ENERGY SAVINGS WITH VARIABLE SPEED DRIVES ABSTRACT. K M Pauwels. Energy auditor, Laborelec, Industrial Applications, Belgium

Similar documents
High Voltage DC Transmission 2

IGBT Induction Heater Profiles

Open-Delta Systems Affect Variable Frequency Drives

How adjustable speed drives affect power distribution

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Voltage Source Converter Modelling

VARIABLE FREQUENCY DRIVE

Active Harmonic Filter (AF3)

A New Concept of Power Quality Monitoring

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

VSD cables in. Working with. industrial & automation applications

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

SHUNT ACTIVE POWER FILTER

Distributed Energy Engineering

Reliable power onboard and offshore

VFDs and Harmonics in HVAC Applications

MV VFD Discussion MIA Detroit 2016

DQ-58 C78 QUESTION RÉPONSE. Date : 7 février 2007

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

POWER- SWITCHING CONVERTERS Medium and High Power

Development of a Single-Phase PWM AC Controller

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Low Pass Harmonic Filters

Improving Passive Filter Compensation Performance With Active Techniques

Australian Journal of Basic and Applied Sciences. Design of a Half Bridge AC AC Series Resonant Converter for Domestic Application

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Pumping of clear unfilled liquids in housing, agricultural and industrial sectors.

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Evaluation of transformer-free UPS design vs transformer-based

Reduce harmonics in HVAC&R inverters through C-Less technology

Reliability of the Impact- Echo Method on Thickness Measurement of Concrete Elements

Nicolò Antonante Kristian Bergaplass Mumba Collins

Matrix Drives Boost Power Quality and Energy Savings

Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations

McGill Power Sales & Engineering, INC.

VF-nC1 Adjustable Speed Drive Engineering Specification

VARIABLE FREQUENCY DRIVE

Power Electronics. Contents

Vacon Baltic Days Tallinn, Estonia

Research Article International Journals of Advanced Research in Computer Science and Software Engineering ISSN: X (Volume-7, Issue-6)

Economical Solutions to Meet Harmonic Distortion Limits[4]

Thyristorised Automatic Power Factor

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

Dr.Arkan A.Hussein Power Electronics Fourth Class. 3-Phase Voltage Source Inverter With Square Wave Output

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

A Series-Resonant Half-Bridge Inverter for Induction-Iron Appliances

Vannes à commande manuelle manually actuated valves

Harmonics White Paper

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

Reducing Total Harmonic Distortion with Variable Frequency Drives

Supplementary questionnaire on the 2011 Population and Housing Census BELGIUM

6. Explain control characteristics of GTO, MCT, SITH with the help of waveforms and circuit diagrams.

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1

ZENER ELECTRIC PTY LTD

TOSHIBA International Corp

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Meduim Voltage Drives

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation

11. Define the term pinch off voltage of MOSFET. (May/June 2012)

Frequently Asked Questions (FAQs) MV1000 Drive

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

CHAPTER 1 INTRODUCTION

LINEATOR. Advanced Universal Harmonic Filter

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

S11 Adjustable Speed Drive Engineering Specification

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Introduction to HVDC VSC HVDC

AN003. Basic Terms Used for DC Power Supplies. Elaborated by: Marco Geri (R&D Manager - NEXTYS SA.)

PowerFlex Medium Voltage Drives with Direct-to-Drive Technology Eliminating the Isolation Transformer

ARDUINO BASED SPWM THREE PHASE FULL BRIDGE INVERTER FOR VARIABLE SPEED DRIVE APPLICATION MUHAMAD AIMAN BIN MUHAMAD AZMI

Medium Voltage Drives in Industrial Applications. By: Navid Zargari & Steven Rizzo Rockwell Automation Cambridge, ON

Power factor correction and harmonic filtering. Harmonic filters and EMI

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

SAMCon High Voltage Shore Connection System On-shore and Onboard

Uninterruptible Power System (UPS) 20 to 320 kva

Modeling of the behavior of power electronic equipment to grid ripple control signal

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Thyristors. In this lecture you will learn the following. Module 4 : Voltage and Power Flow Control. Lecture 18a : HVDC converters.

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter

AC Drive Technology. An Overview for the Converting Industry. Siemens Industry, Inc All rights reserved.

