- Wiring Brochure Universal Reset Module 423

Similar documents
- Wiring Brochure Universal Reset Module 423e

Relay (R1) 003. Balancing Valve. Slab Pump (P1) Max. 4 pipe diameters apart. Injection Pump (P2) 150 No 24V only. Power. Off.

(Wireless Solution)

Resusci Anne Advanced SkillTrainer

Resusci Anne Advanced SkillTrainer

3M Model 1230 Disk Media Unlocker. Owner's Manual

BAS Integration Manual

Remote Control Outlets Operating Instructions

C-Bus 8 Channel Low Voltage Relay

Model: VR-1A INSTALLATION AND OPERATING INSTRUCTIONS

R PROFLAME Instruction Book Collection

Video Mono Audio Baluns

OSMAC RDR Low-voltage Retrofit Kit

Operating Distance An operating distance (in conjunction with our GLR27 series receivers) of 350 metres is possible.

Shields. Outdoor Shields Owner s Manual. Avoidance Solutions.

FinishLynx Interface. Includes: Power requirements: 9 VDC Power Adapter (included) Size: Approximately 5 x 3 x 2 Approximate weight: 5.57oz.

Agilent G1888 Network Headspace Sampler

Video Stereo Audio Baluns

Installation Instructions

Model: VR-2A INSTALLATION AND OPERATING INSTRUCTIONS

HARDWARE GUIDE. FlexIO Controller M2000 Series. Specifications and Operational Guide

ELSEMA. GLR2701 Single Channel 27MHz Gigalink Receiver with Timer Controlled Relay Output

XD-V30 Digital Wireless System

Setup Guide. support.spruceirrigation.com.

XD-V70 Wireless Receiver

Installation and Operation Manual MSI. Multi-Sensor Interface Hub. Interface Module for all Sensors Network and Wireless CAUTION

12V Victor 888 User Manual

DM-45 Digital Multimeter

Wireless 900 MHz Receiver

GE Interlogix Fiber Options S714D & S7714D. Instruction Manual FIBER-OPTIC NETWORK TRANSMISSION SYSTEM

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

Wireless Room Temperature and Humidity Transmitter (Units without Temperature Setpoint or Override) Installation and Operating Instructions

Owner s Manual AC & BATTERY POWERED FET

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español

On-Line Cardio Theater Wireless Digital Transmitter Installation and Instruction Manual

GETTING STARTED GUIDE NI AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous

CAUTION. RXM5010 Touchscreen Remote Installation and Operation Manual MODEL: RXM5010

MS1000 User Information MS1000-H systems equipped with MX900 Micro Transceiver will Send and Receive.

SER8300 Series Terminal Equipment Controller with Optional PIR sensor Installation Guide

Do not expose this device to water or moisture of any kind. Do not mix new and old batteries or batteries of different types.

Rosemount 753R Remote Web Based Monitoring Indicator

SAFETY WARNINGS AND GUIDELINES

Installation Instructions RF8010/RF8310 RF8010/RF8310: EXTERNAL ANTENNA

2-Slot Desktop Chassis (DC) Extended Temperature

Explosion Proof Page/Talk Paging Amplifier

USER'S MANUAL DMR-6700

Indoor Micro Shields Owner s Manual. Please read this entire guide before operating.

Buzz Lightyear Learn & Go

Blue Point Engineering Inc.

