IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Similar documents
NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

PART 1 OWNER/APPLICANT INFORMATION

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

APPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

APPENDIX B: Generation Interconnection Application Form

Form B. Connection Impact Assessment Application Form Distribution System

Connection Impact Assessment Application Form

Connection Impact Assessment Application

Embedded Generation Connection Application Form

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Embedded Generation Connection Application Form

Impact Assessment Generator Form

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW

Initial Application Form for Connection of Distributed Generation (>10kW)

Embedded Generation Connection Application Form

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

Wind Power Facility Technical Requirements CHANGE HISTORY

QUESTIONNAIRE for Wind Farm Power Stations only

Generation Interconnection Study Data Sheet Synchronous Machines

Distributed Generation Application Form (Generation of Greater than 20 kw to 15 MW)

Imperial Irrigation District System Planning ATTACHMENT A

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

General Information. * Required

ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS

TABLE OF CONTENT

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Southern Company Interconnection Requirements for Inverter-Based Generation

ELECTRICAL POWER ENGINEERING

Facility Interconnection Requirements for Colorado Springs Utilities Version 03 TABLE OF CONTENTS

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Fault Ride Through Technical Assessment Report Template

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Sizing Generators for Leading Power Factor

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE

An Introduction to Completing a NERC PRC-019 Study for Traditional and Distributed Generation Sources

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

EH2741 Communication and Control in Electric Power Systems Lecture 2

Conventional Paper-II-2013

Effects of Harmonic Distortion I

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD

System Protection and Control Subcommittee

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

FACILITY CONNECTION REQUIREMENTS

SYNCHRONOUS MACHINES

Generation and Load Interconnection Standard

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

If any queries arise ESB Networks DAC can be contacted at or

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Utility Interconnection and System Protection

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

In Class Examples (ICE)

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Distribution System Development & Preliminary Studies

Transmission Interconnection Requirements for Inverter-Based Generation

PAPER-II (Subjective)

Design, Implementation, and Dynamic Behavior of a Power Plant Model

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Table of Contents. Introduction... 1

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

CONTENTS. 1. Introduction Generating Stations 9 40

O V E R V I E W O F T H E

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Final ballot January BOT adoption February 2015

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Generator Protection GENERATOR CONTROL AND PROTECTION

Transcription:

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone Number: 208-388-2658 Fax: 208-388-5504 E-Mail Address: jcreason@idahopower.com An Interconnection Request is considered complete when it provides all applicable and correct information required below. Preamble and Instructions An Interconnection Customers who request interconnection must submit this Interconnection Request by hand delivery, mail, e-mail, or fax to the Transmission Provider. Processing Fee or Deposit: If the Interconnection Request passes ALL screens of SGIP Section 2.2.1, the application may be submitted under the Fast Track Process, and the non-refundable processing fee is $500. Please contact Idaho Power if you have any questions. All Interconnection Requests that do not pass the Fast Track screens, shall submit a deposit of $1,000 for projects up to 30 MW in size and $10,000 for projects greater than 30 MW in size towards the cost of the feasibility study. Interconnection Customer Information Legal Name of the Interconnection Customer (or, if an individual, individual's name) Name: Contact Person: Mailing Address: City: State: Zip: Facility Location (if different from above): Telephone (Day): Telephone (Evening): Fax: E-Mail Address: 1

Alternative Contact Information (if different from the Interconnection Customer) Contact Name: Title: Address: Telephone (Day): Telephone (Evening): Fax: E-Mail Address: Application is for: New Small Generating Facility Capacity addition to Existing Small Generating Facility If capacity addition to existing facility, please describe: Will the Small Generating Facility be used for any of the following? To Supply Power to the Interconnection Customer? Yes No To Supply Power to Others? Yes No For installations at locations with existing electric service to which the proposed Small Generating Facility will interconnect, provide: (Local Electric Service Provider*) (Existing Account Number*) [*To be provided by the Interconnection Customer if the local electric service provider is different from the Transmission Provider] Requested Point of Interconnection: Interconnection Customer's Requested In-Service Date: 2

Small Generating Facility Information Data apply only to the Small Generating Facility, not the Interconnection Facilities. Energy Source: Solar Wind Hydro Hydro Type (e.g. Run-of-River): Diesel Natural Gas Fuel Oil Other (state type) Prime Mover: Fuel Cell Recip Engine Gas Turb Steam Turb Microturbine PV Other Type of Generator: Synchronous Induction Inverter Generator Nameplate Rating: kw (Typical) Generator Nameplate kvar: Interconnection Customer or Customer-Site Load: kw (if none, so state) Typical Reactive Load (if known): Maximum Physical Export Capability Requested: kw List components of the Small Generating Facility equipment package that are currently certified: Equipment Type 1. 2. 3. 4. 5. Certifying Entity Is the prime mover compatible with the certified protective relay package? Yes No Generator (or solar collector) Manufacturer, Model Name & Number: Version Number: Nameplate Output Power Rating in kw: (Summer) (Winter) Nameplate Output Power Rating in kva: (Summer) (Winter) Individual Generator Power Factor Rated Power Factor: Leading: Lagging: Total Number of Generators in wind farm to be interconnected pursuant to this Interconnection Request: Elevation: Single phase Three phase Inverter Manufacturer, Model Name & Number (if used): List of adjustable set points for the protective equipment or software: Small Generating Facility Characteristic Data (for rotating machines) RPM Frequency: (*) Neutral Grounding Resistor (If Applicable): Synchronous Generators: 3

