When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Similar documents
2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Modeling insulation in high-voltage substations

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Lightning performance of a HV/MV substation

Insulation Co-ordination For HVDC Station

Substation Insulation Coordination Study

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring

ABSTRACTS of SESSION 6

Transformers connected via a cable Overvoltage protection

ABSTRACT 1 INTRODUCTION

TECHNICAL REPORT. Insulation co-ordination

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

GIS Disconnector Switching Operation VFTO Study

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

High voltage engineering

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

University of Zagreb Faculty of Electrical Engineering and Computing

Lightning overvoltage and protection of power substations

Utility System Lightning Protection

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

HIGH VOLTAGE Insulation Coordination

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Tab 8 Surge Arresters

The line-lightning performance and mitigation studies of shielded steelstructure

ArresterFacts 024. Separation Distance for Substations. ArresterFacts 024 Separation Distance for Substations. September 2014 Rev 7 Jonathan Woodworth

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

G. KOEPPL Koeppl Power Experts Switzerland

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Power System Studies

C4-301 EXPERIMENTAL EVALUATION OF TRANSFERRED SURGES IN MV TRANSFORMERS FROM HV/LV

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Transmission of Electrical Energy

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

7P Series - Surge Protection Device (SPD) Features 7P P P

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Power Quality and Reliablity Centre

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

INTERNATIONAL STANDARD

TRIGGERED by energy transition towards sustainability,

Protection against unacceptable voltages in railway systems

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

How OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA

Ferroresonance Experience in UK: Simulations and Measurements

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Tab 2 Voltage Stresses Switching Transients

Lightning transient analysis in wind turbine blades

X International Symposium on Lightning Protection

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

1. Introduction to Power Quality

Electric Stresses on Surge Arrester Insulation under Standard and

Investigation on the Performance of Different Lightning Protection System Designs

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

Overvoltage Protection of Light Railway Transportation Systems

Selection of MO surge arresters Overvoltage protection

Earthing of Electrical Devices and Safety

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

Insulation Test System

Electromagnetic Interference in the Substation Jose up 400/115 kv

Choosing the right Pico Technology active differential probe

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Transcription:

TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the way to install surge arresters close to a power transformer to provide protection against lightning overvoltage. Depending on the length of the cables used in the installation, the insulation levels in base insulators of surge arresters and bushings of transformers change according to the voltage they support. For validation purposes, the voltage at base insulators and bushings has been analysed for different cable lengths in a typical substation. The results obtained from the simulations conducted with the ATP-EMTP software show the maximum lengths that cannot be exceeded for each insulation level selected for base insulators and bushings in case of a 145 kv power transformer. KEYWORDS overvoltage, insulated cables, surge arresters, base insulators, transformer bushings 82

Jesús BERNAL Influence of cable lengths on power transformers protection Selection of the insulated bases in surge arresters 1. INTRODUCTION The purpose of this article is to investigate overvoltages which appear at the bushing terminals of a Power Transformer (PT) when the transformer is protected by surge arresters (SA) (see Fig. 1), as well as overvoltage appearing in the insulators of the base of surge arresters when an insulated cable provides the connection between the base and the surge counter. In order to study the cases above, three distances are considered: The distance between the PT and the point where the SA is connected: L1 The length of the conductor that connects the SA with the line: L2 The length of the grounding conductor of the SA (between the base and surge counter): L3 The length of the grounding conductor between the surge counter and the earthing system: L4 Figure 1. Physical representation of the system under study www.transformers-magazine.com 83

