Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Similar documents
Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

GIS Disconnector Switching Operation VFTO Study

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

Tab 2 Voltage Stresses Switching Transients

The various factors influencing the VFTO levels in 500kV and. 750kV GIS have been discussed by developing the simulink models which

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

High voltage engineering

Sources of transient electromagnetic disturbance in medium voltage switchgear

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Modeling insulation in high-voltage substations

Analysis of Very Fast Transient over Voltages of Transformer in Gas Insulated Substation (GIS) using Wavelet Technique

Power Quality and Reliablity Centre

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

TECHNICAL REPORT. Insulation co-ordination

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

A Study on Ferroresonance Mitigation Techniques for Power Transformer

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

ANALYSIS OF VERY FAST TRANSIENT OVER VOLTAGES IN GAS INSULATED SUBSTATION

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

EE 1402 HIGH VOLTAGE ENGINEERING

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY. Approach for Fault Detection in GIS.

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

Effect of Shielded Distribution Cable on Very Fast Transients

Abstract. 1 Introduction

Utility System Lightning Protection

AORC Technical meeting 2014

Ferroresonance Experience in UK: Simulations and Measurements

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Switching Induced Transients:

Lightning overvoltage and protection of power substations

FERRORESONANCE SIMULATION STUDIES USING EMTP

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

CONTENTS. 1. Introduction Generating Stations 9 40

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Lightning performance of a HV/MV substation

Lightning transient analysis in wind turbine blades

G. KOEPPL Koeppl Power Experts Switzerland

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Electric Stresses on Surge Arrester Insulation under Standard and

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Although shunt capacitors

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Chapter 1. Overvoltage Surges and their Effects

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Electrical Power and Energy Systems

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Electrical Power Systems

ABSTRACT 1 INTRODUCTION

DEPARTMENT OF EEE QUESTION BANK

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

Generation of Sub-nanosecond Pulses

Insulation Co-ordination For HVDC Station

DC current interruption tests with HV mechanical DC circuit breaker

Single Line Diagram of Substations

Substation Preventive Maintenance

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

A MODEL TO SIMULATE EM SWITCHING TRANSIENTS IN ELECTRIC POWER DISTRIBUTION SUBSTATIONS

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Coherence and time-frequency analysis of impulse voltage and current measurements

Transcription:

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering College, Moinabad, Hyderabad Abstract: --VFTO of a 132 kv gas insulated substation have been calculation by using EMTP 2.4 version software. This paper is focused on simulation options of the transient connection GISoverhead line in simulation software. However, it is difficult to find a model presentation in certain software. Due to this fact, this paper shows possible ways of simulating the GIS-air connection with objects in EMTP 2.4 Software. Calculation of Transient Overvoltage has been carried out using EMTP software for various switching conditions in a 2-phase 132kV gas insulated substation. Keywords Control circuitry, EMTP Software, Gas Insulated Substation (GIS), Transient overvoltages, Switching operations, 2-phase fault I. INTRODUCTION VFT arise within a gas-insulated substation (GIS) any Time there is an instantaneous change in voltage. Most often this change occurs as the result of the opening or closing of a disconnect switch, but other events, such as the operation of a circuit breaker, the closing of a grounding switch, or the occurrence of a fault, can also cause VFT. These transients generally have a very short rise time, in the range of 4 to 100 ns, and are normally followed by oscillations having frequencies in the range of 1 to 50 MHz[1]. Their magnitude is in the range of 1.5 to 2.0 per unit of the doubleline-to-neutral voltage crest, but they can also reach values as high as 2.5 per unit. These values are generally below the BIL of the GIS and connected equipment of lower voltage classes. VFT in GIS are of greater concern at the highest voltages, for which the ratio of the BIL to the system voltage is lower[2]. Some equipment failures and arcing problems between grounded parts have occurred at system voltages above 132 kv, they have been correlated with disconnect switch and circuit breaker operation[3]. The generation and propagation of VFT from their original location throughout a GIS can produce internal and external overvoltages. The main concern are internal overvoltages between the center conductor and the enclosure. However,external VFT can be dangerous for secondary and adjacent equipment. These external transients include transient voltages between the enclosure and ground at GISair interfaces, voltages across insulating spacers in the vicinity of GIS current transformers, when they do not have a metallic screen on the outside surface, voltages on the secondary terminals of GIS instrument transformers, radiated electromagnetic fields (EMF) which can be dangerous to adjacent control or relay equipment[4]. VFT can also occur during switching of vacuum breakers and with certain lightning conditions. The objective of this document is to present an explanation of the VFT phenomena that can occur in GIS and provide guidelines for representing GIS components in digital simulations. Some examples with detailed input data are presented. A discussion about the accuracy of the simulations and their verification with field Measurements are also included[5]. The simulation depends on the quality of the model of each individual GIS component. In order to achieve reasonable results in GIS structures highly accurate models for each internal equipment and also for components connected to the GIS are necessary. The disconnector spark itself has to be taken into account by transient resistance according to the Toepler s equation and subsequent arc resistance of a few ohms[6]. During recent field tests on a 132KV substation, measurements were made of the trapped charge left when a DS was opened onto a floating section of switchgear. Numerous measurements led to the conclusion that for this switch, a potential of 0.1 0.2p.u is left on the floating section and that this result is consistent [7][8]. For a range of frequencies lower than 100 MHz, a bus duct can. be represented as a lossless transmission line. The surge impedance and the travel time can be calculated from the physical dimensions of the duct. Empirical corrections are usually needed to adjust the propagation velocity. 13

