ET 51 - Electrician Theory Examination Marking Schedule

Similar documents
FINAL - ET 60 - Electrician Theory Examination Marking Schedule

ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET

ET 40 - Electrician Theory Examination Marking Schedule

ET 61 - Electrician Theory Examination Marking Schedule

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

FINAL - EST Electrical Service Technician Answer Schedule

EAS Electrical Appliance Serviceperson Answer Schedule

ELECTRICIAN S THEORY EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2

EASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE. SECTION 1 Marks Reference Marking notes Qu 1 A 10 MΩ (2 marks)

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

, Power Industries and Communications Industry Training Board

Unit 27 Three-Phase Circuits

Licensed Electricians Practical Assessment (LEP)

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

Licensed Electricians Practical Assessment (LEP)

TN, TT & IT Earthing Arrangements

Module Title: Electrical Installation II Laboratory Sheet:

MV network design & devices selection EXERCISE BOOK

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Residual current circuit breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs)

TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

FIB / FIC. r with Overcurrent Protection (RCBO) Doepke. » effi cient. » reliable. » fl exible. » future-oriented

7. INSPECTION AND TEST PROCEDURES

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests

Residual Current Operated Circuit-Breakers (RCCBs)

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

CURRENT FUTURE REGULATIONS PROPOSALS

Electrical Protection System Design and Operation

INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

# - - Internal * On Line Examination

ELECTRICAL POWER TRANSMISSION TRAINER

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math

NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

Circuit Analyzer MS5908A. Operation S Manual MS5908A TEST. ma VA ms Hz% 12 A 15 A 20 A HOLD ms VA. V Vd Z RCD GFCI

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Variable Transformers Product Design & Engineering Data

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

L O V A G. T E S T I N S T R U C T I O N I E C / E N E d C O N D I T I O N S F O R T E S T I N G

17TH EDITION BS TH EDITION BS7671 HOW THIS AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.

Page 13-2 Page Page 13-7

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Protection of Electrical Networks. Christophe Prévé

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Industrial Electrician Level 3

Capacitor Switching Contactors

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

CONTENTS. 1. Introduction Generating Stations 9 40

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

technical information

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

Grounding Recommendations for On Site Power Systems

PROTECTION AGAINST FAULT CURRENT

Auto Diagnosis Test #2 Review

Transformer Protection Principles

MASTECH MS5908. Circuit Analyzer

2 Grounding of power supply system neutral

Fuseless Capacitor Bank Protection

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

Single-Phase Transformation Review

Wisconsin Contractors Institute Continuing Education

650 PHOENIX CONTACT Courtesy of Power/mation Energy Lane, Saint Paul, MN

Circuits and Circuit Elements

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

Busbars and lines are important elements

Impact Assessment Generator Form

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

COPYTRACER Anti-counterfeit registration number

Specialists in HV and MV test and diagnostics. Testing in Substations

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

Frequently Asked Question on Isolated Power Supply(IPS)

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

Chapter F Protection against electric shocks

Generator Protection GENERATOR CONTROL AND PROTECTION

Electrical Wiring: Commercial, Seventh Canadian Edition

NZQA registered unit standard version 2 Page 1 of 8. Demonstrate knowledge of theory for registration of electrical installers

NATIONAL SENIOR CERTIFICATE GRADE 12

QUICK SETUP GUIDE SECULIFE IP

PROTECTION of electricity distribution networks

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

MFT1700 series. Multifunction testers. User manual

Transcription:

ET 51 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker can exercise their discretion and decide on the overall accuracy of any answer that is presented in the candidate s own words. 3. Symbols and terms - alternatives Power W or P Voltage V or E or U Phase Active Question 1 (a) To determine whether the fault rating of the protection devices is adequate to safely interrupt a circuit. To find the prospective short circuit current level of the installation. (2 marks) (b) (i) Insulation resistance test (i) and (ii) are interchangeable 1 MΩ or 10,000Ω (ii) Earth leakage test 5 ma (c) No. It does not operate on residual pulsating (1½ marks) direct current. (d) (i) No effect. (ii) The power dissipated drops 10% The power dissipated drops 195W (e) 235 x 12 = 2820VA = 2115 W 2820 VA = 0.75 1

Question 1 (f) The main fuse may not operate due to the high impedance of the earth fault loop. Any metal not normally live could be live at up to 230V. The main switch does not isolate the installation. Internal components of equipment are live with control switch in the off position. Fire hazard at a high-resistance joint (g) (i) To ensure the device can safely clear the prospective short-circuit current. To ensure the protective device will operate in the required time (2 marks) (ii) (h) (i) An HRC fuse An ACB The maximum value of torque the motor can produce. (ii) 1500 rpm (i) Any TWO of: A touch voltage hazard between conductive parts and the mass of earth. Protective devices may not operate under fault conditions. Fire hazard at any high resistance joint in the main neutral. Over or under voltage could damage equipment particularly on three phase installations. (2 marks) (j) A thermistor detects a rise in temperature in the motor windings. The change in resistance operates the thermistor monitoring relay which opens the motor control circuit. 2

