Optimal Voltage Control using Singular Value Decomposition of Fast Decoupled Load Flow Jacobian

Similar documents
A Novel Approach for Reducing Proximity to Voltage Instability of Multibus Power System with Line Outage Using Shunt Compensation and Modal Analysis

Enhancement of Power System Voltage Stability Using SVC and TCSC

Optimal Placement of Unified Power Flow Controller for Minimization of Power Transmission Line Losses

Use of PQV Surface as a Tool for Comparing the Effects of FACTS Devices on Static Voltage Stability Ali Zare, Ahad Kazemi

Identification of weak buses using Voltage Stability Indicator and its voltage profile improvement by using DSTATCOM in radial distribution systems

Optimal Allocation of TCSC Devices Using Genetic Algorithms

Voltage Stability Analysis with Equal Load and Proportional Load Increment in a Multibus Power System

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS

Power Quality enhancement of a distribution line with DSTATCOM

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Transient Stability Improvement of Multi Machine Power Systems using Matrix Converter Based UPFC with ANN

Voltage Stability Assessment in Power Network Using Artificial Neural Network

ECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

factors that can be affecting the performance of a electrical power transmission system. Main problems which cause instability to a power system is vo

Analysis and Enhancement of Voltage Stability using Shunt Controlled FACTs Controller

ELEMENTS OF FACTS CONTROLLERS

PV CURVE APPROACH FOR VOLTAGE STABILITY ANALYSIS

AN ADVANCED REACTIVE POWER MANAGEMENT SYSTEM FOR THE SEOUL METROPOLITAN POWER SYSTEM

Online Wide-Area Voltage Stability Monitoring and Control: RT-VSMAC Tool

Design of Improved Solar Energy Harvested Hybrid Active Power Filter for Harmonic Reduction, Power factor Correction and Current Compensation

STATCOM Control of Ill-Conditioned Power Systems Using Dogleg Trust-Region Algorithm

Harmony Search and Nonlinear Programming Based Hybrid Approach to Enhance Power System Performance with Wind Penetration

Voltage Control and Power System Stability Enhancement using UPFC

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

Particle Swarm Based Optimization of Power Losses in Network Using STATCOM

I. INTRODUCTION. Keywords:- FACTS, TCSC, TCPAR,UPFC,ORPD

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC

COMPARATIVE PERFORMANCE OF WIND ENERGY CONVERSION SYSTEM (WECS) WITH PI CONTROLLER USING HEURISTIC OPTIMIZATION ALGORITHMS

Minimization of Power Loss and Improvement of Voltage Profile in a Distribution System Using Harmony Search Algorithm

Transfer Capability Enhancement of Transmission Line using Static Synchronous Compensator (STATCOM)

A New Hybrid Approach to Thevenin Equivalent Estimation for Voltage Stability Monitoring

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

THD Reduction Using Series Transformer Connection In A STATCOM Within Mosul Ring System

State Estimation Advancements Enabled by Synchrophasor Technology

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

A REVIEW OF VOLTAGE/VAR CONTROL

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

Wind Power Plant Voltage Control Optimization with Embedded Application of Wind Turbines and Statcom

Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT

IT is generally more convenient and economical to connect

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

Transactions on Information and Communications Technologies vol 16, 1996 WIT Press, ISSN

Identifying Long Term Voltage Stability Caused by Distribution Systems vs Transmission Systems

Implementation of Line Stability Index for Contingency Analysis and Screening in Power Systems

Voltage-Current and Harmonic Characteristic Analysis of Different FC-TCR Based SVC

Voltage Improvement Using SHUNT FACTs Devices: STATCOM

Investigation of D-Statcom Operation in Electric Distribution System

ENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER

POWER SYSTEM II LAB MANUAL

IMPLEMENTATION OF NEURAL NETWORK IN ENERGY SAVING OF INDUCTION MOTOR DRIVES WITH INDIRECT VECTOR CONTROL

Classification of networks based on inherent structural characteristics

Fuzzy Approach to Critical Bus Ranking under Normal and Line Outage Contingencies