TRANSFORMER IN GRID In case of an overvoltage, conductors suffer a voltage drop when a high current flows through the surge arrester, affecting the terminal voltage In case of an overvoltage, each of the conductors in Fig. 1 will suffer a voltage drop when a high current flows through the surge arrester, affecting the terminal voltage. The considered length of the connection between the surge counter and the grounding system is about 1.5 metres. This length (L4) was kept constant because it determines the location of the counter, which has to be within easy reach for the worker conducting the reading. Fig. 2 illustrates the details of the surge arresters assembly. Depending on the distance between the base of the surge arresters and the surge counter (L3), the base insulators of surge arresters will suffer different overvoltage. Since many manufacturers recommend maximum lengths (L3) for the base insulators that they supply, overvoltage in these insulators has been studied depending on the length L3. 2. SYSTEM MODELLING This study is based on the use of detailed computational simulations using the Electro-Magnetic Transient Program - Alternative Transient Program (EMTP- ATP). This version of the EMTP (ATP) is a universal program system for digital simulation of transient phenomena, both electromagnetic and electromechanical in nature. Using this digital program, complex networks and control systems of arbitrary structure can be simulated. Besides the computation of transients, ATP has extensive modelling capabilities and additional important features. Also, the software is regularly updated by the EMTP-ATP user groups [1]. This model has been made in accordance with IEC 600071-4 [2] and the guidelines referenced under [3], [4] and [5]. Being a deterministic study, the worst-case scenarios will be considered here. 2.1 132 kv overhead lines The power transformer is fed from one OverHead Line (OHL). The typical model considered in this study has the following specifications: The impedance of each OHL is 300 Ω The velocity of propagation considered is 3 10 8 m/s There are two sections of the line. The first one is 10 km long (in order to avoid the reflection from the network side), which was used to model a transmission network with overhead lines supported by transmission towers. Towers were not taken into account in the modelling because this would reduce the overvoltage due to back flashover phenomenon (conservative assumption). In this way, there is a smaller possibility for earth leakages in the system, leaving the remaining groundings of the system more affected. The second section of 1 km in length was used to simulate the distance between the substation and the point at which the lightning strikes. It is clear that the situation would not be improved even if the distance was less than 1 km; however, the flashover nor back flashover phenomenon (conservative scenario) were not included here. A further analysis conducted as part of a sensitivity study could take into account these variables (flashover, corona, distances, etc). In addition, substations usually have a protection system provided by franklin rods or aerial grounding wires. It is considered that a lightning strike occurring near the substation will hit this equipment, and the literature usually refers to the distance between 600 and 1000 metres. In case a lightning strike hits the nearest gantry, the insulator of the surge arresters is the smallest concern. Please note that this is a deterministic study (not probabilistic), looking for weak points. 2.2 Power transformer 132 / 20 kv A typical capacitance of the HV winding to ground for 132 kv is 1.5 nf, and is evident from a final transformer test report. The study of overvoltages which appear at the bushing terminals is based on computational simulations using the EMTP-ATP Table 1. Typical capacitances for studies of power transformers at High Frequency (HF) Nominal voltage (kv) Capacitance (nf) 500 3 187-220-275 2.5 110-155 1.5 Figure 2. Assembly of surge arresters 84 66-77 1

A transferred overvoltage between windings has not been studied. The capacitance of the IEC standard is given in the high frequency section. However, a power transformer test report provides test results at power frequency. To get the capacitance at high frequency is a hard work, which requires using a detailed model of the power transformer and applying high frequency hypothesis. Furthermore, the reference [2] proposes values for typical capacitance between HV transformer winding and earth (see Table 1). 2.3 Conductors for setting of the surge arrester Typically, the surge arrester must be connected as close as possible to the equipment it protects (in this case the power transformer) to ensure its protection. However, the aim of the modelling is to study a range of different cases to establish how different cable lengths affect overvoltages. There are conductors whose length depends on the installation of surge arresters. In this model three different conductors have been taken into account (see Fig. 1 and Fig. 2): L1: The conductor used to simulate the distance at which the surge arrester is connected. Due to the layout requirements, the SA may not be installed near power transformers. This distance will vary from 0 to 40 metres. L2: The conductor needed to connect the surge arrester. Its length may vary from 1 to 3 metres. L3: The conductor that connects the SA with the discharge counter. Its length may vary from 1.5 to 7 metres, depending on the height at which SA is placed. This is an insulated cable in order to ensure the correct reading of the surge counter. L4: The connection of the SA between the surge counter and the grounding system is provided with one conductor of about 1.5 metres. These connections are modelled by an inductance of 1 µh/m, according to [2]. 2.4 Substation grounding system The considered resistance of the grounding grid was 1 Ω. As the frequency of the overvoltages and overcurrents appearing in conductors is much higher than the power frequency, it was necessary to apply the reference [2]. Due to ionization, earth connections are non-linear resistors, so the R (i) type 99 model of the ATP-EMTP was used (resistance that depends on the current which flows through it). After the calculations were performed, it was concluded that the value of 1 Ω does not change significantly with the frequency. 2.5 Surge arresters Surge arresters with a rated voltage of 145 kv have been selected for this study. Table 2 outlines various parameters of these arresters for further use in the EMTP model. 2.6 Lightning strike In this study, lightning overvoltage wave shapes have been taken into account [2]. According to [2], a lightning strike should Figure 3. Typical lightning current A lightning strike was modelled as an ideal current surge of negative polarity and the wave shape of 8/20 µs be modelled as an ideal current surge. The wave shape is defined in [9] with the parameters illustrated in Fig. 3. The wave shape of 8/20 µs was selected for the lightning current [2] model, because it is most widely used by manufacturers, utilities and universities. This is a current wave shape (not a typical voltage wave shape of 1.2/50 µs). The reference [9] suggests that 90 % of the lighting strikes are negative. Therefore, the negative polarity of the lightning strike has been selected for this study. In terms of the maximum lightning current, overhead lines are equipped with shield wires which prevent a direct lightning strike to the phase. Only a lightning strike with lower peak current values can directly strike the phase conductors. The value considered for this current was 20 ka [3]. Table 2. Surge arrester specifications Um (kv) Ur (kv) Uc (kv) Residual voltage at lightning impulse current (8/20 µs) Residual voltage at switching impulse current (30/60 µs) 5 ka 10 ka 20 ka 40 ka 1 ka 2 ka 3 ka 145 144 92 286 kv 328 kv 359 kv 394 kv 281 kv 291 kv 299 kv www.transformers-magazine.com 85

