Motor Protection. May 31, Tom Ernst GE Grid Solutions

Similar documents
Application Note. GE Grid Solutions. Multilin 8 Series 869 Broken Rotor Bar Detection. Introduction

System Protection and Control Subcommittee

Overcurrent and Overload Protection of AC Machines and Power Transformers

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE

GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1. Modified_103007

Transformer Protection

ISSN: Page 298

Transformer Fault Categories

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual

Generator Advanced Concepts

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Transformer Protection Principles

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Protective Relays Digitrip 3000

Improving Transformer Protection

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

WDG 12 - Technical Data Sheet

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

440 (12) 416 (12) 416 (12) 440 (12)

WDG 71 - Technical Data Sheet

WDG 12 - Technical Data Sheet

Generator Protection GENERATOR CONTROL AND PROTECTION

WDG 51 - Technical Data Sheet

WDG 61 - Technical Data Sheet

WDG 13 - Technical Data Sheet

Deploying Current Transformers in Applications Greater Than 200 A

WDG 07 - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

Substation applications

Spec Information. Reactances Per Unit Ohms

WDG 83 - Technical Data Sheet

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

1 INTRODUCTION ORDER CODE / INFORMATION

Preface...x Chapter 1 Electrical Fundamentals

Spec Information. Reactances Per Unit Ohms

Relaying 101. by: Tom Ernst GE Grid Solutions

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

Transformer Protection

GENERATOR DATA JANUARY 30, 2015

PD300. Transformer, generator and motor protection Data sheet

Application Note. GE Grid Solutions. Multilin 8 Series Applying Electrical Signature Analysis in 869 for Motor M&D. Overview.

ALTERNATOR TECHNICAL DESCRIPTION 1. LSA 53.2 XL13 / 4p. Chargé d'affaire : Karthikeyan GN 1 Moteurs Leroy-Somer +33 (0) xx

889 Advanced Generator Protection Technical Note

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

Impact of Incipient Faults on Sensitive Protection

Class 300 Equipment CBS 305, 320 Current Boost Systems FEATURES. DESCRIPTION Page 2. SPECIFICATIONS Pages 2 through 4.

S4L1D-G41 Wdg Technical Data Sheet

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

S4L1S-D4 Wdg.17 - Technical Data Sheet

COPYRIGHTED MATERIAL. Index

Protection Introduction

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

Beyond the Knee Point: A Practical Guide to CT Saturation

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

System Protection and Control Subcommittee

Time constants ( s ) Resistance. Other data - Class H /6600 V kva. Efficiencies ( % )(3 phase - Classe H V kva)

Testing Power Sources for Stability

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Application of Electrical Signature Analysis. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

AV-300i Specifications. Saftronics Inc. PC10 Product Specifications PC10. Mini Vector AC Drive

ES-777-MV-P2_A1 03/01/10

Short-Circuit Current Calculations

www. ElectricalPartManuals. com Type CGR Ratio Ground Relay Descriptive Bulletin Page 1

Distance Element Performance Under Conditions of CT Saturation

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT

PROTECTION of electricity distribution networks

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Differential Protection with REF 542plus Feeder Terminal

MM200 Motor Management System

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT

GS1 Parameter Summary Detailed Parameter Listings...4 9

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT

Detecting and Managing Geomagnetically Induced Currents With Relays

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Time-current Coordination

PROTECTION SySTEM Integrated protection and control for medium sized AC motors

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

S0L1-J1 - Technical Data Sheet

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

PI734C - Technical Data Sheet

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Multimeter 500CVD21 RTU500 series

Transcription:

Motor Protection May 31, 2017 Tom Ernst GE Grid Solutions

Motor Relay Zone of Protection -Electrical Faults -Abnormal Conditions -Thermal Overloads -Mechanical Failure 2

Setting of the motor protection relay is based on the motor datasheets information and system configuration Datasheets are normally provided by motor manufacturer System configuration data can be obtained from single line diagram 3

CT Selection 869 4

Phase CTs The CT should be nominally sized at or greater than motor FLA The CT must have an accuracy class high enough so that the current waveform presented to the relay will allow the overcurrent to operate Higher CT ratio is generally better from a saturation point of view than a lower CT ratio 5