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM

An efficient power flow algorithm for distribution systems with polynomial load

FOUR TOTAL TRANSFER CAPABILITY. 4.1 Total transfer capability CHAPTER

Power flow improvement using Static Synchronous Series Compensator (SSSC)

A New VSC HVDC model with IEEE 5 bus system

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

PMU based Wide Area Voltage Control of Smart Grid: A Real Time Implementation Approach

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Optimal Placement of Shunt Connected Facts Device in a Series Compensated Long Transmission Line

A Direct Power Controlled and Series Compensated EHV Transmission Line

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

STUDY AND SIMULATION OF THE UNIFIED POWER FLOW CONTROLLER (UPFC) IN POWER SYSTEM

Genetic Algorithms as a Reactive Power Source Dispatching Aid for Voltage Security Enhancement

Keywords: Stability, Power transfer, Flexible a.c. transmission system (FACTS), Unified power flow controller (UPFC). IJSER

Comparative performance of wind energy conversion system (WECS) with PI controller using heuristic optimisation algorithms

Power Transfer Limit of Rural Distribution Feeder

Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM

Placement of Multiple Svc on Nigerian Grid System for Steady State Operational Enhancement

OPTIMAL PLACEMENT OF UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEMS USING PARTICLE SWARM OPTIMIZATION METHOD

Chhattisgarh Swami Vivekanand Technical University, Bhilai

Modeling and Simulation of STATCOM

SuperOPF and Global-OPF : Design, Development, and Applications

Voltage Level and Transient Stability Enhancement of a Power System Using STATCOM

Power System Stability Improvement in Multi-machine 14 Bus System Using STATCOM

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

AN ABSTRACT OF THE THESIS OF

Improvement in Power Quality of Distribution System Using STATCOM

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge

Multilevel Inverter Based Statcom For Power System Load Balancing System

Optimal Location of Series FACTS Device using Loss Sensitivity Indices. 3.2 Development of Loss Sensitivity Indices

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Direct Voltage Control in Distribution System using CMLI Based STATCOM

In Class Examples (ICE)

Keywords: unbalanced voltage, unbalanced current, Load balancing transformer

Voltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases

IOSR Journal of Electrical and Electronics Engineering (IOSRJEEE) ISSN: Volume 1, Issue 5 (July-Aug. 2012), PP

Study of Effectiveness of Under-excitation Limiter in Dynamic Modeling of Diesel Generators

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

Voltage Stability Calculations in Power Transmission Lines: Indications and Allocations (IEEE 30 BUS SYSTEM)

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Transcription:

