ADAM-4022T Serial Base Dual Loops PID Controller User s Manual

Similar documents
ADAM-4022T Serial Base Dual Loops PID Controller User s Manual

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E

Universal Controller

DC1010/DC1020/DC1030/DC1040

APPENDIX APPENDIX A 1

Series Temperature Controller Instruction Sheet

Series Valve Temperature Controller. Instruction Sheet

PROCESS & TEMPERATURE CONTROLLERS

Series F4P Communications Guide

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

XC series PLC expansion module User Manual

Shenzhen ATC Technology CO.,LTD ATC. A-1 Serial Remote I/O Module. User Manual. V1.13 Edit:2018/01/

CT435. PC Board Mount Temperature Controller

OVEN INDUSTRIES, INC. Model 5C7-362

Modbus Integration Integration for Modbus Functionality for VT8300 Series

BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules

ADAM 4000/4100 Series

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

PROGRAMMABLE CONTROLLER

TC LV-Series Temperature Controllers V1.01

Industrial Modbus I/O Modules

PL420 PROGRAMMABLE LOGIC CONTROLLER

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER

I-7088, I-7088D, M-7088 and M-7088D User Manual

Network Instrumentation Module Controller Module NX-D15/25/35

MELSEC-L Temperature Control Module User's Manual -L60TCTT4 -L60TCTT4BW -L60TCRT4 -L60TCRT4BW

InsuLogix T MODBUS Protocol Manual

K3P ENG.qxd 23/10/ Pagina 1

CoolEx User Manual 2008 XDIMAX LTD. Revision 1.0

SRC-110 Series Zone Controllers with Modbus RTU

GE Fanuc IC695ALG600. Rx3i PacSystem

TECHNICAL DATASHEET #TDAX022420

High Performance Process & Temperature Controllers

Excellent low-cost Process & Temperature Controllers

MV110-8AS. Analog input module 8 channel. User guide

SRC-110 Series Zone Controllers. BACnet MS/TP. Product sheet CT2.143 SRC-110-BAC

NX Series Inverters. HVAC Pocket Programming Guide

APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1

WCT W Single Coil TX V3.0 Runtime Debugging User s Guide

Technical Bulletin, Communicating with Honeywell TM ST3000/STT3000 Smart Transmitters

Digital Temperature Controller

CM3-SP04EAO CM3-SP04EAA CM3-SP04EOAI CM3-SP04EOAV

Bulletin B1243: RIBTW24B-BCAI RIBMNW24B-BCAI

F4-08RTD 8-Channel RTD Input

MICRO-CONTROLLER X (48 48 mm)

Modbus communication module for TCX2: AEX-MOD

I/A Series Model 718TC 1/8 DIN Temperature Controller with ma Output

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

DIN rail mounting temperature controller with current transformer input deltadue series D1 line

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

Technical Manual. Standard Communication Protocol TA3840C

MPS SERIES. INSTALLATION and TECHNICAL MANUAL MPS 4 MPS 5 MPS 9 4 PV

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

XC-E6TCA-P Temperature control module User s manual

SMART TEMPERATURE TRANSMITTERS. smar

USB-TEMP and TC Series USB-Based Temperature Measurement Devices

LabCon User Manual. Multi-Purpose Temperature Controller Temp High SP

WCT W Single Coil TX V3.1 Runtime Debugging User s Guide

BACnet PTEC Controller Dual Duct 2 AVS - Constant Volume with Two Inlet Sensors and Optional Reheat, Application 6665

Uni-Mux XQL Multi-Channel Data Acquisition Module

Process controller with Modbus Master/Slave & PROFIBUS DP 1/8 DIN - 48 x 96 mm Platinum Series X5000 Line

RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application

Data Acquisition Modules/ Distributed IO Modules

Continental Hydraulics Installation Manual CEM-PA-A

E2P0 DVP

TTH300. Temperature transmitter. Additional Information. FOUNDATION Fieldbus. Measurement made easy

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

Table of Contents. HWIO-Gateway User Manual

PACSystems* RX3i IC695ALG600-DD

3 in 1 Laser Power Supply (diode driver + Q-switch driver + DC power supply of marking head)

PROGRAM CONTROLLER OUTLINE

Series Temperature Controller Instruction Sheet

VI. SET-UP PARAMETER. Input filter

2F. No.25, Industry E. 9 th Rd., Science-Based Industrial Park, Hsinchu, Taiwan Application Note of OGM220, AN001 V1.8

ZHUHAI PILOT TECHNOLOGY CO., LTD.