TRANSFORMER IN GRID 2.7 Time step and simulation time The range of time step is 1 to 20 ns according to [3]. The time step selected for this study was 5 ns since this is a common value. The simulation time ranges from 20 to 50 μs, and is typically at 40 μs [3]. For this study, the maximum simulation time was 2.06 milliseconds. As the lightning strikes at the instant of 2 milliseconds, the recommended simulation time to take the data is 2.04 milliseconds, so that the overvoltage data are maximum values that appear in this range. Figure 4. Electrical equivalent model 2.8 Corona effect According to IEC TR 60071-4 [2], the corona effect implies a higher capacitance of the wires due to ionization of the air around the wires. The corona effect appears both between phases and between phase and earth. However, since this effect tends to reduce the slope of the incident impulse, to ignore it is to assume a conservative position. 2.9 Complete model Fig. 4 shows the complete model of the installation under study, representing an approximation of the physical model to an electrical equivalent. Fig. 5 shows the ATPDraw model used for development of the simulations. Several sensitivity studies have been conducted on this model in order to analyse the impact of different parameters on the overvoltage. 2.10 Initial assumptions Figure 5. ATPDraw model of the system under study 86 This study demonstrates how a lightning strike causes the change of the overvoltage, as well as how this is affected by the margin of protection of the PT and the base insulators of surge arresters. In order Several sensitivity studies have been conducted in order to analyse the impact of different parameters on the overvoltage

This study demonstrates how a lightning Table strike causes a change of the overvoltage, as well as how this is affected by the margin of protection of the power transformer and the base insulators of surge arresters to carry out the study, sensitivity analysis was performed with L1, L2 and L3 conductor lengths. The Lightning Impulse Withstand Level (LIWL) considered for the 132 kv PT windings was 550 kv. The LIWL considered for base insulators of surge arresters was between 20 and 25 kv, based on our experience. 3. Initial basic insulation levels considered 132 kv transformer kvpeak -- 550 132 kv insulators to hold the SA kvpeak -- 20-25 When the distance L1 increases, more transients appear in the conductor. As the distance between the SA and the transformer grows, the waves of the voltage travel backwards and forwards through the cable (cable with the length L1) more frequently, whenever there is a discontinuity. -100-150 -200-250 -300 Equipment Unit Rated switching impulse withstand voltage Insulation levels Rated lightning impulse withstand voltage As stated earlier, the LIWL at power transformer terminals is 550 kv. If the considered Margin of Protection (MP) is 20 %, the maximum overvoltage should be 440 kv. This overvoltage is reached between 25 m and 30 m, as illustrated in Fig. 7. -350 3. LIGHTNING OVERVOLTAGES -400-450 Some studies are conducted so as to investigate various scenarios. However, all of them share the fact that a lightning strike hitting the overhead line occurs 1 km away from the SA. The goal is to find out how L1, L2 and L3 lengths influence the overvoltage in transformer bushings and in the base insulators of the SA. 3.1 L1 variation with constant values for L2 and L3 The considered values are shown in Table 4. Table 4. L1 length variations L1 L2 L3 L4 From 0 to 40 metres 2 metres 4.5 metres 1.5 metres 3.1.1 Voltage at power transformer terminals Fig. 6 illustrates the overvoltage at power transformer terminals. Collection of the voltage data for each length is given in Table 5. -500 2,0033 2,0087 2,0140 2,0193 2,0247 2,0300 [ms] 2,0353 Figure 6. Transients in the voltage at power transformer terminals when L1 changes Table 5. Peak values of the voltage at power transformer terminals when L1 changes Length L1 (m) - 401 0-413 15-446 30 480 470 460 450 440kV 440 430 420 410 400 390 0 5 10 15 20 25 30 35 40 Figure 7. Voltage at power transformer terminals when L1 changes www.transformers-magazine.com 87