Optimal Voltage Control using Singular Value Decomposition of Fast Decoupled Load Flow Jacobian Talha Iqbal, Ali Dehghan Banadaki, Ali Feliachi Lane Department of Computer Science and Electrical Engineering West Virginia University Morgantown, WV 26505-6109, USA Email - ti0001@mix.wvu.edu Abstract The problem of regulating voltages within the required limits is complicated by the fact that power system supplies power to a vast number of loads and is fed from many generating units. As loads vary, reactive power requirements of the transmission system vary. Moreover, voltage magnitude is relatively less sensitive to active power compared to reactive power due to high X/R ratio of transmission lines. Therefore, separating voltage control from active power is not only justified but also the common and practical way in power transmission systems. Considering these facts, the fast decoupled power flow jacobian can be used to control voltage magnitudes by reactive power compensation. In this paper, an optimal voltage control is presented to obtain new voltage set-points for PV buses by maximizing the effect of input change on output change using the Fast Decoupled Load Flow (FDLF) jacobian matrix. The proposed algorithm was tested on three IEEE systems: 9 bus, 14 bus and 30 bus systems. Keywords optimal voltage control; Singular Value Decomposition; Fast Decoupled Load Flow Jacobian; Eigenvalues; Eigenvectors I. INTRODUCTION Voltage and frequency control in power systems have always been considered as two fundamental regulation problems. Frequency regulation through active power control was considered and settled first but voltage control problem has no standard solution yet [1]. Voltage regulation through active power control is also theoretically possible but this method is never used in practice except under extreme operating conditions where there are high system security risks [2-4]. In modern power networks, voltage and frequency control with optimal operation of the network is a big challenge. Voltage regulation in power system is complicated by the fact that it supplies power to a large number of loads and has many generating units including renewable energy resources [5-9]. As loading conditions are changed, the reactive power requirements of the transmission system vary [10]. Moreover, in transmission systems, due to high X/R ratio of transmission lines, voltage magnitude is less sensitive to active power and relatively more sensitive to reactive power. Therefore, decoupling voltage control from active power is not only justified but also the common and practical way in power system operations [11]. Considering these facts, fast decoupled load flow assumptions can be used for voltage control. In transmission systems with X >> R, voltages can be controlled by the injection or absorption of reactive power. In general, five methods of injecting reactive power are available: static shunt capacitors, static series capacitors, synchronous compensators, static VAR compensators and STATCOMs [2]. Currently, the system voltage profile is kept within normal operating limits by putting a reactive power source at the bus, changing transformer tap ratio or controlling the generator terminal voltage [12]. Voltage control based on sensitivity analysis has been a hot research topic for the last few decades. A voltage control technique based on defining voltage control areas using the jacobian matrix is presented in [13]. But this method has a high degree of trial and error [14-15]. [16] discusses a method of controlling voltage based on the structure of the network. Voltage control areas are determined based on electrical distance between the buses. This method of finding electrical distance has been applied in [17] and [18]. In [19], voltage control areas are identified based on direct relationship between generator s reactive power and load, by finding a sensitivity matrix that relates the reactive power output of a generator to a load. In this paper, an optimal voltage control algorithm is proposed to obtain new voltage set-points for PV buses by maximizing the effect of change in input (i.e. ΔV PV) on output change (i.e. ΔV PQ) using the FDLF jacobian matrix, so that we can have maximum reactive reserve and minimum shift of the controls. The remainder of the paper is organized as follows: The proposed optimal voltage control approach is formulated in Section II. Section III describes all steps involved in the proposed voltage control algorithm through a control flow diagram. Section IV discusses implementation and simulation results of the proposed voltage control approach through case studies. Performance comparison with sensitivity based voltage control approach is presented in Section V. Conclusions and discussion on future work are discussed in Section VI. II. PROBLEM FORMULATION A. Eigenvalues and Eigenvectors Linear systems can be represented mathematically by linear matrix equations. Consider a linear system represented by a 2x2 matrix A. It takes x as input vector and transforms it linearly into y as output vector as shown in Fig. 1, where y = Ax. When A operates on x, it changes its magnitude as well as direction,