RS232 AC-DC VOLTAGE POWER AMPLIFIERS PCU-10K / 15K / 20K / 24K-AB/4G/HP PERFORMANCES APPLICATIONS DESCRIPTION COMMERCIAL REFERENCES

Thanks for choosing Phyn

Y-0035 POWER ELECTRONICS TRAINING SET

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Auxiliary DC Voltage

Power Quality improvement of a three phase four wire system using UPQC

Mitigating Voltage Sag Using Dynamic Voltage Restorer

POWER ELECTRONICS. Converters, Applications, and Design. NED MOHAN Department of Electrical Engineering University of Minnesota Minneapolis, Minnesota

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Active Rectifier in Microgrid

INDUSTRIAL HEATING. Furnaces North America 98 Heat Treatments Vacuum/Surface Treatments Process Control & Instrumentation Industrial Gases/Energy

Transcription:

ENERGY SAVINGS WITH VARIABLE SPEED DRIVES ABSTRACT K M Pauwels Energy auditor, Laborelec, Industrial Applications, Belgium This paper focuses on the economic benefits that can be obtained by replacing mechanical flow control of pumps and fans with variable speed drives. TECHNOLOGY First, different topologies of variable speed drives are discussed: Rectifier topologies (diode, thyristor, IGBT) Control of invertors by Pulse Width Modulation (PWM). A short overview of the advantages for the different topologies is given. Some restrictions on Variable Speed Drives are briefly mentioned. CASE STUDIES The flow regulation methods are: 1) load/unload regulation, 2) valve regulation, 3) frequency regulation. The 3 regulation methods are compared from an energy efficiency point of view. Depending on the load profile, energy savings up to 41 % can be obtained by applying frequency regulation instead of load/unload regulation. CASE STUDY 3 Case study 3 shows the case of a convertor in a stainless steel factory. Two 8 kw fans blow air into the convertor. The air flow is controlled by a valve. Replacing the valve with a VSD implies a yearly saving of 4.188.277 kwh. The core of the paper consists of three case studies. The case studies are taken from our energy consulting experience in Belgian industry. CASE STUDY 1 Case study 1 discusses VSD installation on the circulation pumps of the electrocoat bath in a car assembly factory. Before, flow was controlled by valve regulation. Installing a variable speed drive generated a yearly saving of 176.4 kwh for one pump. The payback time amounts to approximately 14 months. CASE STUDY 2 Case study 2 explains the economic benefits of VSD on lubricated screw compressors. Measurements on three screw compressors with different flow regulation were effectuated.

ECONOMIES D ENERGIE GRACE A LA VARIATION DE VITESSE - RESUME K M Pauwels Energy auditor, Laborelec, Industrial Applications, Belgium, kenneth.pauwels@laborelec.be Ce résumé est axé sur les avantages économiques qui peuvent être obtenus en remplaçant le contrôle mécanique de débit des pompes ou des ventilateurs par une régulation de vitesse (VSD). TECHNOLOGIE Tout d abord, différentes topologies des régulateurs de vitesse sont examinées: Topologie des redresseurs (diode, thyristor, IGBT) Contrôle des circuits par modulation de largeur ( Pulse Width Modulation, PWM). Un bref aperçu des avantages des différents techniques est donné. De même, certaines limitations des VSD sont mentionnées. CAS 2 Il explique l intérêt économique du VSD sur les compresseurs à vis lubrifiés à l huile. Des mesures sur 3 compresseurs équipés de systèmes de régulation différents ont été réalisées: 1) régulation charge/décharge 2) régulation par vanne 3) régulation de vitesse Les 3 méthodes sont comparées du point de vue rendement énergétique. Suivant le profil de charge, des gains énergétiques allant jusqu à 41 % ont été obtenu avec le VSD par rapport à la régulation charge/décharge. CAS 3 ETUDES DE CAS La base de ce document est constituée de 3 études de cas extraites de notre expérience en consultance énergétique en Belgique. Il expose le cas d un convertisseur dans une usine de production d acier inoxydable. Deux ventilateurs de 8 kw soufflent l air dans le convertisseur. Le remplacement de la vanne par un VSD a entraîné une économie annuelle de 4.188.277 kwh. CAS 1 Il traite de l installation d un VSD sur la pompe de circulation d un bain d electro-coating dans une usine d assemblage de voitures. Avant, le débit était contrôlé par une vanne. Le VSD a rapporté un gain annuel de 176.4 kwh pour une seule pompe. Le retour d investissement est d environ 14 mois.