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup

MICRO-CONTROLLER X (96 96 mm)

PID Controller-Single Loop (1/16 DIN - Microcontroller Based) (Product Code 10.10)

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS

Process and Temperature Controllers

TECHNICAL DATASHEET #TDAX021901

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

GE Fanuc IC695ALG312. Rx3i PacSystem

MV110-8A. Analog input module 8 channel. User guide

The wireless alternative to expensive cabling...

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22.

The wireless alternative to expensive cabling...

XMT*JK two-way series temperature controller. Instruction manual

RWD68U Controller. Installation and Commissioning Guide Document No October 1, Function. Application

Automation System TROVIS 6400 Industrial Controller TROVIS Mounting and Operating Instructions EB 6497 EN. Electronics from SAMSON

PID CONTROLLERS LT SERIES

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2

PACSystems* RX3i. Isolated RTD Input Module, 8 Channels, IC695ALG508-CA. Module Features. GFK-2501C November 2012

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

1. Model number Page OUT2 (Heating/Cooling control) action [Reverse (Heating) action]

TC-408 PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL

Transcription:

ADAM-422T Serial Base Dual Loops PID Controller User s Manual

Warning Message : The ADAM-422T is recommended to be used in general purposed air conditioning application. When using this product in applications that required particular safety or when using this product in important facility, pay attention to the safety of the overall system and equipment. For example, install fail-safe mechanism, carry out redundancy checks and periodic inspections, and adopt other appropriate safety measures as required.

ADAM-422T dual loop PID Controller Introduction Function The ADAM-422T dual loop PID controller is a Serial-based controller. It was designed as the product of Advantech s ADAM-4 series with Serial based PID controller With an excellent accuracy ±.15%, the ADAM-422T is an ideal controller for temperature and other process variable in heating and cooling application, test and environmental work. Easy to operate ADAM-422T utility software can help you to select input and range configuration, set the operating parameter (SP, Sv, Pv.. etc) for your process control needed. ADAM-422T utility software also integrates the trend chart to help you to monitor and debug your control setting. Industrial Design ADAM-422T was designed to use in industrial environment. It can be installed in standard DIN rail inside the cabinet. And it can be powered by unregulated 1~Vdc to meet the various power supplied source in field. It also withstands ambient temperature up to 6 o C and resists the effects of vibration and mechanical shock.

Wiring & Installation The ADAM-422T is a Dual loop PID controller. There are three analog input, one analog output, one digital input and one digital out put for each loop usage. The analog input channels is 16-bit, universal signal accepted design. It provides programmable input ranges on all channels. It accepts various analog inputs +/-1V, ~2mA and 4~2mA. The analog output channel is 12 bit with ~1V, ~2mA and 4~2mA acceptable input type. Each analog channel is allowed to configure an individual range for several applications. The digital input can be configured as the emergency shutdown trigger input and the digital output is designed as the common alarm output. The PID loop function can be disabled by ADAM-422T utility software tool, that is, ADAM-422T can be a pure universal I/O module after disabling the PID loop function. ADAM-422T Fig. 7-1 ADAM-422T Drawing

Application Wiring Fig. 7-2 Analog Input/Output Wiring Diagram Fig. 7- Digital Input/Output Wiring Diagram

Jumper Setting P AI P1 AI P AI1 P1 AI1 P AO P1 AO Initial Switch JP1 Loop 1 AI Channel JP2 Loop 1 AI Channel 1 JP Loop AI Channel JP4 Loop AI Channel 1 JP5,JP6 Loop AO Channel JP7,JP8 Loop 1 AO Channel I: Current Signal V: Voltage Signal Input Default: V Output default: I Note: When using RTD or Thermistor, please set the jumper to voltage signal setting. Initial Switch Setting You can set the initial mode by switching the switch to INIT, after setting your ADAM-422T, you can switch to NORMAL mode.