45 AND 60 UNIVERSAL REMOTE INSTALLATION AND OPERATION INSTRUCTIONS

Installation Instructions RF5910

DA216S DISTRIBUTION AMPLIFIER

Installation Instructions

CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL

WRZ-RMT10K-0 Wireless Remote Temperature Transmitter

Wireless Keychain Remote Control

User s Manual. Twist & Learn Gorilla Pals VTech

Universal End of Period (EOP) Segment Installation Manual

INSTALLATION INSTRUCTIONS FOR THE CLIKCARD COMMERCIAL RECEIVER (NARROW BAND)

SAFETY WARNINGS AND GUIDELINES INTRODUCTION

TWO-WAY RADIO. Þ ß Ô ² ú RPV516/RPU416. Owner's Manual

EA200 uhf EA200 vhf User Guide

MNL-5Rxx. Application. Model Chart. TAC I/A Series MicroNet MN 50 Controller Installation Instructions

IS7705. Installation & Operation Manual AUDIO INTEGRATION KIT. TranzIt LINK

INSTRUCTION MANUAL LCS TX

Indoor Shields Plus Owner s Manual. Please read this entire guide before operating.

S5-ADU. Front... 4 Rear... 4

HARDWARE GUIDE. Digital Sensor - T1100 Series. Specifications and Operational Guide

MEGA REMOTE RADIO REMOTE CONTROL SYSTEM

Ambient Level Controller

P/N B ProBlue and DuraBlue Thermostat Service Kit - P/N

SELECTIVE CALL INTERCOM SYSTEM MODEL: IM-5000 MASTER STATION

Instruction Manual. for Media Monkey. 1

ProfiScale MULTI Multimeter

RF (RADIO FREQUENCY) WIRELESS PENDANT

Scoreboard Operator s Instructions MPCX2 Pitch Count Control

KANEKA OLED Lighting Module SL (LE-01L, LE-02L, LE-03L, LE-01H, LE-02H, LE-03H) Instruction Manual

MULTIPLE OUTPUT DIGITAL DELAY

ALPHA meter. General. Installation instructions IL S

INSTALLATION AND OPERATION MANUAL

Instruction Manual Model Upconverter

Disclaimers. Important Notice

NV-WA40W. Installation and User Guide

I n s ta l l at i o n M a n u a l f o r T E D P r o H o m e T E D P r o L i t e A B C Rev 4.0

fisher-price.com Visit service.fisher-price.com for assembly video

MP Series Radar Transmitter Installation & Operation Manual

IR-3000 Wireless PIR Sensor. Owner s Manual

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com # # AAC Clamp Meter. Instruction Manual

MDC4500-4B Amplifier/Combiner Data Sheet & User Manual. February Rev 0.95

Digital Room Sensor Technical Guide

User s Manual

USER MANUAL 600A AC Clamp Meter + NCV Model MA610

FP-RLY-420. Features. Installing the FP-RLY-420. FieldPoint Operating Instructions. Eight-Channel SPST Relay Module

Log Periodic Antenna

Instruction Manual Model Upconverter

312, 316, 318. Clamp Meter. Users Manual

USER MANUAL. Mini Multimeter with Non-Contact Voltage Detector (NCV) Model EX330

Appearance of device and accessories may vary.

EasyAssist. Direct to Radio Call Button. Operating Manual

2011 / Circuit Tracer

Transcription:

- Wiring Brochure Universal Reset Module 423 W 423 03/09 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in 4 Wiring Brochure Wiring and 5 Data Brochure Control settings 6 Job wiring instructions installation of specific control and sequence of operation Record Record settings & wiring details for future reference Overview The following wiring brochure describes how to wire the tekmar Universal Reset Module 423. The 423 is to be installed in an enclosure together with a tekmar Zone Manager. The 423 controls two boilers (on-off or modulating),, and setpoint. The wiring of tekmarnet 4 (tn4) components is simple and cost effective. Stage1/ Stage 2/ Boil Enbl Setp Enbl 50 51 52 53 + Mod1 (dc) 54 55 + C1 tn4 C2 tn4 C3 tn4 Mod2 (dc) 1 2 3 56 57 58 59 60 61 62 63 64 65 Com Boil Com Out 66 67 68 69 70 Do not apply power H7010A Meets Class B: Canadian ICES & FCC Part 15 Made in Canada Menu Universal Reset Module 423 tn4 / Boil Sens Sup / Ret Off / Off / tekmar Stager s On-Off / Mod Off / Rotation Item tektra 1006-01 Powered Outputs 24 V (ac) Demands: 20-260 V (ac) Relay Rating: 115 V (ac) 5 A Test 8 VA 1 VA 71 72 73 74 24 V (ac) C Vlv C R 75 76 77 78 Setpoint Demand Demand 79 80 81 82 Primary N N 10 A max tekmar wiring Enclosure (not included) tekmar Zone Manager 1 of 12 2009 W 423-03/09