TRANSFORMER IN GRID The base insulators of the surge arrester suffer more from transients when the distance between the surge arrester and the transformer is bigger 3.1.2 Voltage at the base insulators Fig. 8 shows the overvoltage at the base insulators of surge arresters. The maximum overvoltage values for each L1 length is given in Table 6. The base insulators of the SA suffer more from transients when the distance is bigger, as evident from the voltage waves in Fig. 8. The considered LIWL of the base insulators was between 20 kv and 25 kv. The length L1 has a greater impact on the transformer terminals than base insulators. When the conductor L1 increases by 20 metres, the voltage at the terminals rises by 40 kv, whereas the voltage in base insulators decreases by 1 kv. In other words, terminals are able to withstand the voltage higher by 2 kv per metre of the conductor, whereas base insulators are able to withstand the voltage lower only by 0.05 kv. 3.2 L2 variation with constant values for L1 and L3 The considered values are shown in Table 7. 20 15 Table 7. L2 length variations L1 3 metres 10 5 0 L2 L3 L4 From 1 to 3 metres 4.5 metres 1.5 metres -5-10 2,0034 2,0050 2,0066 2,0083 2,0099 2,0115 [ms] 2,0131 Figure 8. Transients in the voltage at the base insulators when L1 changes Table 6. Peak voltage values at the base insulators when L1 changes Length L1 (m) 15.65 0 15.6 15 15.04 30 3.2.1 Voltage at power transformer terminals Fig.10 illustrates the terminal overvoltage in three cases. The voltage data for each length is given in Table 8. Table 8. Peak voltage values at power transformer terminals when L2 changes - 399.3 1-401.5 2 Length L2 (m) -404 3 26 24 22 LIWL =20 kv 20 18 16 14 12 10 0 5 10 15 20 25 30 35 40 Figure 9. Voltage at the base insulators of surge arresters when L1 changes 88 LIWL =25 kv The length between the surge arrester and the transformer has a greater impact on the transformer terminals than on the base insulators

Typically, the length of the distance between the connection of the SA and the power transformer is always as short as possible in order to reduce the terminal overvoltage. However, Fig. 11 shows that there is no significant variation in the voltage with the change in the length of the conductor that connects the SA with the line if L1 is constant. The reason for this small variation can be explained as follows. As illustrated in Fig. 7, the overvoltage that appears when L1 is longer than 5 metres is remarkable. Taking into account that L2 is 2 m in length, this gives the total distance of 7 m. So, the overvoltage changes considerably when the total distance exceeds 7 m. The total length of the distance between the SA and the PT for this simulation was the sum of L1 (equalling to 3 metres) and L2 (which takes the value of 1, 2 or 3 metres). So, in this section, the distance was increased from 4 to 6 m, which is in the range of values where the voltage does not vary much (Fig. 7). The length to consider when installing a surge arrester is the total distance: L1 + L2. 3.2.2 Voltage at the base insulators Fig. 12 illustrates the overvoltage at the base insulators in three cases. The voltage data for each length is presented in Table 9. Although the voltage increases with the increase of L2, this is nothing in comparison to the way the voltage changes with the change in L1. The consequence of altering L1 is much more evident than that occurring with the change in L2. Fig. 13 illustrates the overvoltage at the base insulators of surge arresters. Although the voltage increases with the increase of distance L2, this is nothing in comparison to the way the voltage chang es with the change in dis tance L1 There is no significant variation in the voltage with the change in the length of the conductor that connects the surge arrester with the line if the distance between the surge arrester and the transformer is constant -290-310 -330-350 -370-390 -410 2,0040 2,0059 2,0079 2,0098 2,0117 2,0136 [ms] 2,0155 Figure 10. Transients in the voltage in terminals of power transformers when L2 changes 405 404 403 402 401 400 399 0,5 1 1,5 2 2,5 3 3,5 Figure 11. Voltage at power transformer terminals when L2 changes 18 14 10 6 2-2 2,0038 2,0044 2,0050 2,0056 2,0063 2,0069 [ms] 2,0075 Figure 12. Transients in the voltage at the base insulators when L2 changes Table 9. Peak voltage values in the base insulators when L2 changes 16.26 1 15.9 2 15.6 3 Length L2 (m) www.transformers-magazine.com 89