Operation Interface Open the ADAM 4 Utility Software, the software tool will auto-scan the ADAM 4 module through the network. Clicking the 422T in the system tree of left dialog block, User can select Modbus or BACnet as supported Protocol Clicking the 422T in the system tree of left dialog block to go to ADAM-422T configuration page. In this page, user can configure the input channel, output channel and PID loop function. And ADAM-422T support two communication protocol Modbus/RTU and BACnet MS/TP. User can select the supported protocol in this page.

Input Channel Configuration Page : In ADAM-422T input channel configuration page, user can enable the input channel, select the input signal type and select the DI status. Channel, 1 is the analog input as the control parameter for PID loop and channel 2, is for PID loop 1 when the PID loop function is enabled. ADAM-422T also support MODBUS/RTU protocol, user can see the detail MODBUS address register number for each channel in this page. It can be a very important reference for communication work. Input Channel Config. Page Input Signal Type Select MODBUS Register Address

Calibration ADAM-422T input channel configuration also support Zero and Span calibration function. Clicking the Zero Calib and Span Calib bottom to go to the calibration dialog block, user can set the initial zero value and span range then click the Execute bottom to proceed the channel calibration work. Please refer the following pictures for operation guideline.

Output Channel Configuration Page : For output channel configuration, there are two analog output channel in ADAM-422T. The output channel is used as the control output for PID loop and channel 1 is for PID loop 1 when PID loop function is enabled. The configuration for output channel is quite similar as input configuration. User can easily to finish the configuration with the friendly operating interface of ADAM-422T utility software. Channel Calibration Output Signal Type Select Analog Manual Output Setting ADAM-422T can be a pure universal I/O module when PID being set in Free mode. User can use Data Area to setup the analog output to send a specific value for such kind application. This function can also be controlled with MODBUS/TCP protocol through Ethernet network for HMI/SCADA application. For calibrating the analog output channel, user can use external certificated signal measured device as calibrator then use the Trim for 4mA and Trim for 2mA calibrating function to fine tuning the channel output signal for calibration requirement.

PID Loop Configuration ADAM-422T is designed as a stand alone PID controller. We offer a very convenient software tool for user to configure the PID controlled parameter. In this configuration page, there is a real time trend chart to show the values changing of SV, PV and MV. It is very helpful for user to monitor and diagnose the PID control situation. For the functionality of the bottom in PID configuration page, please refer the explanation of the following table. Bottom Function PID loop number Control Mode Selection : Free : Stop PID Control Auto : PID Loop Automatically Manual : Manual Control

Parameter Setting and Monitoring SV : Setpoint Value PV : Process Value MV : Controlled Output Value PV, MV Alarm Status PID Setting Button (go to PID setting page) PID Tuning Button (go to PID tuning page) After finishing the setup work in configuration page, please click the setting bottom to go to the detail parameter setting screen.

PV/SV Setting : Button SV Range High SV Range Low PV Range High PV Range Low Low Pass Filter Interval (msec) Alarm H-High Alarm High Alarm Low Alarm L-Low Function PID Algorithm: Standard: Standard PID calculation. DIFF First: Differentiation as first priority. SV high limit value SV low limit value PV high limit value PV low limit value Low Pass Filter set value Low Pass Filter Calculation : MV Feedback = ing MV x Filter Value + Previous MV x (1- Filter Value) PID loop sensing time interval SV & PV High High alarm setpoint SV & PV High alarm setpoint SV & PV Low Low alarm setpoint SV & PV Low alarm setpoint

MV Setting Button Range High Range Low Filter (.~1.) MV Init. Value MV Output High MV Output Low MV E-Stop Value Function PID Action: Control Action Mode Setting Direct: Direct (Heating) Action, The "MV" decreases when the "PV" increases. Reverse: Reverse (Cooling) Action, The "MV" increases when the "PV" increases. MV/FB high limit value MV/FB low limit value Filter set value Setting MV initial value MV output high limit MV output low limit Setting MV frozen value while PID being emerged shutdown

For PID parameter tuning, please refer the PID tuning page. In this page, the P, I, D parameters can be adjusted to achieve the optimal control result. The real time trend chart provides a powerful tool for user to supervise the parameters adjustment result.