Table of Contents Wiring Symbols & Definitions...2 Module Installation...3 Electrical Drawings...4-7 Wiring the Control...8-10 Troubleshooting Instructions... 10-12 Technical Data... 12 Wiring Symbols Demand, signals control to operate. Requires a power and neutral connection. Use 24 to 260 V (ac), usually switched externally. Example: Demand Dry contact switch. Operates a device. Example: Powered switch. 24-115 V (ac) power, switched output to valve, pump, etc. tekmarnet 4 Earth ground Do not apply power to these terminals. Serious control damage will result. Definitions The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product. Caution: Refer to accompanying documents Caution: Refer to accompanying documents INSTALLATION CATEGORY II Local level appliances Caution Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for uses as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit. Do not attempt to service the control. Refer to qualified personnel for servicing. Apart from any field replaceable fuse(s) there are no user serviceable parts. Attempting to do so voids warranty and could result in damage to the equipment and possibly even personal injury or death. 2009 W 423-03/09 2 of 12

Module Installation Install the Universal Reset Module 423 in the left side of a tekmarnet 4 (tn4) wiring enclosure. The enclosure comes with a Zone Manager pre-installed in the right side. Review the figure below to understand the installation of the 423. To Install the 423 1. Remove the front cover of the wiring enclosure by removing the two screws. 2. Remove the left side blank by removing the centre screw holding the blank and the Zone Manager in place. Make sure the Zone Manager stays in place. 3. Discard the blank. 4. The 423 has connector pins protruding from the underside of the board. The Zone Manager has wiring harnesses with plugs that connect to these pins. Remove the required wiring harnesses from their retaining clips in the enclosure. 5. Carefully connect the Zone Manager s plugs onto the pins on the underside of the 423. There is one smaller gauge connector with three pins and one larger gauge connector with 2 pins. These connectors can be installed only one way. Take care to ensure a good connection and avoid bending the pins. 6. Lower the 423 into the enclosure at an angle. Insert the two tabs on the left side of the 423 in to the corresponding slots in the left side of the wiring enclosure. 7. Lower the 423 toward the center of the enclosure until the two halves fit together. Make sure that the connector wires are placed underneath without pinching the wire. 8. Replace the center screw to hold the two controls in place. 9. Strip all wiring to a length of 3/8 in. or 10 mm for all terminals. Electrical Drawings The electrical drawing examples on the following pages show the 423 in common applications Choose the drawing that most accurately depicts the components in your system and use that drawing as a guide to aid in wiring your system. These are only concept drawings, not engineered drawings. They are not intended to describe a complete system nor any particular system. It is up to the system designer to determine the necessary components for and configuration of the particular system being designed including additional equipment isolation relays (for loads greater than the controls specified output ratings) and any safety devices which in the judgement of the designer are appropriate in order to properly size, configure and design that system and to ensure compliance with building and safety code requirements. 3 of 12 2009 W 423-03/09