Experimental results show that the propagation velocity in GIS ducts is close to 0.95-0.96% of the speed of light. The error committed by ignoring skin effect losses is usually negligible[9]. II. CALCULATION OF 3-PHASE TO 2-PHASE IN A 132KV GAS INSULATED SUBSTATION The calculated values of the circuit parameters in previous chapter, the equivalent circuits are constructed by using EMTP software. By using the circuits the transients are calculated for different lengths of Gas insulated substation. The transients are also calculated during the faults with and without load at different distances. During the current operation of dis-connector switch in a GIS, re-strikes(pre-strikes) occur because of low speed of the dis-connector switch moving contact, hence Very fast Transient Over voltage are developed. These VFTO s are caused by switching operations and 3-phase fault to 2-phase in 132Kv GIS. Using EMTP of the equivalent models is developed. For simulating Very Fast Transient Overvoltages two concepts are important. One is the representation of the spark channel development and the other is the equivalent circuits of different GIS components under these conditions transient occur. For considering a strike across the switching contacts, voltage collapse across the disconnector during the strike and voltage drop across the disconnector after the strike occurs are important factors for estimating the VFTO levels in a GIs. The source of these VFTO s is due to the restrikes or prestrikes during disconnector opening or closing operations, which generate the travelling wave. Due to its construction the GIS is considered as a series of very short lengths transmission lines made up of many sections of different values of surge impedances derived from the capacitance and inductance values of each section. As a consequence there are many reflections and refractions of the travelling wave occurring at the points of discontinuity. The result is a network of high frequency overvoltages appearing within the GIS. The Very Fast Transient Over voltages are caused by two ways, due to switching operations and line to 2- phase faults. Since the contact speed of disconnector switches is low, restriking occurs many times before the interruption is completed. Each restrike generates Very Fast Transient Over voltages with different levels of magnitude. Isolators (also called disconnects/disconnectors) are installed in several locations in a GIS and are referred to as busbar isolators or line isolators. Two situations can be examined during switching action of an isolator. 1. Two networks are to be isolated, for example, on the right and left of the GIS; each network has its distributed inductance and capacitance. Under unfavorable conditions, there can be a phase shift between the voltage of the two networks, and a voltage of twice the system voltage can arise across the poles of the isolator (Fig. 1). 2. The second more frequent use is to connect or disconnect unloaded portions of the GIS. The second network on the right in Fig. 1, system 2, is absent and the isolator disconnects a part of GIS or overhead line from the source. Disconnector operation typically involves slow-moving contacts that result in numerous discharges during operation. A restrike occurs every time the voltage between contacts exceeds the dielectric strength of the gaseous medium. Each restrike generates a spark, which equalizes the potential between the contacts. Following spark extinction, the source and load-side voltages again deviate and another spark occurs when the voltage across the contacts reaches new dielectric strength. Now consider the opening of disconnect with flashover. Assume that the load side of the interrupter has trapped charge V1 and surge impedance Z1, and the source side has a trapped charge Vs and surge impedance Zs. At the time of breakdown (sparking occurs as soon as the voltage between the source and load exceeds the dielectric strength across the contacts), the voltage on the load side goes from V1 to: And the voltage on the source side goes from Vs to: After restrike, a high-frequency current will flow through the spark and equalize the capacitive load voltage to the source voltage. The potential difference across the contacts will fall and the spark will extinguish. A subsequent restrike occurs when the voltage between the contacts reaches the new dielectric strength level, determined by the speed of the parting of contacts and the disconnect characteristics. 14