Appendix A ASC II Command Set Command Description Remarks % AANNTTCCFF Sets the address, input mode, baud rate, checksum status (NN: new address TT: always CC: baudrate FF: bit6=1 checksum enable bit6=1 checksum disable)!nn: OK $AAB channel diagnostic!aammmm: OK (m: normal 1 over highest value 2 over lowest value invalid calibration) $AAF $AAM $AA $AA1 $AA2 $AA2Ci $AA2Cihhh $AACi Return the firmware version code from the specified module.!aaav.vv: OK Return the module name from the!aa422t: OK specified module Calibrate the analog input module to!aa: OK correct the gain error Calibrate the analog input module to!aa: OK correct the offset error Returns the configuration!aaccff: OK parameters. the MAX calibration value for!aacihhh: OK analog output (i: channel ~1) Calibrate the analog output to correct the MAX value (i: channel ~1 hhh: 12bits raw data) the MIN calibration value for analog output (i: channel ~1) $ AACihhh Calibrate the analog output to correct the MIN value (i: channel ~1 hhh: 12bits raw data) $AA5vv $AA6 $AA7 Enable/Disable multiplexing (vv: ~F) Asks a specified input module to return the status of all AI channels Asks a specified module to return the status of all DI/DO channels!aa: OK!AACihhh: OK!AA: OK!Aa: OK?Aa: error!aavv: OK!AAooii: OK

Command Description Remarks $AA7CiRrr Set the channel input range code (i: channel ~!AA: OK rr: range code) $AA8Ci the channel input range code (i: channel ~)!AACiRrr: OK $AA9Ci the channel output range code!aacirrr: OK $AA9CiRrr #AA #AAi #AAccdd #AACidd.ddd (i: channel ~1) Set the channel output range code. After setting, the output will be set to minimum value. (i: channel ~1 rr: range code) Return the input values from all channels of the specified analog input module Return the input value from the specified channel in the analog input module (i: channel ~) Set a single or all digital output channels. (cc: all channel, dd: ~ 1 channel, dd:~1 11 channel 1, dd:~1) Analog output to the specified channel (i: channel ~1 dd.ddd: engineering units)!aa: OK >+xx.xxx+xx.xxx+xx.xxx+xx.x xx: OK (format: V, ma is xx.xxx; RTD, Thermistor is xxx.xx) >+xx.xxx: OK >: OK >: OK #AAO all AO channel value >+xx.xxx+xx.xxx: OK #AAOi AO value from an output channel (i: channel ~1) >: OK #AAPRsscc PID value (ss: starting index, h~ffh cc: total tot read, MAX is 4h) #AAPWssvvvvvvvv Set PID value (ss: index, h~ffh vvvvvvvv: the long value) >aaaaaaaabbbbbbbb : OK each value use 8 HEX to indicate a long value >: OK

Appendix B Channel Specification Analog input channel Channel index in command Channel index in hardware LOOP Ain 1 LOOP Ain1 2 LOOP1 Ain LOOP1 Ain1 Input range code mapping and input calibration value Range code Range value Span calibration Zero calibration x7 4~2 ma 2. ma. ma x8 ~1 V 1 V V xd ~2 ma 2. ma. ma x2 PT-1 (-1~1 o C) 14 ohms 6 ohms a=.85 x21 PT-1 (~1 o C) 14 ohms 6 ohms a=.85 x22 PT-1 (~2 o C) 18 ohms 6 ohms a=.85 x2 PT-1 (~6 o C) 4 ohms 6 ohms a=.85 x24 PT-1 (-1~1 o C) 14 ohms 6 ohms a=.92 x25 PT-1 (~1 o C) 14 ohms 6 ohms a=.92 x26 PT-1 (~2 o C) 18 ohms 6 ohms a=.92 x27 PT-1 (~6 o C) 4 ohms 6 ohms a=.92 x2a PT-1 (-4~16 o C) 16 ohms 85 ohms x Thermistor K (~1 o C) 1 K ohms 2 ohms x1 Thermistor 1K (~1 o C) K ohms 8 ohms Output range code mapping Range code x x1 x2 Range value ~ 2 ma 4 ~ 2 ma ~ 1 V