however there are some special vectors which, when applied on the system, do not change their direction but only magnitude is affected i.e. they are stretched or squeezed only. These special vectors are called eigenvectors (v λ) of the matrix A and the amount of stretch or squeeze is called its eigenvalue (λ). In other words, when we apply v λ (an eigenvector of A) to A, we get another vector whose direction is the same as v λ but its magnitude is scaled by some factor which is called eigenvalue i.e. eigenvectors are those vectors which do not knock off their span when operated by the linear system A [20-21]. Since an eigenvector of a matrix (e.g. A) only changes its magnitude when multiplied by the matrix, it indicates a direction in which A would have maximum effect on the input [22]. In other words, any change in input which lies in the span of the eigenvector v λm (corresponding to the highest eigenvalue, λ m, of A), would bring maximum change in the output i.e. if Δx = v λm, where is a scalar, then Δy is maximized. The same concept can be applied to singular vectors of the matrix A [23-24]. The singular value decomposition (SVD) of a matrix A is defined as in (1) = (1) Where columns of U are called left singular vectors of A (eigenvectors of AA T ) and rows of V T are called right singular vectors of A (eigenvectors of A T A). The eigenvalues of AA T are the singular values of A. B. Optimal Voltage Control Using fast decoupled load flow assumptions, the changes in network bus voltage magnitudes can be approximated by (2) = (2) PV is representing voltage controlled buses and PQ is representing load buses. S VQ is Q-V sensitivity matrix of the network and it can be decomposed as in (2a) where Fig. 1: Linear Transformation = (2) S 11 = sensitivity of ΔV PV on ΔQ PV S 12 = sensitivity of ΔV PV on ΔQ PQ S 21 = sensitivity of ΔV PQ on ΔQ PV S 22 = sensitivity of ΔV PQ on ΔQ PQ Equation (2a) can be solved to get (3) = + (3) Here = ( ), is considered as disturbance because we have no control over reactive power demand. Equation (3) gives us relation between load bus and source bus voltages. It can be used to control load bus voltages by adjusting voltages of PV buses. The objective of the controller is to find optimal input (ΔV PV) that would have maximum effect on the output (ΔV PQ). The objective function J can be described by (4) = (4) Where M is weight matrix to select the load bus we want to control or change more. Using (3), J can be approximated (neglecting D) as in (5) = ΔV ΔV (5) Where N=. Objective function J would be maximized if we select ΔV PV in the span of that left singular vector of N which corresponds to its highest singular value (i.e. ). Using singular value decomposition of N (i.e. N = U V T ), (5) can be modified as =ΔV U ΔV (6) If ΔV =u, where is the left singular vector corresponding to the highest singular value of N, then performance index J would be maximized and (6) would be modified as in (7) = (7) Scalar constant is the design parameter in this control problem which would give required change in voltage of the load bus being controlled. In this approach, we are controlling one load bus voltage (having least deviation from reference voltage i.e. 1 pu) at a time using output weight matrix M. We call this controlled bus (CB) in our algorithm. Using (4) and (7), we can get (8) = = = (8) Design parameter can be calculated using (8) = (9) III. PROPOSED OPTIMAL VOLTAGE CONTROL ALGORITHM In this paper, all buses whose voltages are outside normal voltage limits are called critical buses. The proposed optimal voltage control algorithm can be described by following steps: 1 Initialize ΔV PV = 0 (zero vector). Solve power flow and identify critical buses. If there are no critical buses, then return ΔV PV, required = ΔV PV and terminate the algorithm. 2 Select the critical bus as controlled bus which has least deviation from the reference voltage (i.e. 1 pu). 3 Compute which would make control bus voltage (V CB) equal to reference voltage (1 pu). 4 Find ΔV PV using (9) that would give required change in V CB (i.e. ΔV CB in (8)) = (9) 5 Update voltages of the voltage controlled buses (V PV, new) using (10) and return to step 1.

load buses). Bus voltages before and after control are given in Table I. Change in voltages after applying voltage control algorithm are shown in Fig. 4. It is evident from the figure that sensitivity is inherent in this voltage control approach. Bus 9 is most sensitive to generator 1, and hence maximum change in bus 1 voltage, while least sensitive to generator 3 and hence minimum change in bus 3 voltage. B. IEEE 14 Bus System This system has five (bus 1-3, 6, 8) voltage controlled buses (including slack bus) and nine (bus 4, 5, 7, 9-14) load buses. Active power demand is 259 MW and reactive power demand is 73.5 MVAR. All voltages are within limits under normal conditions. The system diagram is shown in Fig. 5. We applied a disturbance (-46.4 MVAR) on bus 10 and its voltage increased from 1.051 pu to 1.112 pu. After applying proposed voltage control algorithm, it came back within normal range in two iterations. In first iteration, bus 10 was controlled to bring it back to reference voltage (1 pu) but it pushed bus 12 below 0.9 pu Fig. 2: Optimal Voltage Control Algorithm Flowchart V, =V, +ΔV (10) Note: Instead of running power flow in each iteration, we can also use (11) to approximate ΔV PQ, new and identify critical buses.,, (11) The control flow diagram of the proposed voltage control algorithm is shown in Fig. 2. IV. CASE STUDIES The proposed optimal voltage control algorithm was tested on three IEEE test systems, namely a 9 bus, a 14 bus and a 30 bus system respectively [25]. In every case, we randomly added some disturbances (inductive or capacitive) into the original system to make one or more bus voltages go out of limits and then applied this control algorithm to bring them back within normal limits. All simulations results were obtained using MATLAB and MATPOWER 6.0 [26]. A. IEEE 9 Bus System This system has three (bus 1-3) voltage controlled buses (including slack bus) and six (bus 4-9) load buses. The active power demand is 315 MW while reactive power demand is 115 MVAR. All voltages are within limits (0.9 to 1.1 pu) under normal operating conditions. The system diagram is shown in Fig. 3. We added a disturbance on bus 9 (70 MVAR) and its voltage came down to 0.8853 pu. After applying voltage control algorithm, its voltage was brought back to 0.9934 pu in one iteration (because there were no other voltage violations on 1.1 1 0.9 0.15 0.1 0.05 0 Fig. 3: IEEE 9 bus System TABLE I. Bus Voltages before and after Control (IEEE 9bus) Bus Before After 1 1.000 1.100 2 1.000 1.086 3 1.000 1.040 4 0.960 1.060 5 0.954 1.045 6 0.995 1.057 7 0.971 1.051 8 0.978 1.066 9 0.885 0.993 before after Bus Voltages before and after Control 1 2 3 4 5 6 7 8 9 Change in Bus Voltages after Control control bus 1 2 3 4 5 6 7 8 9 Bus # Fig. 4: Bus Voltages before and after Control (IEEE 9bus)

