Fig.3.1 coupling device CD in series with the coupling capacitor Midband frequency fm and bandwidth Δf: for all kinds of measuring systems, the midband frequency is defined by: fm= f1+f2 2 And the bandwidth by: Δf= f2-f1 Fig.3.2 coupling device CD in series with the test object U~ high-voltage supply Zmi input impedance of measuring system CC connecting cable OL optical link 3.1 Wide-band PD instruments Up to 1999, no specifications or recommendations concerning permitted response parameters have been available. Now, the following parameters are recommended. In combination with the CD, wideband PD measuring systems, which are characterized by a transfer impedance Zf having fixed values of the lower and upper limit frequencies f1 and f2, and adequate attenuation below f1 and above f2, shall be designed to have the following values for f1, f2 and Δf 4

30 khz f1 100 khz; f2 500 khz; 100 khz Δf 400 khz. The response of these instruments to a (nonoscillating) PD current pulse is in general a welldamped oscillation. The apparent charge q and with some reservation the polarity of the PD current pulse can be determined from this response. The pulse resolution time Tr is small and is typically 5 to 20µs other high-voltage conductors, connected with the screen only for testing purposes. Disturbances may also be caused by higher harmonics of the test voltage within or close to the bandwidth of the measuring system. Such higher harmonics are often present in the low-voltage supply due to the presence of solid state switching devices (thyristors, etc.) and are transferred, together with the noise of sparking contacts, through the test transformer or through other connections, to the test and measuring circuit. 4. Sources and reduction of disturbances Within the informative Annex G of the IEC Standard 1. Quantitative measurements of PD magnitudes are often obscured by interference caused by Disturbances which fall into two categories: (i)disturbances which occur even if the test circuit is not energized. They may be caused, for example, by switching operations in other circuits, commutating machines, high-voltage tests in the vicinity, radio transmissions, etc., including inherent noise of the measuring instrument itself. They may also occur when the high-voltage supply is connected but at zero voltage. (ii)disturbances which only occur when the test circuit is energized but which do not occur in the test object. These disturbances usually increase with increasing voltage. They may include, for example, partial discharges in the testing transformer, on the high-voltage conductors, or in bushings (if not part of the test object). Disturbances may also be caused by sparking of imperfectly earthed objects in the vicinity or by imperfect connections in the area of the high voltage, e.g. by spark discharges between screens and 2. Some of these sources of disturbances have already been mentioned in the preceding sections and it is obvious that up to now numerous methods to reduce disturbances have been and still are a topic for research and development, which can only be mentioned and summarized here. (i)the most efficient method to reduce disturbances is screening and filtering, in general only possible for tests within a shielded laboratory where all electrical connections running into the room are equipped with filters. (ii)straight PD-detection circuits are very sensitive to disturbances: any discharge within the entire circuit, including H.V. source, which is not generated in the test specimen itself, will be detected by the coupling device CD. Therefore, such external disturbances are not rejected. Independent of screening and filtering mentioned above, the testing transformer itself should be PD free as far as possible, as H.V. filters or inductors are expensive. It is also difficult to avoid any partial discharges at the H.V. leads of the test circuit, if the test voltages are very high. A basic improvement of the straight detection circuit may 5