ENERGY SAVINGS WITH VARIABLE SPEED DRIVES K M Pauwels Energy auditor, Laborelec, Industrial Applications, Belgium SUMMARY TECHNOLOGY This paper focuses on the economic benefits that can be obtained by replacing mechanical flow control of pumps and fans with variable speed drives. Firstly, different topologies of variable speed drives are discussed: rectifier topologies (thyristor, IGBT) as well as the control of invertors with Pulse Width Modulation. A short overview of the advantages for the different topologies is given. The most important restrictions are also mentioned. The core of the paper consists of three case studies, which are taken from our energy consulting experience in Belgian industry. Case study 1 discusses VSD installation on the circulation pumps of the electrocoat bath in a car assembly factory. Before, flow was controlled by valve regulation. Installing a variable speed drive instead generated a yearly saving of 176.4 kwh for one pump. The payback time amounts to approximately 14 months. Case study 2 explains the economic benefits of VSD on lubricated screw compressors. Depending on the load profile, energy savings up to 41 % can be obtained by applying frequency regulation instead of load/unload regulation. Case study 3 shows the case of a convertor in a stainless steel factory. Two 8 kw fans blow air into the convertor. The air flow is controlled by a valve. Replacing the valve with a VSD implies a yearly saving of 4.188.277 kwh. A variable speed drive (VSD) essentially consists of two main parts: rectifier and invertor (fig. 1). Fig. 1 concept of a VSD Rectifier Nowadays, two main topologies are used for medium power rectifier units: diode rectifiers M The rectifying unit consists of a diode bridge. This means that the DC link voltage is fully depending on the AC supply voltage. Some typical characteristics of diode bridges are: - Good power factor: phase shift between voltage and current is very low. - No control needed. - Introduction of line-side harmonics: a diode bridge is a non-linear load. This means that a non-sinusoidal current is taken from the feeding line. Current harmonics cause voltage harmonics. These voltage harmonics can disturb nearby charges. IGBT rectifiers To eliminate the disadvantages of diode (and thyristor) rectifiers, new solutions are developed.

These solutions are all based on the principle that the diode bridge is substituted by an inverter consisting of IGBT components (Fig. 2). IGBT stands for Insulated Gate Bipolar Transistor. Invertors with IGBT rectifiers are called Active Front End (AFE) invertors. Some features of Active Front Ends are: - good power factor, even better then diode rectifier bridge - rectifier is controlled by means of Pulse Width Modulation (PWM) - PWM technology reduces harmonic distortion to a very low level Fig. 3 Pulse Width Modulation RESTRICTIONS In spite of all the advantages, some problems can occur with Variable Speed Drives. The problems are all related to a deteriorated power quality. Production of harmonics Fig. 2 active front end Invertor The invertor uses the DC voltage from the DC bus to create an AC voltage with variable frequency (and amplitude). Nowadays, all invertors are equiped with IGBT (or similar) components. PWM control (Pulse Width Modulation) is widely used for control of the IGBT switches. PWM control consists in rapidly switching on and off the IGBT switches in such a way that pulses with variable width constitute a sinusoidal waveform (Fig. 3). Power electronics always take a distorted current from the feeding line. This causes line-side current harmonics. Some problems that may occur with lineside harmonics are: Harmonics cause supplementary heating in transformers, cables, This fastens the aging process. Nearby capacitor banks can be damaged severely by harmonics. Older types of thyristor control (based on switching at zero voltage) can be disturbed. Next to line-side harmonics, motor-side harmonics are also generated. One of the big problems caused by motor-side harmonics is overvoltage: overvoltage appears due to reflections of the voltage waveform at both ends of the transmission cable. Transmission line theory tells us that matching impedances for all components are required to reduce reflection as much as possible. Sensitivity to voltage dips and short interruptions An invertor basically consists of a rectifying and an inverting unit, linked by a DC-circuit (Fig. 1). In the DC-circuit, the capacitor is the only energy storing element. Even with a big capacity, the stored energy is low.

