Standardized Measurements for Elevated NEV and Energized Object Concerns Doug Dorr, Charles Perry, Mark McGranaghan Arindam Maitra, Wes Sunderman

Similar documents
EPRI Contact Voltage R&D Program Update Doug Dorr EPRI

Stray Voltage and Swimming Pools

Grounding for Power Quality

Education & Training

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

IEEE WORKING GROUP ON VOLTAGES AT PUBLICLY AND PRIVATELY ACCESSIBLE LOCATIONS. Web Cast May 17, 2007

ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS

NON-TRADITIONAL STRAY VOLTAGE: AS LEARNED IN THE FIELD

Contact Voltage Detection

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

AC Voltage- Pipeline Safety and Corrosion MEA 2015

Stray Electricity. Occurs as small voltage differences between

Technique for Accurate Voltage Measurement of Energized Street Level Objects

AC INTERFERENCE OF TRANSMISSION LINES ON RAILWAYS: INFLUENCE OF TRACK-CONNECTED EQUIPMENT I. ABSTRACT

Exhibit DD Specific Standards for Transmission Lines. Boardman to Hemingway Transmission Line Project

Reliability and Power Quality Indices for Premium Power Contracts

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Harmonic Distortion Levels Measured at The Enmax Substations

OVERVIEW OF IEEE STD GUIDE FOR VOLTAGE SAG INDICES

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

ECE 528 Understanding Power Quality

Industrial and Commercial Power Systems Topic 7 EARTHING

EPR Safety Mat Modelling & Field Testing Summary Report

Power Quality, Earthing And Bonding Oct $4,250 Dubai, UAE. In any of the 5 star hotels. The exact venue will be informed once finalized.

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

The Confusion Surrounding Stray Voltage

American Electrical Institute

Roadmap For Power Quality Standards Development

Power System Neutral/Ground Voltages Causes, Safety Concerns and Mitigation

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Grounding Recommendations for On Site Power Systems

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Upgrading Your Electrical Distribution System To Resistance Grounding

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Article 250 Grounding & Bonding

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

IEEE WORKING GROUP ON VOLTAGES AT PUBLICLY AND PRIVATELY ACCESSIBLE LOCATIONS. Web Cast November 30, 2006

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Harmonic Filters for Single Phase Equipment

Intermediate Frequency Electric and Magnetic Emissions Testing

UNIT-4 POWER QUALITY MONITORING

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

EN50160 Individual Report Summary

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

EPG. by Chris C. Kleronomos

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Safe Engineering Services & technologies ltd.

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

SECTION 5 TRANSFORMERS

MS2030 CAT III 600 V A V AUTO RS232

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

A PARAMETRIC ANALYSIS OF AC INTERFERENCE CAUSED BY HIGH VOLTAGE POWER LINES ON NEIGHBORING RAILROAD TRACKS

Earthing of Electrical Devices and Safety

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

1. Introduction to Power Quality

B perpendicular to plane of loop

I. Introduction to Animal Sensitivity and Response

Appendix 6-F: Electric and Magnetic Field Study Report

Harmonic control devices. ECE 528 Understanding Power Quality

What Are We Protecting? Over-Voltage Protection for CP Systems. Personnel (primary) Equipment (secondary)

Novel Simulation Method to Quantify Induced Voltage & Current between Parallel or Partially Parallel Proximity AC Transmission Circuits

PQ Monitoring Standards

POWER QUALITY AND SAFETY

Monitoring DC Decoupling Devices at Isolation Flanges for Compliance and Pipeline Integrity

Power Quality Starts At the Load

QUESTIONNAIRE ON FAULT LOCATION SYSTEMS

Article information: Access to this document was granted through an Emerald subscription provided by Emerald Author Access

Environmental Exposures to ELF Georg Neubauer

Fencing Options. Properly installed corner brace assemblies are the cornerstone of any fence. Fences with. A Horizontal brace (compression member)

CS101. Conducted Susceptibility CS101. CS101 Maximum Current. CS101 Limits. Basis For CS101 Limits. Comparison To MIL-STD Vdc or Less

Guide for Conducting a Stray Voltage Evaluation Under the MPSC Stray Voltage Rule 1

The Many Uses of Transmission Line Arresters

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

High Voltage Pylon Earth Measurements


CONTINUING EDUC ATION

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Technical Brief: Flow Direction of Harmonics and High- order Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Power Quality Evaluation of Electrical Distribution Networks

New Methods to Mitigate Distribution System Harmonics

Review of Electrical Noise on 120/240 volt Power Systems. Dec 12,

AC Magnetic Field Survey Report

T-68 Protecting Your Equipment through Power Quality Solutions

Summary of the Impacts of Grounding on System Protection

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

DEPARTMENT OF DEFENSE HANDBOOK

User's Guide. AC Circuit Load Tester. Model CT70

Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

Emicon Engineering Consultants L.L.C.