The transient magnitude of the voltage on one side of disconnect can exceed if the surge impedances differ on the two sides of the disconnector, that is, if the disconnector is near a T or a capacitive voltage transformer is located close to the disconnector. In case of a line-to-ground fault, the voltage collapse at the fault location occurs in a similar way as in the disconnector gap during striking. Step-shaped travelling surges are generated and injected to GIS lines connected to the collapse location. The rise time of these surges depend on the voltage the collapse. Fig 1.A disconnector in GIS, interconnecting two systems, possible switching in phase opposition Fig. 2. Equivalent circuit for 10mtrs. Length in a 3 -phase to 2-phase of a 132kv GIS Fig. 3. EMTP circuit for 10mtrs length in a 3-phase to 2-phase of a 132KV GIS III. EQUIVALENT CIRCUIT FOR 132KV GIS SYSTEM This circuit is divided into three sections of 1mtrs, 4mtrs and 5mtrs respectively from load side and by the circuits shown in figure 2 & 3.are made use of. In a 3-phase circuit one phase 15

(say phase B) has been earthed. This in effect makes the transmission line of 2-phases only. The EMTP circuit of the same will be as shown in Fig 3 The Fast transient over voltages are generated not only due to switching operations but also due to 3-phase to 2-phase fault in 132Kv GIS.The bus duct is dividing into three sections of length from load side. The GIS bushing is represented by a capacitance of 125pf. The resistance of 1 ohm spark channel is connected in series with circuit breaker. EMTP Circuit for 10 mtrs. Length in a 3-phase to2-phase 132Kv GIS shown in the fig. 3. The proposed method implemented on EMTP the voltage before and after circuit breaker is taken to be 1.0 p.u and - 1.0pu as the most enormous condition but depending on the time of closing of circuit breaker the magnitude of the voltage on the load side changes. For different values of voltages on the load side the magnitudes and rise time of the voltage wave are calculated keeping source side voltages as constant as 1.0p.u the values are tabulated in table I. Similarly by changing the magnitudes of the voltage on the source side, keeping voltage on load side constant at 1.0p.u. Then the transient due to variation of voltage on source side obtained. The values are tabulated in Table II. TABLE I VR VY tr ty phase phase 1 1.0 2.40 2.41 12 13 2 0.9 2.36 2.38 11 12 3 0.8 2.24 2.26 12 13 4 0.7 2.05 2.04 14 11 5 0.6 2.03 2.05 13 12 6 0.5 1.80 1.79 13 13 7 0.4 1.73 1.67 12 12 8 0.3 1.66 1.64 13 12 9 0.2 1.48 1.46 12 11 10 0.1 1.36 1.37 12 12 IV. RESULTS AND DISCUSSION The various transient voltage and current at different positions in a 3 phase to 2-phase of a 132kv GIS for the first switching operation presented in results. The inductance of the bus bar is found out from the diameters of enclosure and conductors. The bus capacitance is calculated using formula for concentric cylinders. The maximum values of VFTO, the EMTP software is used and a simulation is carried out by designing suitable equipment circuits and its models are developed. The main advantages of such models are used to enable the transient analysis in GIS. During closed operation, the current through the resistance of the circuit breaker is shown in fig.4 & fig 5. From the graph it was found the maximum currents is 35A & 37A at a rise times of 15ns & 14ns. TRANSIENT DUE TO VARIATION OF VOLTAGE ON LODE SIDE S.no Load side Voltage Magnitude of the voltages VR VY Rise Time (Nano secs) tr ty phase phase 1-1.0 2.44 2.43 11 12 2-0.9 2.33 2.35 12 13 3-0.8 2.27 2.25 12 12 4-0.7 2.15 2.14 12 11 5-0.6 1.86 1.85 11 12 6-0.5 1.88 1.87 11 10 7-0.4 1.70 1.68 12 11 8-0.3 1.65 1.65 13 11 9-0.2 1.47 1.45 12 13 10-0.1 1.40 1.39 11 10 Fig. 4 Current waveform during closing operation of CB for 10mts length in a A-phase of 132kv GIS TABLE II TRANSIENTS DUE TO VARIATION OF VOLTAGE ON SOURCE SIDE S.no Load side Voltage Magnitude of the voltages Rise Time (Nano secs) 16