therefore become necessary by applying a balanced circuit, which is similar to a Schering bridge. (iii)another extensively used method is the time window method to suppress interference pulses. All kinds of instruments may be equipped with an electronic gate which can be opened and closed at preselected moments, thus either passing the input signal or blocking it. If the disturbances occur during regular intervals the gate can be closed during these intervals. In tests with alternating voltage, the real discharge signals often occur only at regularly repeated intervals during the cycles of test voltage. The time window can be phase locked to open the gate only at these intervals. 5. Calibration of PD detectors in a complete test circuit A calibration of measuring systems intended for the measurement of the fundamental quantity q is made by injecting short duration repetitive current pulses of well-known charge magnitudes q0 across the test object, whatever test circuit is used. These current pulses are generally derived from a calibrator which comprises a generator producing step voltage pulses (see G ) of amplitude V0 in series with a precision capacitor C0. If the voltages V0 also remain stable and are exactly known, repetitive calibration pulses with charge magnitudes of q0=v0c0 are injected. A short rise time of 60 ns is now specified for the voltage generator to produce current pulses with amplitude frequency spectra which fit the requirements set by the bandwidth of the instruments and to avoid integration errors if possible. Fig.5.1 The usual circuit for the calibration of a PD measuring Instrument MI within the complete test circuit Whereas further details for the calibration procedures shall not be discussed here, the new philosophy in reducing measuring errors during PD tests will be presented._ It has been known for some time that measuring uncertainties in PD measurements are large. Even today, PD tests on identical test objects performed with different types of commercially available systems will provide different results even after routine calibration performed with the same calibrator. The main reasons for this uncertainty are the different transfer impedances (bandwidth) of the measuring systems, which up to 1999 have never been well defined and quantified. The new but not very stringent requirements_31_ related to this property will improve the situation; together with other difficulties related to disturbance levels measuring uncertainties of more than about 10 per cent may, however, exist. The most essential part of the new philosophy concerns the calibrators, for which up to now no requirements for their performance exist. Tests on daily used commercial calibrators sometimes display deviations of more than 10 per cent of their nominal values. Therefore routine type, and performance tests on calibrators have been introduced with the new standard. At least the first of otherwise periodic performance tests should be traceable to national 6

standards, this means they shall be performed by an accredited calibration laboratory. With the introduction of this requirement it can be assumed that the uncertainty of the calibrator charge magnitudes q0 can be assessed to remain within š5 per cent or 1 pc, whichever is greater, from its nominal values. Very recently executed intercomparison tests on calibrators performed by accredited calibration laboratories showed that impulse charges can be measured with an uncertainty of about 3 per cent. appropriate test procedure should be specified by the relevant technical committee. Under no circumstances, however, shall the voltage applied exceed the rated short-duration power frequency withstand voltage applicable to the apparatus under test. NOTE 2 In the case of high-voltage apparatus, there is some danger of damage from repeated voltage applications approaching the rated short-duration power frequency withstand voltage. 6. Determination of the partial discharge inception and extinction voltages 6.1 Determination of the partial discharge magnitude at a specified test voltage A voltage well below the expected inception voltage shall be applied to the test object and gradually increased until discharges attain, or exceed, a specified low magnitude. The test voltage at this specified magnitude is the partial discharge inception voltage Ui. The voltage is then increased to a specified voltage level and thereafter gradually reduced to a value at which the discharges become less than the same specified magnitude. The test voltage at this discharge limit is the partial discharge extinction voltage Ue. Note that the value of Ui can be affected by the r ate of rise of voltage, and Ue can be affected by the amplitude and time of voltage application and also by the rate of decrease of voltage. NOTE 1 In some types of insulation, partial discharges occur only intermittently when the voltage is first raised to U, in others the discharge magnitude rises rapidly, whereas in others discharges extinguish when Ui is maintained for some time. Thus, the 6.1.1 Measurement without pre-stressing The partial discharge magnitude in terms of the specified quantity is measured at a specified voltage, which can be well above the expected partial discharge inception voltage. The voltage is gradually increased from a low value to the specified value and maintained there for the specified time. As the magnitudes can change with time, the specified quantity shall be measured at the end of this time. The magnitude of the partial discharges may also be measured and recorded while the voltage is being increased or reduced or throughout the entire test period. 6.1.2 Measurement with pre-stressing The test is made by raising the test voltage from a value below the specified partial discharge test voltage up to a specified voltage exceeding this voltage. The voltage is then maintained for the specified time and, thereafter, gradually reduced to the specified partial discharge test voltage. At this 7