Short Circuit Current Calculations

Transcription:

Standardized Measurements for Elevated NEV and Energized Object Concerns Doug Dorr, Charles Perry, Mark McGranaghan Arindam Maitra, Wes Sunderman Doug Dorr EPRI Solutions Inc. ddorr@eprisolutions.com 407-968-3010 IEEE T&D Conference May 24th 2006 1

Presentation Summary Brief overview of past and present EPRI experiences related to contact voltages Brief overview of the 2005-2009 EPRI Stray Voltage Strategic Roadmap Some items where definitions will help support measurement protocols A few supporting examples of induced voltages and harmonic NEV that demonstrate the need for an IEEE guide that focuses at least in part on standardized measurement protocols Suggestions on Future Stray Voltage Work 2

Questions and Concerns Fielded by the EPRI Solutions Power Quality Hotline 1994-2006 Personnel safety concerns related to touch potentials Animal contact area concerns related to health and productivity impacts Residential water and gas pipe shocking concerns Harmonic frequency voltages imposed on industrial gas lines Power circuit resonance conditions creating elevated NEV levels Shocking concerns with boat docks Insulated metallic pipe corrosion concerns Impacts of power line carrier communications technologies and other transient generating devices at contact locations Impacts of new gas and water line installations in power line right of ways Induced voltages onto fences and light poles Tingling sensations at swimming pools and outdoor water faucets Different opinions on measurement equipment specifications, measurement protocols and measurement durations 3

EPRI Stray Voltage Research Roadmap The prioritized research plan identified five areas of opportunity where supplemental or new research was needed: Test and measurement protocols Modeling and simulation guidelines Test equipment and mitigation methods Technology transfer Informational website Regulatory guidance (NEV and MOEV baselines and what voltage levels are not a concern) 4

EPRI Program 128 Base Research Project Objectives and Solutions EPRIs present industry support plans related to elevated neutral to earth voltage and metallic object to earth voltage concerns 2005 Informational website, measurement protocols 2006 Develop distribution system modeling and simulation guidelines 2007 Testing on mitigation and measurement devices and perform survey of NEV levels on distribution systems 2008 09 Regulatory informational support, design best practices and other R&D as directed by the project sponsors 5

Some Examples of Past EPRI Research The subject is not new.. in fact research into suspected animal contact impacts go back to the 1940 s and the range of issues cover the spectrum for current effects to advance mitigation strategies EPRI TR 114340 Stray Voltage Sensitivity Levels for Dairy Cattle, Swine, and Poultry Document Resolving Residential Pool Shocking Concerns EPRI EL-3106 V1, V2, V3, V4 This report series addresses complex common corridor coupling problems for overhead electric power transmission lines and buried natural gas pipelines Modeling and simulation results on the impact of automated meter reading technologies at animal contact points Dozens of field investigations involving dairy farms, gas pipelines, swimming pools, hot tubs and other stray voltage sources Distribution wide NEV assessment modeling EPRI 1010652 Neutral to Earth Voltage and Urban Stray Voltage Measurement Protocols: Test Equipment and Procedures Five wire distribution demonstration project in upstate NY 6

Example of Coupling to a Pipeline EL-3106 Source: EPRI EL-3106 7

Example Trending Correlation of Circuit Currents (yellow/pink) to NEV (green) Distribution System Current Levels Versus "Pipeline to Earth" Voltage Levels at Gas Meter 450 14 400 A Phase C Phase NEV 12 350 300 10 Current (amps) 250 200 8 6 NEV (RMS volts) 150 4 100 50 2 Figure Source: EPRI Solutions Inc. all rights reserved 0 0 11/17/2005 0:00 11/18/2005 0:00 11/19/2005 0:00 11/20/2005 0:00 11/21/2005 0:00 11/22/2005 0:00 11/23/2005 0:00 11/24/2005 0:00 Date/Time 8

