SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

Similar documents
BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Safety through proper system Grounding and Ground Fault Protection

Fault Analysis. EE 340 Spring 2012

UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016

एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

, ,54 A

In Class Examples (ICE)

Exercises on overhead power lines (and underground cables)

Initial Application Form for Connection of Distributed Generation (>10kW)

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

Industrial and Commercial Power Systems Topic 7 EARTHING

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

IV. Three-Phase Transfomers

2. Current interruption transients


Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Var Control. Adding a transformer and transformer voltage regulation. engineers loadflow program. The control system engineers loadflow.

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

A Direct Power Controlled and Series Compensated EHV Transmission Line

Chapter 2-1 Transformers

Rajasthan Technical University, Kota

The power transformer

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

Chapter 2: Transformers

AC Power Instructor Notes

Summary of Relaying Reviews Reporting

A Guide to the DC Decay of Fault Current and X/R Ratios

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Practical Transformer on Load

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits

Lecturer: Dr. J B E AL-ATRASH No. of Pages: 4

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

3-phase short-circuit current (Isc) at any point within a LV installation

Beyond the Knee Point: A Practical Guide to CT Saturation

Grounding System Theory and Practice

SECTION 1 INTRODUCTION

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Preface...x Chapter 1 Electrical Fundamentals

Power Factor & Harmonics

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Chapter # : 17 Symmetrical Fault Calculations

EL 403 MODEL TEST PAPER - 1 POWER SYSTEMS. Time: Three Hours Maximum Marks: 100

Power Quality Basics. Presented by. Scott Peele PE

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

Rajasthan Technical University, Kota

ESO 210 Introduction to Electrical Engineering

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

Transmission Line Models Part 1

Look over Chapter 31 sections 1-4, 6, 8, 9, 10, 11 Examples 1-8. Look over Chapter 21 sections Examples PHYS 2212 PHYS 1112

EN Assignment No.1 - TRANSFORMERS

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

The Analysis of Voltage Increase Phenomena in a Distribution Network with High Penetration of Distributed Generation

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

SCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering

University of Rajshahi Department of Electrical & Electronic Engineering B.Sc. Engineering Part-IV Odd Semester Examination- 2017

Electrical Circuits Question Paper 6

Exercises. 6 Exercises

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

Dynamic Model Of 400 Kv Line With Distance Relay. Director Research, The MRPC Company, Hyderabad, India 2

Transmission Line Fault Location Explained A review of single ended impedance based fault location methods, with real life examples

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

The calculation of short-circuit current in the electrical design of traction substation

Spring 2000 EE361: MIDTERM EXAM 1

Exercise 2: Parallel RLC Circuits

2 Grounding of power supply system neutral

Constant Terminal Voltage. Working Group Meeting 4 19 th September 2014

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

ECE456 Power System Protection

Fatima Michael college of Engineering and Technology

Distance Relay Response to Transformer Energization: Problems and Solutions

Bus Protection Fundamentals

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math

Modeling of Three-phase or Bank of Three Single Phase Three Winding Transformers Zero-phase-sequence Leakage Impedance in PSS E Short Circuit Module

EXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION

Generator Protection GENERATOR CONTROL AND PROTECTION

MV network design & devices selection EXERCISE BOOK

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

Power Plant and Transmission System Protection Coordination Fundamentals

TABLE OF CONTENT

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

ARC FLASH HAZARD ANALYSIS AND MITIGATION

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

Final Exam Fall 2018

Analysis of a 405 km transmission line with series compensation

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Transcription:

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SLIDE In this video, we will cover a sample exam problem for the Power PE Exam. This exam problem falls under the topic of Protection, which accounts for 6 of 80 problems on the PE exam. The question reads, Two generators are connected in parallel and each serves their own transformer. The outputs of these transformers are connected to a common bus and then a common transmission line. If a three phase fault occurs on the transmission line, then what will be the fault current? The ratings of the equipment are shown on the next slide. You can assume the circuit is three phase and the neutrals are solidly grounded. SLIDE 2 The properties of the generators and transformers are shown on this slide. The voltages, MVAs and sub-transient reactances are provided for the generator. The voltages, MVAs and percent impdeances are provided for the transformers. Finally the rated voltage and impedance per phase of the transmission line is provided. This problem only provides the necessary information to complete the problem, but the PE exam may also include extra information like transformer configurations, transient reactances as opposed to sub-transient reactances and negative or zero components. Where as in this problem only positive components are shown. Generator : 500 MVA, 3.8 kv, X = 0.5 Transformer : 500 MVA, 3.8/230 kv, X = 0.3 Generator 2:,200 MVA, 3.8 kv, X = 0.08 Transformer 2:,200 MVA, 3.8/230 kv, X = 0.08 Transmission Line: 230 kv, X = 0 Ω per phase On the exam, you should be able to construct a simple one line diagram to show which components are in parallel and which components are in series, if the PE exam does not provide a diagram for you. Protection-

SLIDE 3 There are multiple methods to complete this problem, like the MVA method and the Per Unit Method. However, this video focuses on the MVA method and if you would like more information on the Per Unit method, please see the website in the description link. SLIDE 4 The first step in the MVA method is to convert all components properties to equivalent short circuit MVA. This is the maximum amount of power that can flow through the component during a short circuit. Each component has its own way of finding its equivalent short circuit MVA which will be covered in the next slide. SLIDE 5 For the generator the short circuit MVA value is found by dividing the full load MVA of the generator by the generator s sub transient reactance. Do not use the transient reactance or steady state reactance, since the transient and steady state reactance values do not give you the instantaneous short circuit current. SLIDE 6 ; Next, the transformer short circuit MVA value describes the total amount of apparent power through a transformer during a 3-phase fault. This value is found by dividing the full load MVA of the transformer by the percent impedance of the transformer. 00% % ; Protection-2

SLIDE 7 The short circuit current in a transmission line is simply a function of the voltage in the line and the impedance in the line. The short circuit MVA value is found by taking the rated voltage in kilo-volts squared and dividing the value by the per phase impedance. The units will result in MVA for the short circuit MVA of the transmission line. SLIDE 8 ; Ω The previous calculations will result in the following short circuit MVA values as shown in this figure. The next step is to combine each of these MVA values with the equations for combining components in parallel and series on the next slide. Protection-3

SLIDE 9 The following equations can be used to combine each component. You can notice from these equations that when parallel components are used, then the MVA is increased and when series components are used the resulting total MVA is reduced. SLIDE 0 First you want to work from left to right to simplify the circuit. First, combine the generator and transformer in series for both sets. Notice, that the series components will increase impedance to short circuit current which decreases the MVA short circuit value.,786 2 2 2 2 7,500 Protection-4

SLIDE Then combine these two circuits in parallel. Notice that parallel lines provide additional paths for short circuit current to flow, which increases the MVA short circuit value. & 9,286 SLIDE 2 Finally combine the previous value in series with the transmission line, which results in the value as shown. 3,370 & SLIDE 3 Protection-5

Finally the last step is to use the resulting MVA combined value for the entire circuit from the power source to the fault location and the apparent power equation to find the short circuit current or fault current for a three phase fault. The equation is simply P = I*V*Root 3. Make sure you use the voltage at the fault location. The resulting answer is (C) 8,640 A. Thank you! 3,370 000, 8,460 3 230 Protection-6