PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

Similar documents
MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

AT Current Instrument Transformer Instructions for installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. TPE 6x.xx Indoor supporting current transformers

MEDIUM VOLTAGE PRODUCT. TJP 5.x Indoor voltage transformers

MEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers

MEDIUM VOLTAGE PRODUCT. TJP 7.x Indoor voltage transformers

Products for High Voltage Application. AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers

MEDIUM VOLTAGE PRODUCTS. KEVA C Indoor voltage sensors for Cellpack separable connectors

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

Current and Voltage (potential) Instrument transformers Instruction for installation, use and maintenance

Medium Voltage Products. KECA 80 C85 Indoor current sensor

MEDIUM VOLTAGE PRODUCTS. KEVA C Indoor voltage sensors

Instrument transformers for indoor applications. Product overview. Instrument transformers for indoor applications.

KEVCY 24 RE1; KEVCY 24 RF1 Indoor combined sensor; Indoor voltage sensor

KEVA B Indoor voltage sensor

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Three-phase monitoring relay CM-PFS

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Three-phase monitoring relay

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Three-phase monitoring relay CM-PVE

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Liquid level monitoring relay CM-ENS.2x

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Three-phase monitoring relay CM-PBE

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Three-phase monitoring relays CM-PFE and CM-PFE.2

Electronic timer CT-SDS.22

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Power supply CP-D 12/2.1

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Power supply CP-T 48/20.0 Primary switch mode power supply

Three-phase monitoring relays CM-PVS.81

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL

Power supply CP-T 48/5.0 Primary switch mode power supply

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

Power supply CP-T 24/20.0 Primary switch mode power supply

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Subject to changes 11/2003 Page 1/7

W DATA SHEET Current Transformer 40 x 10, A

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Power supply CP-T 24/10.0 Primary switch mode power supply

Power supply CP-T 24/40.0 Primary switch mode power supply

Electronic timer CT-MVS.12 Multifunctional with 1 c/o (SPDT) contact

Modem 1200 baud 500FSD10 EDS500 series - FSK modems

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Electronic timer CT-MXS.22 Multifunctional with 2 c/o (SPDT) contacts

Reactor and inductor are names used interchangeably for this circuit device.

Powered by technology...driven by service CURRENT TRANSFORMERS. Multifunction Meters. Transducers & Isolators. Temperature Controllers

Insulation monitoring relay CM-IWS.2 For unearthed AC systems up to U n = 400 V AC

SensyTemp TSBA (BA R) Resistance thermometer for building automation, machine construction and environmental engineering

Transformers connected via a cable Overvoltage protection

Power transformers. Shunt reactors Proven history for future success

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

Distribution transformers Part 2 Ground mounted transformers not closecoupled

Multimeter 500CVD21 RTU500 series

Electronic timer CT-AHE OFF-delayed with 1 c/o (SPDT) contact

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

VI 3 - i TABLE OF CONTENTS

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

Series P. Applications

USER MANUAL. Maxwell Technologies Ultracapacitor Energy Storage Modules. Models: BMOD0058 E016 B02 BMOD0006 E160 B02. Document

Switching power supplies CP range, Linear power supplies CP-L range. Content

Selection of MO surge arresters Overvoltage protection

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

P2 H2 NAMEPLATE 6 HOLES M8-10 M SCREW S1 1S2 1S3 X1 X2 X3 PARALLEL HIGH RATIO

Your safety first! This is the reason why our manual begins with the following guidelines:

REF42plus HMI Cutting Tool Operating Guide

Capacitive level meters CLM 40 INSTRUCTIONS MANUAL. průmyslová elektronika

Electronic timer CT-AWE Impulse-OFF with auxiliary voltage, 1 c/o (SPDT) contact

USER MANUAL. Maxwell Technologies BOOSTCAP Ultracapacitor Energy Storage Modules for Low Duty Cycle Applications

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Voltage Transformers type UMZ User s Manual, Operation and Maintenance

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Modem 9600 baud 500FSD11 EDS500 series - FSK modems

RTU560. Multimeter 560CVD03. Power Measuring Display. Characteristics. Application. Data Sheet Multimeter 560CVD03

TR 104, TR 104-Ex Rail mounted Temperature Transmitters

I Pr I P I OUT R L. Applications. Standards

Transcription:

PRODUCT FOR HIGH VOLTAGE APPLICATION Current transformers for Gasinsulated switchgear type ELK Instructions for installation, use and maintenance

2 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE ELK Scope of Contents 3 1. Service conditions 3 2. Technical details 4 3. Instruction for installation 4 General information 4 Safety instructions 5 Connection of transformer primary side 5 Connection of transformer secondary side 6 Mounting 7 4. Instructions for use 7 Routine test report 7 5. Maintenance instructions before installation 7 6. Transport & Storage 8 7. Disposal 8 8. Handling 9 9. Normative references 9 10. Dimensions 9 11. Lifetime 10 Appendix 1. Examples of electrical wiring 11 Appendix 2. Dimensional drawings