Direct Axis Synchronous Reactance, Xd: P.U. Direct Axis Transient Reactance, X' d: P.U. Direct Axis Subtransient Reactance, X" d: P.U. Negative Sequence Reactance, X 2 : P.U. Zero Sequence Reactance, X 0 : P.U. KVA Base: Field Volts: Field Amperes: Induction Generators: Motoring Power (kw): I 2 2 t or K (Heating Time Constant): Rotor Resistance, Rr: Stator Resistance, Rs: Stator Reactance, Xs: Rotor Reactance, Xr: Magnetizing Reactance, Xm: Short Circuit Reactance, Xd'': Exciting Current: Temperature Rise: Frame Size: Design Letter: Reactive Power Required In Vars (No Load): Reactive Power Required In Vars (Full Load): Total Rotating Inertia, H: Per Unit on kva Base Note: Please contact the Transmission Provider prior to submitting the Interconnection Request to determine if the specified information above is required. Excitation and Governor System Data for Synchronous Generators Only Provide appropriate IEEE model block diagram of excitation system, governor system and power system stabilizer (PSS) in accordance with the regional reliability council criteria. A PSS may be determined to be required by applicable studies. A copy of the manufacturer's block diagram may not be substituted. Interconnection Facilities Information Will a transformer be used between the generator and the point of common coupling? Yes No Will the transformer be provided by the Interconnection Customer? Yes No Transformer Data (If Applicable, for Interconnection Customer-Owned Transformer): Is the transformer: single phase three phase? Transformer Impedance: % on kva Base Size: kva If Three Phase: Transformer Primary: Volts Delta Wye Wye Grounded Transformer Secondary: Volts Delta Wye Wye Grounded Transformer Tertiary: Volts Delta Wye Wye Grounded Transformer Fuse Data (If Applicable, for Interconnection Customer-Owned Fuse): (Attach copy of fuse manufacturer's Minimum Melt and Total Clearing Time-Current Curves) 4

Manufacturer: Type: Size: Speed: Interconnecting Circuit Breaker (if applicable): Manufacturer: Type: Load Rating (Amps): Interrupting Rating (Amps): Trip Speed (Cycles): Interconnection Protective Relays (If Applicable): If Microprocessor-Controlled: List of Functions and Adjustable Setpoints for the protective equipment or software: Setpoint Function Minimum Maximum 1. 2. 3. 4. 5. 6. If Discrete Components: (Enclose Copy of any Proposed Time-Overcurrent Coordination Curves) Manufacturer: Type: Style/Catalog No.: Proposed Setting: Manufacturer: Type: Style/Catalog No.: Proposed Setting: Manufacturer: Type: Style/Catalog No.: Proposed Setting: Manufacturer: Type: Style/Catalog No.: Proposed Setting: Manufacturer: Type: Style/Catalog No.: Proposed Setting: Current Transformer Data (If Applicable): (Enclose Copy of Manufacturer's Excitation and Ratio Correction Curves) Manufacturer: Type: Accuracy Class: Proposed Ratio Connection: Manufacturer: Type: Accuracy Class: Proposed Ratio Connection: Potential Transformer Data (If Applicable): Manufacturer: Type: Accuracy Class: Proposed Ratio Connection: Manufacturer: Type: Accuracy Class: Proposed Ratio Connection: 5