Electrical Application 423 E1 Description: with and, Setpoint, Two On / Off s. On / Off 2 082 082 Outdoor 070 On / Off 1 3 Stage1/ Stage 2/ Boil Enbl Setp Enbl 50 51 52 53 + Mod1 (dc) 54 55 + C1 tn4 C2 tn4 C3 tn4 Mod2 (dc) 1 2 3 56 57 58 59 60 61 62 63 64 65 Com Boil Com Out 66 67 68 69 70 Do not apply power 24 V (ac) R & C tn4 = 1 H7010A Meets Class B: Canadian ICES & FCC Part 15 Made in Canada Menu Universal Reset Module 423 tn4 See D 423 / Boil Sens Sup / Ret Off / Off / tekmar Stager s On-Off / Mod Off / Rotation Item tektra 1006-01 Connections from Zone Manager Powered Outputs 24 V (ac) Demands: 20-260 V (ac) Relay Rating: 115 V (ac) 5 A Test 8 VA 1 VA 71 72 73 74 24 V (ac) C Vlv C R 75 76 77 78 Setpoint Demand Demand 79 80 81 82 Primary N N 10 A max 115 V (ac) L & N Setpoint Call Refer to Job Record for Maximum Allowable Loads To ground 2009 W 423-03/09 4 of 12

Electrical Application 423 E2 Description: with Aquastat and Valve, Setpoint, Single On / Off. On / Off 2 082 Outdoor 070 1 3 Stage1/ Stage 2/ Boil Enbl Setp Enbl 50 51 52 53 + Mod1 (dc) 54 55 + C1 tn4 C2 tn4 C3 tn4 Mod2 (dc) 1 2 3 56 57 58 59 60 61 62 63 64 65 Com Boil Com Out 66 67 68 69 70 Do not apply power 24 V (ac) R & C tn4 = 1 H7010A Meets Class B: Canadian ICES & FCC Part 15 Made in Canada Menu Universal Reset Module 423 tn4 See D 423 / Boil Sens Sup / Ret Off / Off / tekmar Stager s On-Off / Mod Off / Rotation Item tektra 1006-01 Connections from Zone Manager Powered Outputs 24 V (ac) Demands: 20-260 V (ac) Relay Rating: 115 V (ac) 5 A Test 8 VA 1 VA 71 72 73 74 24 V (ac) C Vlv C R 75 76 77 78 Setpoint Demand Demand 79 80 81 82 Primary N N 10 A max 115 V (ac) L & N Valve Call Setpoint Call Refer to Job Record for Maximum Allowable Loads To ground 5 of 12 2009 W 423-03/09

Electrical Application 423 E3 Description: with Aquastat and, Setpoint, Multi-stage Control. 0-10 V(dc) to tekmar Stager 2 082 Outdoor 070 1 3 Stage1/ Stage 2/ Boil Enbl Setp Enbl 50 51 52 53 + Mod1 (dc) 54 55 + C1 tn4 C2 tn4 C3 tn4 Mod2 (dc) 1 2 3 56 57 58 59 60 61 62 63 64 65 Com Boil Com Out 66 67 68 69 70 Do not apply power 24 V (ac) R & C tn4 = 1 H7010A Meets Class B: Canadian ICES & FCC Part 15 Made in Canada Menu Universal Reset Module 423 tn4 See D 423 / Boil Sens Sup / Ret Off / Off / tekmar Stager s On-Off / Mod Off / Rotation Item tektra 1006-01 Connections from Zone Manager Powered Outputs 24 V (ac) Demands: 20-260 V (ac) Relay Rating: 115 V (ac) 5 A Test 8 VA 1 VA 71 72 73 74 24 V (ac) C Vlv C R 75 76 77 78 Setpoint Demand Demand 79 80 81 82 Primary N N 10 A max 115 V (ac) L & N Call Setpoint Call Refer to Job Record for Maximum Allowable Loads To ground 2009 W 423-03/09 6 of 12