(i.e. 0.899 pu). In second iteration, bus 12 was controlled and all buses remain within normal limits. Bus voltages before and after control for both iterations as well as change in voltages after applying voltage control algorithm has been shown in Fig. 6. We might face a situation in which we have two (or more) conflicting buses (i.e. one bus needs to decrease the PV bus voltage while the other wants to increase the same PV bus voltage) as critical buses. In this situation, the number of iterations would increase because we are controlling one bus at a time, but eventually system would come within normal voltage limits if there exist a solution. This problem can be solved by controlling multiple buses simultaneously. One such situation was studied by adding multiple disturbances into the system (bus 7 and 14). A conflict was observed between bus 7 and bus 14 because bus 7 was violating upper limit while bus 14 was violating lower limit. The solution was obtained after five iterations. Bus voltages after each iteration are given in Table II while voltages for both buses in each iteration are shown in Fig. 7 along with the change TABLE II. Bus Voltages before and after Control (IEEE 14bus) Bus Before Iter. 1 Iter. 2 Iter. 3 Iter. 4 Iter. 5 1 1.000 1.013 0.989 1.004 0.987 1.000 2 1.000 1.041 0.964 1.013 0.959 1.001 3 1.000 1.025 0.978 1.008 0.975 1.001 4 0.984 1.033 0.953 1.009 0.955 1.001 5 0.976 1.026 0.950 1.005 0.953 0.998 6 1.000 1.100 0.998 1.1 1.028 1.100 7 1.074 1.145 1.022 1.102 1.028 1.094 8 1.000 1.084 0.900 1 0.900 0.988 9 1.004 1.086 0.963 1.054 0.976 1.047 10 0.996 1.082 0.961 1.054 0.977 1.049 11 0.994 1.087 0.976 1.073 0.999 1.071 12 0.967 1.070 0.962 1.067 0.992 1.066 13 0.948 1.051 0.939 1.046 0.968 1.044 14 0.828 0.937 0.794 0.912 0.819 0.908 Fig. 7: Bus 7 and Bus 14 Voltages in each iteration (IEEE 14bus) Voltage (1 pu) Voltage (1 pu) 1.1 1.05 1 0.95 before iteration 1 iteration 2 Fig. 5: IEEE 14 bus System Bus Voltages before and after Control 0.9 0 5 10 15 Change in Bus Voltages after Control 0-0.05 control bus iter. 1 control bus iter. 2-0.1 0 5 10 15 Bus # Fig. 6: Bus Voltages before and after Control (IEEE 14bus) in voltages after applying control algorithm (first iteration is representing voltages before control in the figure). C. IEEE 30 Bus System This system has 6 voltage controlled buses (bus 1, 2, 13, 22, 23, 27) and 24 load buses. Active power demand is 189.2 MW and reactive power demand is 107.2 MVAR. All voltages are within normal limits under normal operating conditions. The system diagram is shown in Fig. 8. We added disturbances on bus 8 (90 MVAR) and bus 25 (-100 MVAR) which resulted in voltage violations on bus 8 (.878 pu) and bus 25 (1.116 pu). After applying voltage control algorithm, all voltages came back within normal limits in two iterations. Bus voltages for each iteration are given in Table III. While voltages in each iteration as well as change in voltages after applying voltage control algorithm are shown in Fig. 9. V. PERFORMANCE COMPARISON We compared our optimal voltage control approach (OVC) with sensitivity based voltage control approach (SVC) which uses sensitivities of PQ bus voltages on PV bus voltages (changing PV bus voltage to which control bus is most sensitive). The performance index described in (4) that it is being maximized was computed for comparison. The performance