Phase CTs Our Motor has a FLA of 413 Amps Our maximum fault current is 22KA 6

Phase CTs C100 400/5 INPUT PARAMETERS: ENTER: Saturation Curve CALCULATED: Inverse of sat. curve slope = S = 16 --- V Rt = Total burden resistance = Rw + Rb = 0.295 s RMS voltage at 10A exc. current = Vs = 125 volts rms slope pf = Total burden pow er factor = 1.000 Turns ratio = n2/1= N = 80 --- = 1/S Zb = Total burden impedance = 0.295 mf gr's Winding resistance = Rw = 0.195 ohms V Tau1 = System time constant = 0.027 Burden resistance = Rb = 0.100 ohms e data Lamsat = Peak flux-linkages corresponding to Vs 0.469 Burden reactance = Xb = 0.004 ohms volts log-log plot, w = Radian freq = 376.99 System X/R ratio = XoverR = 10.0 --- rms equal RP = Rms-to-peak ratio = 0.37410 Per unit offset in primary current = Off = 1.00-1<Off<1 decade A = Coefficient in instantaneous ie spacing Per unit remanence (based on Vs) = lrem 0.00 --- versus lambda curve: ie = A * l^s : 4.89E+06 Symmetrical primary fault current = Ip = 22,000 amps rms dt = Time step = 0.000083 I e amps rms 10 Lb = Burden inductance = 0.00001 800 600 400 200 0-200 -400 Thick lines: Ideal (blue) and actual (black) secondary current in amps vs time in seconds. Thin lines: Ideal (blue) and actual (black) secondary current extracted fundamental rms value, using a simple DFT with a one-cycle window. -600-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150 Saturated Magnitude Trace 7

Phase CTs C100 600/5 INPUT PARAMETERS: ENTER: Saturation Curve CALCULATED: Inverse of sat. curve slope = S = 16 --- V Rt = Total burden resistance = Rw + Rb = 0.300 s RMS voltage at 10A exc. current = Vs = 125 volts rms slope pf = Total burden pow er factor = 1.000 Turns ratio = n2/1= N = 120 --- = 1/S Zb = Total burden impedance = 0.300 mf gr's Winding resistance = Rw = 0.200 ohms V Tau1 = System time constant = 0.027 Burden resistance = Rb = 0.100 ohms e data Lamsat = Peak flux-linkages corresponding to Vs 0.469 Burden reactance = Xb = 0.004 ohms volts log-log plot, w = Radian freq = 376.99 System X/R ratio = XoverR = 10.0 --- rms equal RP = Rms-to-peak ratio = 0.37410 Per unit offset in primary current = Off = 1.00-1<Off<1 decade A = Coefficient in instantaneous ie spacing Per unit remanence (based on Vs) = lrem 0.00 --- versus lambda curve: ie = A * l^s : 4.89E+06 Symmetrical primary fault current = Ip = 22,000 amps rms dt = Time step = 0.000083 I e amps rms 10 Lb = Burden inductance = 0.00001 500 400 300 200 100 0-100 -200 Thick lines: Ideal (blue) and actual (black) secondary current in amps vs time in seconds. Thin lines: Ideal (blue) and actual (black) secondary current extracted fundamental rms value, using a simple DFT with a one-cycle window. -300-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150 Increase the ratio - less saturation 8