3 Instruction for installation, use and maintenance These installation, use and maintenance instructions apply for current instrument transformers intended for indoor or outdoor operation. The instructions refer to: Current instrument transformers for indoor or outdoor use, of the following types: ELK CN3 1080, ELK CN3 720, ELK CN14 840, ELK CN14 560, CN14C 01 Example of current transformer rating plate 1. Service conditions Indoor and outdoor transformers The transformers ELK CN3, ELK CN14 and CN14C without a primary conductor are designed for installation in gas-insulated switchgear for indoor and outdoor applications. The transformers are designed for standard ambient temperatures between -25 C and +40 C and altitudes below 1000 m above sea level. Different ambient temperatures can also be agreed upon with the customer. The transformers are designed for protection class IP54. 01 2. Technical details Technical details and specifications of each of the transformers are shown on a rating plate fixed to the terminal box. It is not allowed to operate the transformer at values exceeding the nameplate data. Dimensional drawings of transformers ELK CN3, ELK CN14 and CN14C are shown in Appendix 2. Where: 1) CN14C type code of transformer (ELK CN3-720 / ELK CN3-1080 / ELK CN14-560 / ELK CN14-840 / CN14C ) 2) 2016 year of manufacture 3) 1VLT... serial number 4) 50 / 60 Hz rated frequency 5) IEC 61869-1/-2 corresponding standard (standards) 6) 245/460/1050kV voltage level 7) 50kA/ 3s rated short-time thermal current / duration 8) or.n.: order number 9) Icth = 3150A rated continuos thermal current 10) Idyn = 135kA rated dynamic current 11) 3150//1/1/1/1A rated transformer ratio 12) 1S1-1S2, 2S1-2S2 parameters of all cores 13) additional specifications if required 14) weight, material number, insulation class

4 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE ELK 02 Example of current transformer connection schema nameplate 03 Example of a secondary terminal board of the ELK CN type transformers Connection of transformer primary side The ELK CN transformers don t have their own primary conductor. If ELK CN transformers will be used in other applications than ABB switchgear ELK-3, ELK-14 or ELK-14/245C please contact us for support. Attention: a primary conductor must be centred in the application with tolerance ±1cm. 02 The connection schema nameplate is placed under the cover of the terminal box. 3. Instruction for installation General information The instrument transformer is electrical equipment and the electrical installation of the instrument transformer can be done by skilled personnel, only. The level of experience, age and eligibility criteria for persons working with, on or near electric installations is governed by national legislation. If no such eligibility legislation is available the corresponding requirements can be found in the EN 50110-1 standard. Connection of transformer secondary side For all current transformers, the secondary cable connections must be led to a terminal box. The transformers ELK CN contain an outlet cable which is connected to the terminal on the DIN rail. If not specified otherwise in the order, the cable cross-section may not exceed 6mm2.The terminals are equipped with M4 screws for connection of the secondary outlets. Maximum allowed torques for secondary screw connections: Highest and lowest allowed torque values for secondary screw connections Screw Highest torque (Nm) Lowest torque (Nm) M4 1.8 1.5 The end of the windings of all cores are correspondingly identified. Terminal arrangement according to the number of terminals and parameters of transformer. The type of terminals and terminal arrangement may be changed by the customer after agreement with the manufacturer. Safety instructions 1. Always consider the transformer as a part of electric circuit which it is connected to. Don t touch incoming connectors and terminals, or any other parts of the transformer, unless you know for sure these are earthed. 2. Always ground the metallic base of the instrument transformer. 3. Always connect one terminal of each secondary winding of the transformer to the earth. When the secondary of the transformer is interconnected, there should be only one grounded point to prevent accidental paralleling with the system grounding wire. 4. Always short-circuit the secondary of a current transformer that is not currently in use, to prevent secondary voltages, which may be hazardous to personnel or damaging to the transformer s secondary. The secondary, like this, must be additionally grounded. 03