TABLE IV. Comparison of Performance Indices for OVC and SVC Case Study OVC SVC IEEE 9 bus 0.0117 0.0042 IEEE 14 bus 0.0119 0.0068 IEEE 30 bus 0.0052 0.0038 Fig. 10: Comparison of OVC and SVC Fig. 8: IEEE 30 bus System Fig. 9: Bus voltages in each iteration (IEEE 30bus) index (for one iteration) for both cases are given in Table IV and shown in Fig. 10. It is evident from the results that the proposed optimal voltage control (OVC) approach is giving better performance index in all cases and hence better approach compared to sensitivity based voltage control (SVC). VI. CONCLUSION AND FUTURE WORK In this paper, an optimal voltage control was proposed using the Fast Decoupled Load Flow (FDLF) jacobian matrix. The proposed algorithm was tested on different standard IEEE systems and satisfactory results were obtained. In case of no conflict, the maximum number of iterations in which the algorithm converges is either equal to or less than the total number of critical buses at first iteration. The drawback of this approach is that it controls only one bus at a time resulting in more number of iterations in cases where we have conflicting buses as critical buses. This problem can be addressed by simultaneously considering multiple buses for control. These issues are being investigated at this time. TABLE III. Bus voltages in each iteration (IEEE 30bus) Bus Before Iter. 1 Iter. 2 Bus Before Iter. 1 Iter. 2 1 1.000 1.000 1.037 16 0.968 0.948 0.991 2 1.000 1.000 1.100 17 0.967 0.941 0.990 3 0.957 0.947 1.014 18 0.961 0.938 0.976 4 0.949 0.936 1.010 19 0.957 0.932 0.974 5 0.959 0.950 1.041 20 0.961 0.934 0.979 6 0.926 0.908 0.988 21 0.991 0.957 1.006 7 0.929 0.915 1.000 22 1.000 0.965 1.013 8 0.878 0.857 0.941 23 1.000 0.972 0.980 9 0.958 0.932 0.994 24 1.020 0.977 1.014 10 0.975 0.945 0.998 25 1.116 1.045 1.096 11 0.958 0.932 0.994 26 1.100 1.028 1.079 12 0.977 0.964 1.000 27 1.000 0.900 0.968 13 1.000 1.000 1.019 28 0.925 0.898 0.977 14 0.969 0.953 0.985 29 0.980 0.877 0.947 15 0.974 0.955 0.984 30 0.968 0.864 0.935