Example of Harmonic NEV Concerns The primary objectives of the EPRI research was to better understand the means of reducing neutral-toremote earth voltage (NEV) levels on the primary power distribution circuits The results of the modeling efforts enable a better understanding of the methods and software programs that can be used to reduce NEV levels at customer connection points The results allow for simultaneous estimates of the NEV levels that at different points along distribution circuits This also provides a way to compare solutions form both a cost and a relative improvement perspective 9

Harmonic NEV is not new either. Conrad et. al. assessed the problems 10 years ago! Balanced Three Phase I I I I A B C N = I = I = I = I a b c A sin( ωt) sin( ωt 120 sin( ωt + 120 + I B + I C ) ) = 0 Circuit Balanced Circuit with Single Phase Loads I I I I 3rdA 3rdB 3rdC 3rdN = = = I I = I 3rda I 3rdb 3rdc 3rdA sin(3ω t) [ ωt 120 )] [ ωt + 120 )] sin 3( sin 3( + I 3rdB + I 3rdC = 3* I 3rda sin(3ω t) Source: L. Conrad et. al., Electric Shock and Elevated EMF Levels Due to Triplen Harmonics IEEE Transactions on Power Delivery, Volume 11, No. 2, April 1996 10

Modeling and Simulation What parameters were varied or evaluated in the models? Neutral conductors Grounding Resistance of the substation grid Resistance of the circuit pole ground Capacitor Banks Grounded versus ungrounded Circuit Loading Winter loading vs summer loading Harmonic filter configurations 11

NEV Mitigation Priorities Individual Customer Bonding/Grounding/Isolation Load Balancing (10 percent? 5 percent?) Neutral Impedance Assessment Harmonic Resonance Assessment Ungrounded Capacitors Tuned Harmonic Filters Neutral Impedance Reduction Grounding Assessment Earth Resistivity? Average Ground Rod Resistance Aggregate Services and Customer Ground Resistance Substation Ground Grid Resistance 12

Generic NEV (and MOEV) Evaluation Priorities Adequate call handling and response procedures Safe and accurate measurement protocols Adequate instrumentation and personnel training Consistent documentation for reporting and analysis Understanding of all the possible causes A procedure for peeling the onion start with all possibilities and systematically narrowing down the list Preventive maintenance and spot monitoring Design guidelines 13

Measurement Protocols Much of the work in the area of diagnosing and resolving undesirable contact voltage potentials requires accurate and repeatable measurement protocols The IEEE WG on Stray Voltage has an opportunity to assist the industry in this area The protocol is not simply a three page spreadsheet to fill in the blanks Considerations range from training personnel to selecting the correct, equipment for the task at hand, and implementing the proper measurement and documentation procedures 14

Measurement Protocols If done properly, a consistent and repeatable measurement protocol should answer a lot of the questions that may arise during an investigation Why did the voltage I measured last week disappear? What is the source of the elevated contact voltage? Why did the voltage go away when I measured with a resistance in the circuit? Why do I get different readings with two different instruments? Why does the selected reference point change my voltage reading? 15

Test and Measurement Equipment 16

Measurement Section Should Focus on Recommended Practice Figure source: IEEE Std 1100 2006 Recommended Practice on Powering and Grounding Electronic Equipment 17

Measurement Section Should Detail the Equipment and Other Considerations used in the Assessment Use of trending versus snapshot for time of days and source correlations Harmonics and the importance of understanding the spectral content of the NEV Pen Lights Hand Held Meters Data Loggers Multi Channel Recorders 18

Measurement Objectives 19

Procedures may require different actions based on the levels measured Source: Neutral to Earth Voltage and Urban Stray Voltage Measurement Protocols: Test Equipment and Procedures. EPRI, Palo Alto, CA: 2005. 1010652 20

Procedures should include grounding and bonding assessments 21

Procedures may have some differences when unintentional energization occurs 22

Equipment and Step by Step and Procedures Source: Neutral to Earth Voltage and Urban Stray Voltage Measurement Protocols: Test Equipment and Procedures. EPRI, Palo Alto, CA: 2005. 1010652 23

Equipment Calibrations Chapter Concept: Develop a simple means of checking your equipment and documenting it s accuracy before doing any for the record testing 24

Final Comments IEEE Stray Voltage Working Group is in a position to assist the industry with: Measurement procedures and guidelines that result in accurate repeatable results Information on equipment specifications, calibration procedures, and measurement point connection and reference consideration to promote correct measurements Case studies and examples that promote application of optimized mitigation techniques when necessary 25