Default setting Convert rate: 6 Hz Range code: x8 (1 V) Automatic ADC convert: false Channel mask: xf Auxiliary ADC: temperature sensor

Appendix C PID Parameters Table Modbus Register Loop Modbus Register Loop 1 41 41256 Code Open/Close Mode 412 41258 PID Mode 418 41264 4112 41268 Process value bare data Manipulator value bare data 4116 41272 DI On/Off 4118 41274 DO On/Off 412 41276 Set point Value 4124 4128 4126 41282 412 41288 414 4129 416 41292 414 41296 PV RH (Range high) PV RL (Range low) MV RH (Range high) MV & FB RH (Range low) PV engineering data MV engineering data / Decimal Place Descriptions Enable/Disable PID loop function :Open mode -- no PID control, ADAM-422T will be a pure I/O module 1:Close mode enable PID loop function 2:Manual mode manual control analog output PID Mode Selection :Standard PID Calculation Mode 1:Differential First Mode PV value MV value DI for Emergency Shutdown Alarm DO On SV (Set point Value) PV Source Engineering Value Range high (PV RH must > PV RL) PV Source Engineering Value Range low (PV RL must < PV RH) MV Engineering Value Range high MV RH must > MV RL MV Engineering Value Range high MV RL must < MV RL PV Source engineering data MV engineering data MV engineering data can not only be automatically created by PID loop, but it also can be manual setup when PID loop set in manual mode. It will be translated as MV bare data AO output MV RL<MV engineering data<mv RH

Modbus Register Loop Modbus Register Loop 1 Code 4144 41 PID PV value 4146 412 PID SV value 4148 414 PV Filter value 4154 411 PV Range / Decimal Descriptions Place PID PV value PID SV value 1st order filter value for PV source <(PV Filter value/1)<1. : ~ 1V 1: - 2mA 2: 4-2mA : PT-1 (85) 1~1 C 4: PT-1 (85) ~1 C 5: PT-1 (85) ~2 C 6: PT-1 (85) ~6 C 7: PT-1 (92) 1~1 C 8: PT-1 (92) ~1 C 9: PT-1 (92) ~2 C 1: PT-1 (92) ~6 C 11: PT-1 4~16 C 12: Thermistor K ~1 C 1: Thermistor 1K ~1 C 416 4116 MV Range : ~ 1V 1: - 2mA 2: 4-2mA 4162 4118 PID KP 4164 412 PID KI 4166 4122 PID KD 4174 41 PID KP (PID) 4176 412 PID KI (PID) 4178 414 PID KD (PID) PID Proportional factor for PV Source PID KP=(Input value/1) PID Integrated factor for PV Source PID KI=(Input value/1) PID Differential factor for PV Source PID KD=(Input value/1) PID Proportional factor for PID calculation PID Integrated factor for PID calculation PID Differential factor for PID calculation

Modbus Register Loop Modbus Register Loop 1 Code / Decimal Place Descriptions 418 416 Control loop period setting (msec) for PV <= : Loop empty > : Loop controlling 4184 414 Control loop period setting (msec)for PID <= : Loop empty > : Loop controlling 4186 4142 Count down value of control loop period counting value<= then calculating PID loop 4188 4144 Previous Loop Open/Close status Record the previous Loop Open or Close mode for Loop Initial set 419 4146 NSEC 4192 4148 OLD NSEC 4194 415 Power recovery action setting 4196 4152 MV Initial Value 4198 4154 Last DI State 411 4156 Last DO State 4112 4158 4114 416 4116 4162 PV Alarm HH limit PV Alarm H limit PV Alarm LL limit Calculating the newest Loop interval as nsec Calculating the previous Loop interval as old nsec : maintaining the previous MV output keep PID open 1: setting the previous MV output as initial value and keeping PID Close 2: PID open, using MV initial value as MV output MV initial value for power recovery action Previous Scan DI State (reference for control program) Previous Scan DO State (reference for control program) PV Alarm High High Limit Value (<PV RH) PV Alarm High Limit Value (<PV RH & PV Alarm HH) PV Alarm Low Low Limit Value (>PV RL)