Electrical Application 423 E4 Description: with and, Setpoint, Two Modulating s. 0-10 V(dc) 2 082 082 Outdoor 070 0-10 V(dc) 1 3 Stage1/ Stage 2/ Boil Enbl Setp Enbl 50 51 52 53 + Mod1 (dc) 54 55 + C1 tn4 C2 tn4 C3 tn4 Mod2 (dc) 1 2 3 56 57 58 59 60 61 62 63 64 65 Com Boil Com Out 66 67 68 69 70 Do not apply power 24 V (ac) R & C tn4 = 1 H7010A Meets Class B: Canadian ICES & FCC Part 15 Made in Canada Menu Universal Reset Module 423 tn4 See D 423 / Boil Sens Sup / Ret Off / Off / tekmar Stager s On-Off / Mod Off / Rotation Item tektra 1006-01 Connections from Zone Manager Powered Outputs 24 V (ac) Demands: 20-260 V (ac) Relay Rating: 115 V (ac) 5 A Test 8 VA 1 VA 71 72 73 74 24 V (ac) C Vlv C R 75 76 77 78 Setpoint Demand Demand 79 80 81 82 Primary N N 10 A max 115 V (ac) L & N Setpoint Call Refer to Job Record for Maximum Allowable Loads To ground 7 of 12 2009 W 423-03/09

Wiring the Control Terminals 50-78 The following section explains how to wire individual devices to the Universal Reset Module 423. For step by step wiring refer to the terminal number on the right of the page. Before wiring ensure all power is turned off and take all necessary precautions. Install the supplied wiring compartment barriers by sliding them into the grooves provided as to isolate the low and high voltage wiring. Strip all wiring to a length of 3/8 in. or 10 mm for all terminals. Refer to the current and voltage ratings at the back of this brochure before connecting devices to this control. Wiring the Terminals 50-51, 52-53 Terminals 50-51 and 52-53 are dry contacts. No power is available from these switches. When the switch at 50-51 or 52-53 is closed the boiler is to turn on. The boiler gets no power from these terminals and the boiler must be wired to power as per the manufacturers directions. These terminals are typically connected to the boiler s control circuit (commonly labeled as T-T). Connect these terminals directly to the boiler T-T connections. T-T contacts on boiler T-T contacts on boiler Stage 1/ Boil Enbl 50 51 Stage 2/ Setp Enbl 52 53 Wiring the Modulating Output Terminals 54-57 The control provides a 0-10 V (dc) modulating output to two modulating boilers or to a tekmar boiler staging control that accepts an External Input Signal in place of an outdoor sensor. (Example: 264, 265 and 268) Polarity is important. Connect the + wire from the boiler or staging control to terminal 54 and the wire from the boiler or staging control to terminal 55. Connect the + wire from the boiler to terminal 56 and the wire from the boiler to terminal 57. Note: Some modulating boilers may also require an on / off signal in addition to the modulating signal. See terminals 50-51 and 52-53. Modulating + - + - Modulating or tekmar Stager + - Mod1 (dc) 54 55 + - Mod2 (dc) 56 57 Wiring tekmarnet 4 (tn4) Between Devices Terminals 58-65 Terminals 58 through 65 provide four tn4 connections for tn4 devices on either the bus, tn4 bus 1, tn4 bus 2, or tn4 bus 3. Connect terminals 58 (C) and 59 (tn4) to the corresponding terminals on other tn4 devices on the. Polarity is important. Connect terminals 60 (C) and 61 (tn4) to the corresponding terminals on other tn4 devices on the 1. Polarity is important. Connect terminals 62 (C) and 63 (tn4) to the corresponding terminals on other tn4 devices on the 2. Polarity is important. Connect terminals 64 (C) and 65 (tn4) to the corresponding terminals on other tn4 devices on the 3. Polarity is important. C tn4 typical tn4 connection on additional control C2 tn4 58 59 1 60 61 C3 tn4 2 62 63 C4 tn4 3 64 65 2009 W 423-03/09 8 of 12