REFERENCES [1] S. Corsi, Voltage Control and Protection in Electrical Power Systems From System Components to Wide Area Control. London, UK: Springer, 2015. [2] B. M. Weedy, Electic Power Systems, 5 th ed. New York: Wiley, 2012 [3] C. W. Taylor, Power System Voltage Stability. New York: McGraw-Hill, 1994. [4] F. Saccomanno, Electric Power Systems Analysis and Control. New York: Wiley-IEEE Press, 2003. [5] H.U. Banna, A. Luna, S. Ying, H. Ghorbani, P. Rodriguez, Impacts of wind energy in-feed on power system small signal stability, 3rd International Conference on Renewable Energy Research and Applications, Milwakuee, 19-22 Oct 2014. [6] A.C. Tobar, H.U. Banna, C. K. Ciobotaru, Scope of electrical distribution system architecture considering the integration of renewable energy in large and small scale, IEEE PES Innovative Smart Grid technologies Conference, Europe 2014. [7] A. Iqbal, M. Faraz, M.S. Tariq, H.U. Banna, Economic analysis of a small hybrid power system, IEEE Power Generation System and Renewable Energy Technologies (PGSRET), 2015. [8] A.K Cabrera, H.U. Banna, C.K. Ciobotarus, S. Ghosh, Optimization of an air conditioning unit according to renewable energy availability and user s comfort, IEEE PES Innovative Smart Grid technologies Conference, Europe 2014. [9] T. Iqbal, H.U. Banna, Control system design to automate 100KV impulse generator, International Journal of Scientific and Engineering Research, vol. 5, no. 4, April 2014. [10] P. Kundur, Power System Stability and Control. New York: McGraw- Hill, 1994. [11] H. Saadat, Power System Analysis, 2 nd ed. McGraw-Hill WCB, 2002. [12] Y. Zhu et al., Study on Reactive Power and Voltage Control in Large Grid Based on Sensitivity Analysis, Proc., Power and Energy Engineering Conference (APPEEC), IEEE 2012. [13] R. Schlueter, I.-P. Hu, M. Chang, J. Lo, and A. Costi, "Methods for determining proximity to voltage collapse," IEEE Transactions on Power Systems, vol. 6, no. I, pp. 285-292, Feb 1991. [14] R. Schlueter, "A voltage stability security assessment method," IEEE Transactions on Power Systems, vol. 13, no. 4, pp. 1423-1438, Nov 1998. [15] C. Aumuller and T. Saha, "Determination of power system coherent bus groups by novel sensitivity-based method for voltage stability assessment," IEEE Transactions on Power Systems, vol. 18, no. 3, pp. 1157-1164, Aug 2003. [16] P. Lagonotte, J.-c. Sabonnadiere, J. Leost, and J. Paul, "Structural analysis of the electrical system: application to secondary voltage control in france," IEEE Transactions on Power Systems, vol. 4, no. 2, pp. 479-486, May 1989. [17] J. Zhong, E. Nobile, A. Bose, and K. Bhattacharya, "Localized reactive power markets using the concept of voltage control areas," IEEE Transactions on Power Systems, vol. 19, no. 3, pp. 1555-1561, Aug 2004. [18] E. Nobile and A. Bose, "A new scheme for voltage control in a competitive ancillary service market," Proceedings of PSCC'02, 14 th Power System Computation Conference, June 2002. [19] R. Maharjan and S. Kamalasadan, A New Approach for Voltage Control Area Identification Based on Reactive Power Sensitivities, North America Power Symposium (NAPS), 2015. [20] D. C. Lay, Eigenvalues and Eigenvectors, in Linear Algebra and its Applications, 4 th ed. Boston, MA: Pearson Education, 2012. [21] G. Strang, Eigenvalues and Eigenvectors, in Introduction to Linear Algebra, 5 th ed. Welleslay MA: Welleslay-Cambridge Press, 2016. [22] S. Tilekar. (2016, July 26). on physical significance of eigenvalues [Online], Available: https://www.quora.com/what-is-the-physicalsignificance-of-eigenvalues [23] D. C. Lay, Symmetric Matrices and Quadratic Forms, in Linear Algebra and its Applications, 4 th ed. Boston, MA: Pearson Education, 2012. [24] G. Strang, The Singular Value Decomposition (SVD), in Introduction to Linear Algebra, 5 th ed. Welleslay MA: Welleslay-Cambridge Press, 2016. [25] R. D. Zimmerman, C. E. Murillo-Sánchez, and R. J. Thomas, "MATPOWER: Steady-State Operations, Planning and Analysis Tools for Power Systems Research and Education," IEEE Transactions on Power Systems, vol. 26, no. 1, pp. 12-19, Feb. 2011. [26] R. D. Zimmerman, C. E. Murillo-Sánchez, and R. J. Thomas, "MATPOWER's Extensible Optimal Power Flow Architecture," Power and Energy Society General Meeting, 2009 IEEE, pp. 1-7, July 26-30 2009.