Phase CTs C200 600/5 INPUT PARAMETERS: ENTER: Saturation Curve CALCULATED: Inverse of sat. curve slope = S = 16 --- V Rt = Total burden resistance = Rw + Rb = 0.300 s RMS voltage at 10A exc. current = Vs = 300 volts rms slope pf = Total burden pow er factor = 1.000 Turns ratio = n2/1= N = 120 --- = 1/S Zb = Total burden impedance = 0.300 mf gr's Winding resistance = Rw = 0.200 ohms V Tau1 = System time constant = 0.027 Burden resistance = Rb = 0.100 ohms e data Lamsat = Peak flux-linkages corresponding to Vs 1.125 Burden reactance = Xb = 0.004 ohms volts log-log plot, w = Radian freq = 376.99 System X/R ratio = XoverR = 10.0 --- rms equal RP = Rms-to-peak ratio = 0.37410 Per unit offset in primary current = Off = 1.00-1<Off<1 decade A = Coefficient in instantaneous ie spacing Per unit remanence (based on Vs) = lrem 0.00 --- versus lambda curve: ie = A * l^s : 4.04E+00 Symmetrical primary fault current = Ip = 22,000 amps rms dt = Time step = 0.000083 I e amps rms 10 Lb = Burden inductance = 0.00001 Thick lines: Ideal (blue) and actual (black) secondary current in amps vs time in seconds. Thin lines: Ideal (blue) and actual (black) secondary current extracted fundamental rms value, using a simple DFT with a one-cycle window. 500 400 300 200 100 0-100 -200-300 -0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150 Increase ratio & C-rating almost no Saturation 9

Motor Data Sheets Motor Performance Data Thermal Limit Curves 10

Motor Thermal Limit Curves Thermal Limit Curves: B A D C A. Cold Running Overload B. Hot Running Overload C. Cold Locked Rotor Curve D. Hot Locked Rotor Curve E F E. Acceleration curve @ 80% rated voltage F. Acceleration curve @100% voltage 11

Motor Thermal Parameters G I H J Motor Data Sheet Parameters G. Temperature Rise, Insulation Class H. Full Load Current I. Locked Rotor Current J. Locked Rotor Time; Cold/Hot K. Number of Starts per hour; K 12

Motor Specifications Information required to set Thermal Model: Motor FLA Locked rotor current Locked rotor time hot & cold Stopped & running cool time constants Service factor Motor thermal damage curves 13

Settings Example Select CT Rating, Voltage Sensing Voltage Sensing : Enter the connection type, secondary volts and ratio. VTratio = 14400/120 = 120:1 Vsec = Vnom/VTratio = 13800/120 = 115 V Phase CT: The phase CT should be chosen such that the FLA is 75% to 150% of CT primary. Since the FLA is 297 a 300:5 CT may be chosen. Ground CT: Zero sequence core balance CT is used for high impedance grounded systems. The primary rating should be large enough to assure that the CT can handle all potential fault ground levels without saturating. 50 A >> systems with less than 50 amps of ground fault current. 200 A or 300 A >> systems with up to 300 amps of ground fault current. No ground CT required on low impedance or solidly grounded systems (Use neutral functions (3I0 is calculated from the phase CTs). Secondary rating can be same as phase CTs (1A/5A) or special 50:0.025 A. 14

Settings Example Select FLA, Ground CT Motor FLA: Set as specified by the data sheets. Overload Factor: This is the pickup of the OL curve. Set 10-15% above data sheet service factor. NP Voltage, HP & Poles: Set as specified in the data sheets. Load Average Calc. Period: Set this longer than the oscillatory duration of oscillating loads like reciprocal compressors. Set at 0 for non-oscillatory loads. Max Acceleration Time: Set this to the longest acceleration time expected plus a margin (the acceleration time trip function is enabled separately - see Protection > Group X >> Motor). 15

Settings Example Select Overload Curve for Thermal Model Overload Curve Set the overload curve below cold thermal limit and above hot thermal limit. If only hot curve is provided by manufacturer, then must set at or below hot thermal limit The best fitting curve is time dial multiplier 9 in this example. Note that this is a 3 dimensional curve: f(a,t, TCU), TCU = thermal capacity used. Curve values given are for TCU = 0 (40 C stator temp). The curve represents TCU = 100%. 16

Settings Example Select Overload Curve TD Multiplier for Thermal Model Overload Curve Set the overload curve TD multiplier below cold thermal limit and above hot thermal limit. If only hot curve is provided by mfgr, then must set at or below hot thermal limit. The best fitting curve TD multiplier is 9 in this example. This can be verified with Hot Stall Time of 30s at 540% FLA by using the standard overload curve equation above. 17