and (tekmar 082) Terminals 66-69 Connect the two wires from the 082 to the and Com (66-67) terminals. The is used by the control to measure the water temperature. Connect the two wires from the 082 to the Boil and Com (68-69) terminals. The is used by the control to measure the boiler supply temperature. mounted on boiler pipe mounted in tank Do Not Apply Power Com Boil Com 66 67 68 69 Outdoor (tekmar 070) Terminals 69-70 Connect the two wires from the Outdoor 070 to the Com and Out (69-70) terminals. The outdoor sensor is used by the control to measure the outdoor air temperature. Note: If an Outdoor 070 is connected to a tekmarnet 4 thermostat in the system, it is not required to be connected to the control. mounted on exterior wall Do Not Apply Power Com Out 69 70 Wiring a Valve Terminals 71-72 The control operates a 24 volt zone valve. Power is provided through an internal transformer to a maximum of 8 VA. Connect the wiring from the zone valve terminals 71 and 72 where terminal 71 is 24 volt C (neutral) and terminal 72 is 24 V R (hot) for opening the valve. 71 72 C Vlv Valve Wiring the Demands (, Setpoint) Terminals 73-78 To generate a Demand a voltage between 20 and 260 V (ac) must be applied across the Demand terminals (75-76). To generate a Setpoint Demand, a voltage between 20 and 260 V (ac) must be applied across the Setpoint Demand terminals (77-78). 24 V (ac) is provided on terminals 73 and 74 to power the Demand and the Setpoint Demand. Each demand uses approximately 0.1 VA. The example shows the wiring to generate a Setpoint Demand. 73 74 75 76 77 78 Switch (from Setpoint 24 V (ac) Setpoint Control or aquastat) C R Demand Demand 9 of 12 2009 W 423-03/09

Wiring the and Primary Terminals 79-80, 81-82 The control operates a Primary, and a. If a Primary is used, the pump is wired directly to terminals 81 and 82. If a is used, the pump is wired directly to terminals 79 and 80. The pumps ground wires are connected to the ground screw provided in the wiring chamber. Note: For pumps larger than the control s rated capacity, an external isolation relay must be used. L & N 81 82 Primary N Troubleshooting the Wiring General The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly trained and experienced persons. A good quality electrical test meter, capable of reading from at least 0-300 V (ac), 0-30 V (dc), 0-2,000,000 Ohms, and testing for continuity is essential to properly test the wiring and sensors. Test Meter Control Terminals For an explanation on the use of the Test Button, the Test sequence or any error messages, refer to the Data Brochure. Testing the Control Terminals 50-82 Test the Stage 1 and Stage 2 Contacts Terminals 50-53 1. Shut off power to the control and the boiler circuit. 2. Remove the front cover from the control. Disconnect the wires from the Stage 1 and Stage 2 contacts (terminals 50-51, 52-53). 3. Apply power to the control and press the Test Button. 4. Use an electrical test meter and check for continuity between terminals 50-51 and 52-53. When each stage symbol is displayed in the LCD, there should be continuity. When the stage symbol is not displayed in the LCD, there should be no continuity. 5. Reconnect the wires to the Stage 1 and Stage 2 contacts (50-51 and 52-53), install the front cover on the control and apply power to the boiler circuit. Testing Modulating Action (0-10 V dc) Terminals 54-57 1. Ensure that the control is set to operate the modulating output. 2. Remove the front cover from the control. 3. Press the Test Button. 4. When the % output graph and the burner symbol are displayed in the LCD, use an electrical test meter to measure the (dc) voltage between the Mod (dc) + and the Mod (dc) - terminals (54-55, 56-57). The reading should vary between 0 V (dc) and 10 V (dc). 5. If power is not present: Check the power supply to the Zone Manager and the field replaceable fuse for the transformer on the Zone Manager. If the fuse is blown, determine the cause of the failure before replacing the fuse. Also check the Plug in connections on the underside of the control. 2009 W 423-03/09 10 of 12