TRANSFORMER IN GRID The voltage at transformer terminals grows with an increase in L2, while the voltage at the base insulators of surge arresters decreases If there is an increase in L2, the PT terminal voltage grows, while the voltage at the base insulators of SA decreases. However the difference is small. 21 20 19 18 LIWL=20 kv 3.3 L3 variation with constant values for L1 and L2 The considered length values are shown in Table 10. Table 10. L3 length variations 17 L1 3 metres 16 L2 2 metres 15 L3 From 1 to 7 metres 14 1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 L4 1.5 metres Figure 13. Voltage at the base insulators when L2 changes -260-280 -300-320 -340-360 -380-400 -420 2,0036 2,0071 2,0107 2,0142 2,0178 2,0213 [ms] 2,0249 Figure 14. Transients in the voltage at power transformer terminals when L3 changes 445 440 435 430 425 420 415 410 405 400 395 1 2 3 4 5 6 7 Figure 15. Voltage at power transformer terminals when L3 changes 440 kv Although the voltage at the terminals does not change much, it will be demonstrated that in terms of the base insulators of the surge arresters, L3 is the most important length 3.3.1 Voltage at power transformer terminals Fig. illustrates the terminal overvoltage in three cases. The PT bushings voltage data for each length is presented in Table 11. Table 11. Peak voltage values at power transformer terminals when L3 changes Fig.15 illustrates the overvoltage at power transformer terminals. Although the voltage at the terminals does not change much, it will be demonstrated that in terms of the base insulators of the SA, L3 is the most important length. 3.3.2 Voltage at the base insulators Length L3 (m) 399 1 404 3 408.7 5 413.8 7 Fig.16 illustrates the overvoltage at the base insulators in three cases. The voltage data of for each length is presented in Table 12. Fig. 17 illustrates the overvoltage at the base insulators. 90

Table 12. Peak voltage values at the base insulators when L3 changes Length L3 (m) 5.41 1 15.5 3 24.9 5 33.8 7 The bigger the length L3, the greater the voltage drop at the terminals and base insulators. Therefore, it is advised to use a short distance for the grounding conductor. L3 is the conductor which has the strongest impact on the voltage at the base insulators. If L3 is longer than 5 metres, the base insulators of 25 kv LIWL will not withstand the overvoltage. If the voltage was higher than the LIWL of insulators, the discharge current measured by the surge counter would be lower than the real one because part of it would pass through the base insulators. 4. RESULTS The voltage in the bushings of power transformers and the voltage at the base insulators of surge arresters depends on the way the surge arresters are assembled. More specifically, it depends on L1, L2 and L3 lengths. The sections below explain the influence of each conductor length (L1, L2 & L3) on each parameter (PT protection or insulators of SA protection). Changing L1 distance (L2 and L3 constants): With an increase in length, there is an increase in the overvoltage at PT terminals. According to the hypothesis taken in this study, at more than 25 m in length, the recommended MP is less than 20 %. With an increase in length, the voltage at the insulators of the SA decreases, but not significantly. In fact, terminals withstand the voltage higher by 2 kv per meter of the conductor, whereas base insulators withstand the voltage which is only 0.05 kv lower. In conclusion, L1 must be as short as possible. 40 30 20 10 0-10 -20-30 2,0037 2,0051 2,0066 2,0080 2,0095 2,0109 [ms] 2,0124 Figure 16. Transients in the voltage at the base insulators when L3 changes 40 35 30 25 20 15 10 5 0 1 2 3 4 5 6 7 Figure 17. Voltage at the base insulators when L3 changes LIWL=25 kv LIWL=20 kv The bigger the length L3, the greater the volt age drop at the terminals and base insulators; therefore, it is advised to use a short distance for the grounding conductor www.transformers-magazine.com 91