Settings Example Select Overload Curve for Thermal Model Select overload curve using Hot Stall Time and Locked Rotor Current when Overload Curves are not available: Example: For Hot Stall Time = 30s and LRA = 540% FLA Substitute in the above equation: 30s = TD MULTIPLIER x 2.2116623 (0.02530337 x 4.4 2 + 0.05054758 x 4.4) TD MULTIPLER = 30 x (0.02530337 x 4.4 2 + 0.05054758 x 4.4) 2.2116623 point) = 9.66 SELECT TDM 9 (which is below this intersection 18

Settings Example Determine Unbalance Bias K Factor for Thermal Model Unbalance Bias Of Thermal Capacity Enable the Unbalance Bias of Thermal Capacity so that the heating effect of unbalance currents is added to the Thermal Capacity Used. K=175/LRA 2 = 175/ 5.4 2 = 6 (Typical) K=230/LRA 2 = 230/ 5.4 2 = 8 (Conservative) 19

Settings Example Stopped & Running Cool Time Constants Stopped and Running Cool Time Constants This information is usually supplied by the motor manufacturer but is not part of the data that was given with this motor. If RTD s are present and will be wired to the relay biasing of the thermal model will be used so it is not critical to have these cooling times from the manufacturer: the default values of 15 and 30 minutes can be used for the running and stopped cool times respectively. 20

Settings Example Determine Hot/Cold Safe Stall Ratio for Thermal Model (method 1) HCR LRT LRT HOT COLD Hot/Cold Ratio = 30/35 = 0.86 Hot/Cold Curve Ratio The hot/cold curve ratio is calculated by simply dividing the hot safe stall time by the cold safe stall time or use the motor thermal limits curve. For this example, both are available. Using the data sheets the Hot/Cold Curve Ratio equals 30 / 35 = 0.86 21

Settings Example Determine Hot/Cold Safe Stall Ratio for Thermal Model (method 2) Overload Curve Method Hot/Cold Curve Ratio If the thermal limits curves are being used to determine the HOT/COLD ratio proceed as follows: LRC = 5.4FLA LRTcold = 8sec LRThot = 6sec From the thermal limits curves run a line perpendicular to the current axis that intersects the hot and cold curves at the stall point Draw lines from each points of intersection to the time axis. Record the corresponding times. In this case, 6 and 8 seconds respectively. The Hot/cold ratio can now be calculated as follows: = 6s/8s = 0.75 NOTE: If hot and cold times are not provided and only one curve is given verify with the manufacturer that it is the hot curve ( which is the worst case), then the Hot/ Cold ratio should be set to 1.0 22

Settings Example Determine RTD Bias Setpoints for Thermal Model Enable RTD Biasing This will enable the temperature from the Stator RTD sensors, to be included in the calculations of Thermal Capacity. RTD bias model determines the Thermal Capacity Used based on the temperature of the Stator and is separate from the overload model for calculating Thermal Capacity Used. RTD biasing is a back up protection element which accounts for such things as loss of cooling or unusually high ambient temperature. This measured temperature is used to bias or modify the thermal capacity value stored in the motor relay. 23

Settings Example Determine RTD Bias Setpoints for Thermal Model MID POINT TEMP: 130 C TCU: 25% MIN POINT TEMP: 40 C TCU: 0% MAX POINT TEMP: 155 C TCU: 100% Motor relay will use the calculated thermal capacity unless the RTD thermal capacity is higher. This feature will not trip the motor at the max point temp unless the average current is greater than the overload pickup setting RTD Bias Function Set to Enabled/YES RTD Bias Minimum Set to 40 C which is the ambient temperature obtained from the data sheets. RTD Bias Center Point The center point temperature is set to the motor s hot running temperature and is calculated as follows: Temperature Rise of Stator + Ambient Temperature. The temperature rise of the stator is 80 C + 10% hot spot allowance, obtained from the data sheets. Therefore, the RTD Center point temperature is set to 90 0 C + 40 0 C or 130 C. RTD Bias Maximum This setpoint is set to the rating of the insulation or slightly less. A class F insulation is used in this motor which is rated at 155 C, so setting should be 155 C. 24