Testing tn4 Network Terminals 58-65 To test each tn4 Network, check the wires for continuity. 1. Disconnect the two wires (tn4 and C) at one end and connect them together. 2. Go to the other end of the wires and disconnect them. 3. Using an electrical test meter, check for continuity. Testing tekmar s Terminals 66-70 To test the sensors, the actual temperature at each sensor location must be measured. Use a good quality digital thermometer with a surface temperature probe for ease of use and accuracy. Where a digital thermometer is not available, strap a spare sensor alongside the one to be tested and compare the readings. Disconnect each sensor from the control. Test the sensors resistance according to the instructions in the sensor Data Brochure D 070. Testing Zone Valve Terminals 71, 72 1. Ensure that the control is set to operate the zone valve output. 2. Remove the front cover from the control. 3. Press the Test Button. 4. When is displayed in the LCD, use an electrical test meter to measure the (ac) voltage between the C and Vlv terminals (71-72). The reading should be 24 V (ac) + / 10%. 5. If power is not present: Check the power supply to the Zone Manager and the field replaceable fuse for the transformer on the Zone Manager. If the fuse is blown, determine the cause of the failure before replacing the fuse. Also check the Plug in connections on the underside of the control. 6. When is not displayed in the LCD, use an electrical test meter to measure the (ac) voltage between the C and Vlv terminals (71-72). The reading should be 0 V (ac). Testing Auxiliary 24 V Power Supply Terminals 73-74 1. Remove the front cover from the control. 2. Use an electrical test meter to measure (ac) voltage between the Power R and Power C terminals 74 and 73 The reading should be 24 V (ac) + / 10%. 3. If power is not present: Check the power supply to the Zone Manager and the field replaceable fuse for the transformer on the Zone Manager. If the fuse is blown, determine the cause of the failure before replacing the fuse. Also check the Plug in connections on the underside of the control. Testing the or Setpoint Demand Terminals 75-78 1. Remove the front cover from the control. 2. Use an electrical test meter to measure (ac) voltage between the Demand terminals (75-76) or the Setpoint Demand terminals (77-78). When the demand device is on a voltage between 20 and 260 V (ac) should be measured between terminals and the LCD should display DEM and or SETP. When the demand device is off, less than 5 V (ac) should be measured between the terminals. 11 of 12 2009 W 423-03/09

Testing and Primary Terminals 79-82 1. Remove the front cover from the control. 2. Press the Test Button. 3. When the Primary symbol is displayed in the LCD, use an electrical test meter to measure the (ac) voltage between the Primary terminals (81-82). 4. When the symbol is displayed in the LCD, use an electrical test meter to measure the (ac) voltage between the terminals (79-80). The reading should be 115 V (ac) + / 10%. Note: The proper mode must be selected before testing the pump output. If power is not present: Check the power supply to the Zone Manager. Also check the Plug in connections on the underside of the control. Technical Data Universal Reset Module 423; Four tekmarnet 4,, & Setpoint Control Microprocessor PID control; This is not a safety (limit) control Packaged weight 1.83 lb. (830 g) Dimensions 3-5/8 H x 5-3/8 W x 9/16 D (92 x 137 x 14 mm) Approvals CSA C US, CSA/UL 61010-1, meets Class B: ICES and FCC Part 15 Ambient conditions Indoor use only, 32 to 122 F (0 to 50 C) RH 80% to 88 F (31 C), down to 50% from 104 to 122 F (40 to 50 C) Altitude <6560 feet (2000 m), Installation Category II, Pollution Degree 2 Power Supply Provided by interconnected Zone Manager Relay 115 V (ac) 5 A Primary Relay 115 V (ac) 5 A Combined Load 10 A Maximum (for and Primary ) Valve Output 24 V (ac) 8 VA Maximum Modulation Output 0-10 V Minimum 2500 Relay 115 V (ac) 5 A Demands 20-260 V (ac) / 0.1 VA @ 24 V s NTC thermistor, 10k @ 77 F (25 C ± 0.2 C) ß=3892 Included Outdoor 070 and Universal 082 The installer must ensure that this control and its wiring are isolated and / or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and / or connecting the control to a different circuit from that to which the receiver is connected. Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright 2009 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 12 of 12 All specifications are subject to change without notice. Printed in Canada. W 423-03/09.