voltage level, the voltage is maintained for a specified time and, at the end of this time, the specified PD quantity is measured in a given time interval or throughout the specified time. 7. Measuring uncertainty and sensitivity The magnitude, duration and pulse repetition rate of PD pulses can be greatly affected by the time of voltage application. Also, the measurement of different quantities related to PD pulses usually presents larger uncertainties than other measurements during high-voltage tests. Consequently, it can be difficult to confirm PD test data by repeating tests. This should be taken into consideration when specifying partial discharge acceptance tests. The measurement of apparent charge q using a measuring system in accordance with the provisions of this standard and calibrated in accordance with the provisions of clauses is considered to have a measuring uncertainty of 110 % or +pic, whichever is the greater. The measurements are also affected by disturbances (clause 1 O) or background noise, which should be low enough to permit a sufficiently sensitive and accurate measurement of the specified partial discharge magnitude. The minimum magnitude of PD quantities which can be measured in a particular test is in general limited by disturbances. Though these can effectively be eliminated by suitable techniques as described in annex G, additional limits are determined by the internal noise levels of the measuring instruments and systems, by the physical dimensions and layout of the test circuit and the values of the test circuit parameters. Another limit for the measurement of a minimum PD quantity is set by the capacitance ratio c,/ck and optimal values for the input impedance of the coupling device and its matching to the measuring instruments used. Highest sensitivity would be realized if Ck >> Ca, a condition which is generally inconvenient to satisfy due to the additional loading of the high-voltage supply. Thus, the nominal value of Ck is limited for actual tests, but acceptable sensitivity is usually achieved with Ck about 1 nf or higher. 8. Electrical Test- Partial Discharge Measurement Extinguishing voltage of the partial discharges Uext (1.1xUr)/ (3) The test shall be performed with equipment whose sensibility is 10 pc.as acceptance criteria we will use for calculation the highest standardized service voltage (Us) under the rated, meaning: Uext (1.1xUs)/ (3) For Ur=25kV For Ur=24kV Us=22kV Us=20kV Uext (1.1x22kV)/ (3) Uext (1.1x20kV)/ (3) 14kV 12,7kV Criteria for categories selection of fuse holder 24 kv Extinguishing discharges level from Reject 0,0 kv to 12,7 kv Extinguishing discharges level from APPROVED 24 kv 12,7 kv to 13,9 kv Extinguishing APPROVED 25 kv discharges level from 8

14,0 kv and above For Ur=36kV Us=33kV Uext (1.1x33kV)/ (3) 21kV Extinguishing discharges level from 0,0 kv to 20,9 kv Extinguishing discharges level from 21kV and above Reject APPROVED 36 kv All the pieces that are not included in the mentioned conditions shall be rejected and issued a Nonconformity report. The potential recovery of the rejected pieces could only be performed after the analysis of the Non-conformity Report. Note: If the relative humidity of the atmosphere is 70%, the rejected pieces shall be conserved to a new test when the relative humidity is under normal conditions 70% Hr 50%. 9. Test sample 10. Results 9

system, Partial discharge is very important as electrical aspects 13. Acknowledgement 11. Application 1. Application ranges from Power Generation (Wind, Photovoltaic, among others) to Energy 2. Distribution for various industries and applications. 3. Its typical applications are: 4. Transformer substations; 5. Sectioning substations; 6. Public and private distribution substations. 12. Conclusion 1) To protect the system in crucial condition 2) To withstand the High voltage stress 3) So to avoid the economical losses and better life cycle of component or product in transmission I take this opportunity to express my profound gratitude and deep regards to my guide Prof.M.M.Hapse for his exemplary guidance, monitoring and constant encouragement throughout the course of this thesis. The blessing, help and guidance given by him time to time shall carry me a long way in the journey of life on which I am about to embark. I also take this opportunity to express a deep sense of gratitude to EFACEC India, to give valuable information and guidance, which helped me in completing this task through various stages. I am obliged to staff members of Efacec India, for the valuable information provided by them in their respective fields. I am grateful for their cooperation during the period of my assignment. Lastly, I thank almighty, my parents, brother, sisters and friends for their constant encouragement without which this assignment would not be possible. 14. References 1) High voltage test technique- Partial discharge measurement IEC 60270, 2000-12 2) British standards High voltage test technique- Partial discharge measurement BS EN 60270:2001 3)High Voltage Engineering by E. Kuffel second Edition 2000, Page No.421-459, ISBN 0 7506 3634 3 4) IEC 137-1984 Third edition, Bushing for alternative voltages above 1000V. 5) Partial Discharge Theory and Applications to Electrical Systems by Gabe Paoletti, Alex Golubev 10