Question 2 (a) (i) An excessive current will flow 0n all phases * The HRC fuses will operate (blow). * The thermal overload will open the control circuit (ii) A sustained high current will flow on all phases * The HRC fuses will operate (blow). * The thermal overload will open the control circuit (iii) A sustained high current will flow on two phases * The HRC fuses will operate (blow). * The thermal overload will open the control circuit (b) (i) The thermal overload device would operate Within 2.5 to 3.5 minutes. (ii) The HRC fuses would operate Within about 0.2s (iii) The 50A fuse with 75A flowing will operate in about 10 minutes. The 50A fuse with 150A flowing will operate in about in 0.2s. 3

Question 3 (a) Star point earthed No marks can be For each switchboard - an earthing conductor connected to the earth bar. awarded for part (a), if there are any of the following hazards: For each switchboard - an MEN link between the neutral bar and earth bar. For each switchboard a neutral conductor between the neutral bar and the distribution neutral. A phase connected to a neutral bar No MEN link in either switchboard. No main earth on either switchboard The star point of the transformer is not earthed (b) The protective earthing conductor of the socket outlet final subcircuit The earth bar. MEN link and neutral bar The main neutral conductor The distribution neutral conductor to the star point of the transformer The transformer winding The distribution phase conductor The main phase conductor The main switch The final subcircuit protective device The phase conductor of the socket outlet final subcircuit (c) It is part that has the lowest impedance. 4

Question 4 (a) No marks can be awarded for part (a), if E N L L L there are any of the following hazards: Tripping Device Test button A short circuit No test resistance. The socket outlet is not earthed The test button circuit is connected to the supply side of the tripping device Test resistance Sensing coil/toroid Three-phase socket Correctly connected phases, neutral (1½ marks) and earth. Correctly connected test button and resistance Correctly connected sensing coil/toroid Correctly connected tripping circuit Correctly connected socket Working circuit (1½ marks) (b) It is the current imbalance required to trip the RCD It is the rated residual current of the device (c) * There is an imbalance between the neutral current and phase 5

Question 4 current * There is earth leakage current in the circuit Greater than the residual tripping current of the RCCB (d) RCBO Residual Circuit Breaker with overload (overcurrent) protection SRCD Socket Residual Current Device 6

Question 5 (a) (i) It shows that when the fault current rises The time taken for a fuse to blow shortens (ii) 25A fuse 50A fault current - would operate in about 60 seconds. 25A fuse - 200A fault current - would operate in about 0.08 seconds. (iii) 20 x 1.5 = 30A (iv) 1000 seconds (v) 90A (b) This is the maximum fault current the fuse can safely interrupt. (c) This is the time it takes to interrupt the flow of current and extinguish the arc. It is the sum of the pre-arc time and the arc time (d) This is the maximum current that the fuse is designed to carry continuously 7

Question 6 (a) V s = N s x V p Use of 230V in N p calculations is acceptable = 1 x 11000 47.8 = 230.13V (b) V 1 = V ph x 3 Use of 400V in calculations is acceptable = 230.13 x 3 = 398.6V (c) kva = V 1 x I L x 3 1000 = 11000 x 13.12 x 3 1000 = 249.96 kva (d) I L = VA (V 1 x 3) = 250000 (398.6 x 3) = 362.12A (e) Regulation % = VNL VFL x 100 VNL = 230-222 x 100 230 1 = 3.48% 8

Question 7 (a) Load 2 VAr = kva 2 - P 2 = 4600 2 -- 3450 = 3042.614 VAr Load 3 VAr = kva 2 - P 2 = 2500 2 -- 2300 2 = 979.796 VAr (b) Horizontal Vertical Watts (P) Var (Q) Load 1 9200 0 Load 2 3450 3042.614 Load 3 2300 979.796 Totals 14950 4022.41 Total VA kva = P 2 + VAr 2 = 14950 2 + 4022.41 2 = 139682282.21 = 15.481 kva (c) Pf = W VA = 14950 15481 = 0.965 9

Question 8 (a) (i) The motor is connected in delta with a line voltage of 400V (ii) L1 L2 L3 U V W W1 U1 V1 Correctly connected windings Links connected to achieve a delta configuration Links connected to achieve a three-phase supply (b) (i) To prevent the hoist starting if two phases on the supply were reversed. (ii) The hoist will go up if the down control is operated and will go down when the up control is operated. The upper and lower limits on the hoist become ineffective. (2 marks) (c) The thermal overload protects against a sustained current rise. In excess of overload current settings. The thermistor protects against excessive temperature rise in the motor. Regardless of whether the current rises. (d) (i) As the temperature (of a motor) increases the resistance of the thermistor falls. (ii) As the temperature (of a motor) increases the resistance of the thermistor rises. 10

Question 9 (a) kva = V L x I L x 3 1000 = 400 x 142 x 3 1000 = 98.38 kva (red phase) (b) The transformer is 100kVA (c) I PH = kva V L x 3 = 100,000 400 x 3 = 144.34A (d) I L = kva V L primary x 3 = 100, 000 11,000 x 3 = 5.24A (e) (i) A tap-changer (ii) On the high-voltage side The current switched by the tap-changer is small. (1½ marks) 11