TRANSFORMER IN GRID A further analysis is required to consider deeper effects of L3 on the wave shapes, peak values, etc. at the base insulators of surge arresters Changing L2 distance (L1 and L3 constants): With an increase in length, there is an increase in the voltage at PT terminals. With an increase in length, the voltage at the insulators of the SA decreases, but not significantly. The total length of the distance between the SA and the PT for this simulation is the sum of L1 and L2. Changing L1 or L2 modifies the total distance between the SA and the PT. The sum of L1 and L2 must be as short as possible. Changing L3 distance (L1 and L2 constants): With an increase in length, there is a slight increase in the voltage at PT terminals. With an increase in length, the voltage in the base insulators of the SA increases. In this case, variations in length L3 have the strongest impact on the voltage at the insulators. Also, the length has to be selected depending on the LIWL of the base insulators. It is important to highlight that the connection between the base and the surge counter is provided by the insulated cable, so manufacturers of surge arresters can provide assistance in selecting L3. A further analysis is required to consider deeper effects of L3 on the wave shapes, peak values, etc. at the base insulators of surge arresters. 5. CONCLUSIONS Bearing in mind that the system commonly requires a 20 % margin protection, Table 13 provides a summary of the conclusions: Table 13. Influence of the length of conductors on terminals and base insulators Conductor variations (length or total length) L1 High Negligible L1 + L2 High Negligible L1 + L2 + L3 High -- L3 Impact on the overvoltage at the power transformers bushings Negligible (for typical lengths of L3) Impact on the overvoltage at the surge arresters base insulators High Author Jesús Bernal holds a degree in electrical engineering and works with a major Spanish utility (Iberdrola). His work involves electrical studies, modelling and simulating AIS & GIS substations, power transmission lines, off-shore and on-shore wind farms, photovoltaic plants, etc. He has an extensive experience in developing insulation coordination studies and earthing grids design/calculations. In addition, he provides support to other parts of the projects: technical specifications of substation equipment and evaluation of technical offers for procurement procedures, substation design, etc. A further analysis is required to consider deeper effects of L3 on the wave shapes, peak values, etc. at the base insulators of surge arresters. 6. BIBLIOGRAPHY [1] European EMTP Users Group, Alternative Transients Program, www.eeug.org [2] IEC, Insulation Coordination, Part 4: Computational Guide to Insulation Coordination and Modelling of Electrical Networks, Technical Report IEC TR 600071-4, First Edition, 2004-06 [3] Ali F. Imece, Daniel W. Durbak, Hamid Elahi, Modelling guidelines for fast front transients. Report prepared by the Fast Front Transients Task Force of the IEEE Modelling and Analysis of System Transients Working Group. December 1997 [4] Working Group 02 (Internal Overvoltages) of Study Committee 33 (Overvoltages and Insulation Coordination). Guidelines for representation of the network elements when calculating transients, CIGRE, Vol. 39, Paris, 2000 [5] Electrical Parameters and Impedance characteristics of plant, lines and cables. Technical Guidance Note. TGN (E) 166 / National Grid, Vol. 2 / February 2002 [6] IEC, Insulation Coordination, Part I: Definitions, Principles and Rules, International Standard IEC 71-1, 17th Edition, 1993-12 [7] J. A. Martinez Velasco (Editor), Computer Analysis of Electric Power System Transients: Selected Readings, IEEE Press, 1997 [8] J. A. Martínez Velasco (Coordinador), Coordinación de aislamiento en redes eléctricas de alta tensión, Madrid: Mc Graw Hill, 2007. ISBN: 978-84-481-6697-7 [9] IEC, High-current test techniques Definitions and requirements for test currents and measuring systems, IEC 62475-4, 2010-09 [10] Working Group 01 (Lightning) of Study Committee 33 (Overvoltages and Insulation Co-ordination). Guide to procedures for estimating the lightning performance of transmission lines. CIGRE, Vol. 63, Paris, October 1991 92