Settings Example Determine RTD Bias Setpoints for Thermal Model MAX POINT TEMP: 155 C TCU: 100% MID POINT TEMP: 130 C TCU: 25% MIN POINT TEMP: 40 C TCU: 0% 25

Settings Example Enable Start Inhibit Enable Start Inhibit This function will limit starts when the motor is already hot. The motor relay learns the amount of thermal capacity used at start. If the motor is hot, thus having some thermal capacity used, the relay will not allow a start if the available thermal capacity is less than the required thermal capacity for a start. If Start Inhibit is not used, must wait until Thermal Capacity Used (TCU) falls below 15% before the motor can be re-started. Using Start Inhibit allows one to start a motor sooner. 26

TCU / Start Inhibit Example Thermal Capacity required to start For example, if the THERMAL CAPACITY USED for the last 5 starts is 24, 23, 27, 25, and 21% respectively, the LEARNED STARTING CAPACITY is 27% 1.25 = 33.75% used. Thermal Capacity used due to Overload If the motor had been running in an overload condition prior to stopping, the thermal capacity would be some value; say 80%. If Motor is Stopped: When the motor has cooled and the level of thermal capacity used has fallen to 66%, a start will be permitted. 27

Settings Example Starts/Hr, Time Between Starts Starts/Hour Starts/Hour can be set to the # of cold starts as per the data sheet. For this example, it is 2 Time Between Starts In some cases, the motor manufacturer will specify the time between motor starts. In this example, this information is not given so this feature can be disabled or set at a typical 20 min between starts. 28

Settings Example VFD Support Functions Bypass Switch If the VFD has a bypass switch then set this for the contact input that is ON when the switch is closed. Starting Frequency Traditionally, the frequency tracking function started at 50/60 Hz and then looked at zero crossings of several cycles to determine the correct actual frequency. This caused the first 5 10 cycles of current measurement to be wrong when the motor was started from a VFD. Starting frequency feature allows the tracking to start at a more realistic frequency (6 Hz in this case). 29

Advanced Diagnostics Broken Rotor Bar Detection The Broken Rotor Bar element uses two different algorithms to detect broken or cracked rotor bars: Power Based Coherent Demodulation: This technique uses multiplication of voltage and current samples thereby shifting the fundamental to DC and fault frequency to lower closer to DC value, to detect the broken rotor bar component. This method is running when voltage is available and is meeting MOTOR VOLTAGE SUPERVISION setting check. Conventional current based FFT method: In case voltage is not available or the voltage magnitude is lower than the MOTOR VOLTAGE SUPERVISION setting value, the algorithm switches to analyzing the frequency spectrum from current samples only, to detect the broken rotor bar component. Alarm settings are based on an increase in db as each motor will exhibit a different signature when healthy. 30

Advanced Diagnostics - BRB FFT of Stator Current of Induction Machine with Rotor Bar Fault signature is only about 12 Hz off of fundamental The FFT of the resultant multiplied signal more robust signature than with the current only FFT method signal. 31

Advanced Diagnostics BRB Pickup is set based on initial in-service db measurements taken when the motor is known to be healthy plus a change margin (~15% increase). 32

Advanced Diagnostics Stator Inter-Turn Fault The Stator Inter-Turn Fault element uses sequence components to detect stator turn failure of the induction machine. Local heating caused by shorted turns can rapidly cause additional damage to adjacent windings and stator iron Alarm to avoid additional damage Normalized cross-coupled impedance ratio: Z np /Z pp = (V 2 Z nn *I 2 )/V 1 ~ 0 under balanced non-fault conditions Z pp = positive sequence impedance Z np = cross-coupled negative-to-positive sequence impedance V 1 = positive sequence voltage (motor terminals) V 2 = negative sequence voltage (motor terminals) I 2 = negative sequence current (motor terminals) Z nn = negative sequence impedance 33

Advanced Diagnostics Stator Inter-Turn Fault Operating quantity: OP = Z np /Z pp Z UBbase Z UBbase = normalized cross-coupled impedance ratio under non-fault conditions 34

Thank You Questions?