5 04 Mounting of terminal box 05 Example of transformer ELK CN3 1080 mm with six terminal boxes Mounting The transformers ELK CN are designed as low-voltage current transformers 0.72/3kV, without a built in primary conductor. For use in higher voltages it is therefore necessary to combine them with the primary conductor with self-isolation. A primary conductor is not included in the supply. 04 After connection of the terminal, the terminal box is closed by a cover and bushing plate with corresponding sealing compound against penetration of splash water. The number of terminal boxes may be changed after agreement between the customer and manufacturer and according to the type of transformer. Max. number of terminal boxes is shown in the table below. Mounting and placement of the ELK CN transformers is proposed by the customer depending on application and using of the primary conductor and its insulation. The transformer has a flange with holes used to attach the transformer screws. Before installation of the primary conductor and whole transformer, clean the sealing surface and inside surface of the transformer from dust, grease and another impurities, see 5. Maintenance instructions. For each type of ELK CN transformer use the corresponding fasteners, primary conductor and insulator. Use only a primary conductor designed by ABB. Type Max.Number of terminal boxes Position ELK CN3-1080mm 6 1, 2, 3, 4,5,6 ELK CN3-720mm 2 1, 2 ELK CN14-840mm 4 1, 2, 3, 4 ELK CN14-560mm 2 1, 2 CN14C 1 1 4. Instructions for use Current instrument transformers are used: to convert currents in the primary circuit to an appropriate level for secondary circuit equipment (relays and meters) to insulate the primary and secondary circuit from each other to protect the secondary equipment from the harmful effects of current appearing during the operation (short circuits) The use of a current transformer for a purpose other than described above is forbidden if not agreed with the producer. Routine test report The routine test report of a current instrument transformer includes: a) verification of terminal markings b) inter-turn overvoltage test c) determination of errors d) power-frequency test 05 Upon the customer s request the following information can be provided free of charge: theoretical current/voltage error and phase displacement values theoretical excitation (magnetization) curves

6 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE ELK 06 Transformer surface 07 Example of sticker Additional reports for supplementary charge, made available on request: test report on accuracy excitation (magnetization) curves additional nameplates (if more than 1 is required) verification tests for measuring cores (classes 0.2; 0.2 S; 0.5; 0.5 S) 7. Disposal Materials used in instrument transformers are considered as materials without environmental impact and the materials are not toxic. Instrument transformers have to be disposed of in accordance with national legislation relevant to domestic waste disposal. 5. Maintenance instructions before installation Excessive dust sediments or any other type of contamination are to be removed from the transformer using a soft brush and alcohol, in such a way as not to damage the coating and sealing surface. Protect the sealing surface from both sides of ELK CN during manipulation with a transformer. The spray painted surface inside CT must be smooth without sharp edges and coarse defects. 8. Handling The transformers ELK CN are too heavy and is necessary to use hanging belts attached on holes for screws on three places or to use one or more hanging belts attached around the flange of the transformer. For handling use belts and a crane with sufficient load capacity. Always make sure that the belts are secured safely on the crane and on the transformer. Spray painted surface ATTENTION: During the manipulation with the transformer it is necessary to follow safety work instructions. Never stay under the freight. Always make sure that the freight is safely locked on the crane and make sure that there is no risk of unexpected release or turnover of the freight. Follow the Label Instructions: Sealing surface 06 6. Transport & Storage The permitted temperature for transport and storage ranges from -55 C to +80 C. During transport and storage the transformers have to be protected from direct impact of solar radiation. The transformers are delivered according to delivery instruction HASV600377. 07

7 9. Normative reference IEC 60044-1 IEC 61869-1/-2 IEC 60529 ISO 12100 EN 50110-1 Current instrument transformers Instrument transformers Degrees of protection provided by enclosures Machine safety basic concepts, general principles of design Operation of electrical installations Current instrument transformers are designed, tested and manufactured in accordance with international or national standards, the customer s requirements, based on an agreement between the customer and the manufacturer. The specific standard is always mentioned on the transformer ratio nameplate. As an example the following standards can be mentioned: IEC 60044-1; IEC 60044-6; IEC 61869-1; IEC 61869-2; AS 60044-1; ČSN EN 60044-1; ČSN EN 60044-6 IEEE Std C57.13.6-2005; ANSI C57.13-1978; CSA Std CAN3-C13-M83 BS EN 60044-1; GOST 7746-2001 When agreed, transformers made in accordance with other standards can also be supplied, or in accordance with other release version of the above standards. 10. Dimensions Dimensions of the current transformers acc. appendix 2. 11. Lifetime The product s lifetime is more than 40 years.

8 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE ELK Appendix 1. Examples of electrical wiring Current instrument transformers:

9 Appendix 2. Dimensional drawings Weight of the transformer depends on the number of cores and their parameters. ELK CN3 1080 ELK CN3 720

10 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE ELK ELK CN 14 840 ELK CN14 560

11 CN14C Configuration A0001 CN14C Configuration A0002

CONTACT US ABB s.r.o. EPMV Brno Videnska 117, 619 00 Brno, Czech Republic Tel.: +420 547 152 021 +420 547 152 614 Fax: +420 547 152 626 E-mail: info.ejf@cz.abb.com www.abb.com NOTE We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without prior written consent of ABB. Copyright 2017 ABB All rights reserved 1VLM000628 Rev.3, en 2017.08.28