Modbus Register Loop Modbus Register Loop 1 Code / 4118 4164 PV Alarm L limit 4111 4166 41112 4168 PV Alarm Dead Band % PV Alarm Status Decimal Place Descriptions PV Alarm Low Limit Value (>PV RL & PV Alarm LL) PV Dead band % <(Input Value/1)%<1 % PV Alarm Status Normal 1:HH 2 H :L 4:LL 4118 4194 MV Output High Limit MV Output High Limit (<MV RH) 4114 4196 MV Output Low Limit MV Output Low Limit (>MV RL) 41142 4198 MV Output Alarm Status MV Output Alarm Status Normal 1:H 2 L 41144 414 MV Emergency Value MV output value while emergency shutdown DI being active 41146 4142 PV open wire flag Normal 1 Open wire 4115 4146 PID Direct/Reverse Direct Mode 1 Reverse Mode 41152 4148 SV High Limit 41154 4141 SV Low Limit / SV High Limit value SV Low Limit value

MODBUS functions address mapping (1) Coils Address Mapping Table Index(Address) Remarks 1() DI status 2(1) DI 1 status ~16(2)~(15) Reserved (for those reserved area, there will be no effect if you set it) 17(16) DO status 18(17) DO 1 status 19~128(18)~(127) Reserved

(2) Registers Address Mapping Table Index(Address) Remarks 1() PAin value 2(1) PAin1 value (2) P1Ain value 4() P1Ain1 value 5~1(4)~(9) Reserved 11(1) AO value 12(11) AO 1 value 1~2(12)~(19) Reserved 21(2) PAin status (: normal; 1: over high; 2: over low; : invalid calibration) 22(21) PAin1 status 2(22) P1Ain status 24(2) P1Ain1 status 25~2(24)~(199) Reserved 21(2) PAin range code 22(21) PAin1 range code 2(22) P1Ain range code 24(2) P1Ain1 range code 25(24) AO range code 26(25) AO 1 range code 27~21(26)~(29) Reserved 211~212(21)~(211) Module name 21~214(212)~(21) Version 221(22) AI channel enable 1~1511 (999)~(151) PID data area (total 512 registers) Each PID data formed by two registers, for example: PID data[] = reg[1]*6555+reg[11] PID loop- occupies from PID data[] to PID [127]. PID loop-1 occupies from PID data[128] to PID [255]. For function x, x4, you can read 1 registers at most one time For function x1, you must set even number of registers at a time. The starting address must be an even number as well. You can only set at most 1 registers at a time. --- Not support

Appendix D BACnet objects supported Object type Instance Remarks Analog Input Refer to the PAin 1 Refer to the PAin1 2 Refer to the P1Ain Refer to the P1Ain1 Analog Output Refer to the AO 1 Refer to the AO1 Analog Value Refer to the PID SV of Loop 1 Refer to the PID MV of Loop 2 Refer to the PID SV of Loop Refer to the PID MV of Loop 1 Binary Input Refer to the DI 1 Refer to the DI 1 Binary Output Refer to the DO 1 Refer to the DO 1 Device 11 11 is the default object instance Loop PID loop 1 PID loop 1 Multi-state Input Refer to the PV alarm in PID loop 1 Refer to the MV alarm in PID loop 2 Refer to the PV alarm in PID loop 1 Refer to the MV alarm in PID loop 1 Multi-state Output Refer to the Control Mode in PID loop 1 Refer to the Control Mode in PID loop 1