Example: the stored energy in a 1 mf capacitor (6 V DC) is,1 6 2 2 = 18J =, 5kWh Furthermore, the capacitor in the DC-link is limited to avoid too big inrush currents at switching on. Most important consequence of the low capacity to store energy is the fact that invertors are very sensitive to short interruptions and voltage dips. In the worst case, the control of the VSD simply blocks. Nowadays, a lot of constructors provide different kinds of techniques that improve this weak point. However, none of this solutions guarantees complete protection to short interruptions and voltage dips. CASE STUDY 1: CIRCULATION PUMP Short description (of the original set-up) A car assembly factory paints the body works by means of an electrocoat bath. The paint is attached to the body work by applying a DC voltage to the body work. To maintain temperature and concentration of the paint in the bath, the paint is continuously circulated by pumps, even when there s no production. Flow regulation is effectuated by means of valves.. Measurement results An ultrasonic flow rate measurement (case of valve regulation) revealed a flow rate of 194 m 3 /h. Taking into account the nominal flow rate of 28 m 3 /h, the frequency of the drive needed to be set to 34.8 Hz (nominal frequency = 5 Hz) in order to obtain the required flow rate. In the case of valve regulation, the absorbed power amounts to 36 kw. In the case of frequency regulation, the absorbed power amounts to 15 kw. Gain payback time The pump functions continuously during 5 weeks a year. The use of VSD thus implies a yearly saving of: (36 15)kW x 24 h/d x 7 d/w x 5 w/y = 176.4 kwh/y. For this case, the payback time (investment + installation) amounts to approximately 14 months. Measurements To be able to know the energy saving with Variable Speed Drive, the following parameters have to be measured: 1) flow rate: In order to have a reliable comparison between the two regulation methods, the flow has to be the same in the two cases. 2) Power: for the two regulation methods, the power has to be measured. The measurements were limited to one circulation pump. Characteristics of the pump Nominal power: 45 kw Nominal flow rate: 28 m 3 /h CASE STUDY 2: LUBRICATED SCREW COMPRESSORS Introduction In industry, lubricated screw compressors are widely used. For these compressors, three regulation methods exist: 1) Load/unload regulation Air flow is regulated by opening and closing the inlet vane. During the time that the vane is closed, the motor is running unloaded. 2) Valve regulation Air flow is regulated by a valve that can be put in all positions. 3) Frequency regulation Air flow is regulated by controlling the speed of the electric motor. To compare the energy consumption for the three methods, measurements were carried out.

To do so, three compressors of the same installed power were taken from one constructor, each with a different flow regulation. The power of the compressors is 45 kw. Load profiles Each of the compressors has been tested for three different load profiles: 1) profile A: compressed air consumption all day, even during weekends (fig. 4) 2) profile B: compressed air consumption all day, not during weekends (fig. 5) 3) profile C: compressed air consumption during working hours (5 am to 2 pm), not during weekends (fig. 6) compressed air flow rate (l/s) 12 11 1 9 8 7 6 5 4 3 2 1 Fig. 6 profile C Weekly profile (Sunday to Saturday) These profiles have been simulated by using control valves of different flow rate connected to a compressed air vessel (2 l). The control was made by PLC (fig. 7). compressed air flow rate (l/s) 12 11 1 9 8 7 6 5 4 3 2 1 weekly profile (Sunday to Saturday) Fig. 4 profile A 12 Compressed air flow (l/s) 11 1 9 8 7 6 5 4 3 2 1 Fig. 5 profile B Weekly profile (Sunday to Saturday) Fig.7 picture of the vessel + valves Measurements For each of the three compressors, the three load profiles were simulated during one week. This makes a total measuring time of 9 weeks (3 compressors 3 profiles). The power (1/4 h average) was measured and registered for each of the 9 situations.

Results Measurements Figure 8 gives an overview of the obtained results: Depending on the load profile, a valve regulation gives a saving from 3,9 % up to 8,8 % in comparison with load/unload regulation. The average saving amounts to 8,1 %. Depending on the load profile, a variable speed drive gives a saving from 15,7 % up to 41,1 % in comparison with load/unload regulation. The average saving amounts to 37,2 %. During one week, the position of the valve of 1 fan was registered. The opening of the valve appeared to be 6 % on average. Software simulation Simulation on software (fig. 9) gives a yearly saving of 4.188.277 kwh (for one fan). saving compared to load/unload (%) 45 4 35 3 25 2 15 1 5 41.1 37.2 31.3 15.7 8.8 8.1 7.1 3.9 profile A profile B profile C average valve regulation VSD Taking into account an investment of 15. euro, the payback time amounts to 8 months. Including the estimated installation cost, the payback time comes to 14 months. hours/year 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 kw Fig. 8 overview savings 1 1 CASE STUDY 3 Flow (%) uren/jaar Ventilator smoorklep P = f(debiet)^3 Introduction Fig 9 software simulation 8 kw fan A large stainless steel manufacturer uses an AC arc furnace to melt the steel. The molten steel goes from the arc furnace in a convertor to reduce the percentage of carbon. Essentially, air is blown into the convertor to oxidise the carbon. Two 8 kw fans blow the air into the convertor. The air flow is regulated by valves. CONCLUSIONS Invertor technology is improving continuously: more performant components in combination with more performant control increase accuracy and speed of control, and reduces current harmonics. The three case studies taken from industry show clearly that installing variable speed drives generates important energy savings. Screw compressors, centrifugal pumps and fans with mechanical flow regulation are especially suited for variable speed regulation. However, one has to be aware of the fact that electronic speed regulation also implies some restrictions, especially in relation with deteriorated power quality. Line-side as well as motor-side harmonics are created, invertors are in the mean time very sensitive to short interruptions or voltage dips.