To introduce current chopping the circuit breaker is opened. The transients obtained during opening operation are shown in Fig 8. From the graph, the maximum voltages obtained are 1.22 and 1.24p.u. at rise times of 62 and 64ns respectively. The magnitudes and rise times of 10mts length GIS are tabulated in the table III. EMTP Circuit for 10mtrs. Length in a 3-phase to 2-phase 132kv GIS shown in the fig 3.. Fig. 5 Current waveform during closing operation of CB for 10mts length in a B-phase of 132kv GIS The transients due to closing of the circuit breaker are calculated as shown in fig 6 & fig 7. From this graph, the peak voltages obtained are 2.43 and 2.44p.u at rise times of 67 and 69ns respectively. The magnitudes and rise times of 10mts length GIS are tabulated in the table III. Fig. 8 Transient voltage waveform during opening operation of CB for 10mts length in a 3-phase to 2-phase(C Phase Earthed) of 132kv GIS Fig 6 Transient voltage wave from during closing operation of CB for 10mts length in a A-phase of 132kv GIS Assuming a second re-strike occurs the transients are calculated by closing another switch at the time maximum voltage difference occurs across the circuit breaker. The transients obtained due to second re-strike are shown in Fig 9 & fig 10. From the graph, the maximum voltages obtained is 2.53 and 2.54 p.u at arise time of 124 and 122ns respectively. The magnitudes and rise times of 10mts length GIS are tabulated in the table III. Fig 7 Transient voltage wave from during closing operation of CB for 10mts length in a B-phase of 132kv GIS Fig.9 Transient voltage waveform during second re-strikes for 10mts length in a A-phase of 132kv GIS 17

VI. REFERENCES: Fig.10 Transient voltage waveform during second re-strikes for 10mts length in a B-phase of 132kv GIS TABLE III THE ANALYSIS VALUES ARE TABULATED AS FOLLOWS: Mode of operation During closing operation During opening operation During second re-strike Magnitude of voltages VR phase VY phase Rise time (Nano sec) tr ty 2.43 2.44 67 69 1.22 1.24 62 64 2.53 2.54 124 122 [1] J. Lewis, B. M. Pryor, C. J. Jones, T. Irwin, Disconnector Operations in Gas Insulated Substations Over voltage Studies and Tests Associated with a 420 kv Installation, CIGRE,Vol. 11, 1988, paper 33.09, pages 1-8 [2] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Analysis and Calculation of very fast transient over voltages in 220kv gas insulated Substation International Journal of Engineering &techsciencevol 2(4) 2011 [3] M.kondalu,, Dr. P.S. subramanyam Calculation of Transients at Different Distances in a single phase 220kv Gas Insulated substation published in International journal of Advanced Research in Computer Engineering & Technology Issue4-Volume1pages 28-33 June-2012 [4] H. Hiesinger,RWitzmann. Very fast Transient Breakdown at a needle Shaped Protrusion, IX Int. Conf. on Gas Dis. and Their Appli. Sep 1988. [5] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Estimation Transient overvoltages in gas insulated bus duct from 220kv gas insulated substation, International journal of Computer applications, (0975-8887) volume 20-no.8 april 2011. [6] S. Nishiwaki, Y. Kanno, S. Sato, E. Haginomori, S. Yamashita, and S. Yanabu, Ground Fault by Re-striking Surge of SF6 Gas insulated Disconnecting Switch and Its Synthetic Tests, Transactions on Power Apparatus and Systems, vol. PAS-102, No. 1, pp. 219-227, 1983. [7] N. Fujimoto and S. A. Boggs, Characteristics of GIS Disconnector-induced Short Rise time Transients Incident on Externally Connected Power System Components, IEEE 87 WM 185-2,New Orleans, Feb. 1987. [8] W. Boeck and W. Taschner, Insulating Behavior of SF6 with and without Solid Insulation in Case of Fast Transients, CIGRE Paper No.1547, Aug. 1986. Transactions on Power Systems, vol. PWRD- 1, No. 2, pp. 95-101, 1983. [9] R. Witzman, Fast Transients in Gas Insulated Substations (GIS) Modeling Of Different GIS Components, Fifth International Symposium on High Voltage Engineering, No. 12.06, 1987. V. CONCLUSION The fast transient over voltages are obtained due to switching operation of 3-phase to 2-phase faults are studied. The transients are calculated initially with fixed arc resistance and then variable arc resistance. The variable arc resistance is calculated by using Toepler s formulae. Transients along with load and without load are also estimated. The peak magnitude of fast transient currents are generated during switching event changes from one position to another in a 3-Phaseto 2-phase from 132kv Gas insulated substations for a particular switching operation. These transients over voltages are reduced by connecting suitable resistor in an equivalent circuit during closing and opening operation. 18