Wind Turbine Generating Facility Required Data 1. Single Machine Equivalent One-Line Diagram Please provide a single machine equivalent one-line diagram similar to figure below: 2. Interconnection Transmission Line Point of Interconnection (substation or transmission line name): Line voltage = kv MVA Normal Rating = MVA MVA Emergency Rating = MVA R = ohm or pu on 100 MVA and line kv base (positive sequence) X = ohm or pu on 100 MVA and line kv base (positive sequence) B = μf or pu on 100 MVA and line kv base (positive sequence) 3. Station Transformer (Note: If there are multiple transformers, data for each transformer should be provided) Nameplate Normal Rating (ONAN/ONAF/ONAF): / / MVA Emergency Rating (ONAN/ONAF/ONAF): / / MVA Nominal Voltage for each winding (Low /High /Tertiary): / / kv Available taps: (indicate fixed or with LTC), Operating Tap: Positive sequence ZHL: %, X/R on transformer self-cooled (ONAN) MVA Winding connection vector group (delta-wye-gnd, delta-delta, etc.): 4. Collector System Equivalent Model Collector system voltage = kv MVA Normal Rating = MVA MVA Emergency Rating = MVA R = ohm or pu on 100 MVA and collector kv base (positive sequence) X = ohm or pu on 100 MVA and collector kv base (positive sequence) B = μf or pu on 100 MVA and collector kv base (positive sequence) Attach a one-line diagram of the collector layout indicating conductor length, type, and size. 5. Wind-turbine Generator (WTG) Pad-Mounted Transformer Number of generator step-up transformers: Individual Nameplate rating: MVA Individual Emergency rating: MVA Nominal voltage for each winding (Low /High): / kv Available taps: (indicate fixed or with LTC), Operating Tap: 6

Positive sequence impedance (Z1) %, X/R on transformer self-cooled MVA Winding connection vector group (delta-wye-gnd, delta-delta, etc.): 6. Wind-turbine Generator (WTG) Powerflow Data Proposed projects may include one or more WTG Types (See Note 6.1 below). Please provide the following data for each turbine type included in the proposed project: Number of WTGs: Nameplate Rating (each WTG): MVA Nameplate Rating (each WTG): MW WTG Manufacturer and Model: WTG Type (See Note 6.1): For Type 1 or Type 2 WTGs: Uncompensated power factor at full load: Power factor correction capacitors at full load: Mvar Number of shunt stages and size Please attach capability curve describing reactive power or power factor range from 0 to full output, including the effect of shunt compensation. For Type 3 and Type 4 WTGs: Maximum under-excited power factor at full load: Maximum under-excited power factor at full load: Control mode: (voltage control, fixed power factor) (See Note 6.2) Please attach capability curve describing reactive power or power factor range from 0 to full output. NOTE 6.1 - WTG Type can be one of the following: Type 1 Squirrel-cage induction generator Type 2 Wound rotor induction machine with variable rotor resistance Type 3 Doubly-fed asynchronous generator Type 4 Full converter interface NOTE 6.2 - Type 1 and Type 2 WTGs typically operate on fixed power factor mode for a wide range of output level, aided by turbine-side power factor correction capacitors (shunt compensation). With a suitable plant-level controller, Type 3 and Type 4 WTGs may be capable of dynamically varying power factor to contribute to voltage control mode operation, if required by the generator interconnection agreement. Please consult with the WTG manufacturer when in doubt. The interconnection study will determine the voltage control requirements for the project. Plant-level reactive compensation requirements are engineered to meet specific interconnection requirements. WTG reactive capability data described above could significantly impact study results and plant-level reactive compensation requirements. 7. Plant Reactive Power Compensation Provide the following information for plant-level reactive compensation, if applicable: Individual shunt capacitor and size of each: MVA 7

Dynamic reactive control device, (SVC, STATCOM): Control range MVAr (lead and lag) Control mode (e.g., voltage, power factor, reactive power): Regulation point or bus Description of control strategy Operating characteristic Automatic control model pickup levels and time delay setpoints Indicate if the project includes a plant controller 8. Wind-turbine Generator (WTG) Dynamics Data Provide dynamic models for transient stability analysis in PSLF format using models approved for use by WECC listed in the WECC Approved Dynamic Model Library. Provide low/high voltage-ride-through dynamic models using an approved PSLF format or the equipment low/high voltage protection settings. Provide over/under frequency-ride-through dynamic models using an approved PSLF format or the equipment over/under frequency protection settings. Note 8.1 - Please reference the WECC Wind Plant Dynamic Modeling Guidelines for additional information regarding the dynamics modeling needs of Idaho Power and WECC. Photo Voltaic (PV) Generating Facility Required Data 1. Single Machine Equivalent One-Line Diagram Please provide a single machine equivalent one-line diagram similar to figure below: 2. Interconnection Transmission Line Point of Interconnection (substation or transmission line name): Line voltage = kv MVA Normal Rating = MVA MVA Emergency Rating = MVA R = ohm or pu on 100 MVA and line kv base (positive sequence) 8

X = ohm or pu on 100 MVA and line kv base (positive sequence) B = μf or pu on 100 MVA and line kv base (positive sequence) 3. Station Transformer (Note: If there are multiple transformers, data for each transformer should be provided) Nameplate Normal Rating (ONAN/ONAF/ONAF): / / MVA Emergency Rating (ONAN/ONAF/ONAF): / / MVA Nominal Voltage for each winding (Low /High /Tertiary): / / kv Available taps: (indicate fixed or with LTC), Operating Tap: Positive sequence ZHL: %, X/R on transformer self-cooled (ONAN) MVA Winding connection vector group (delta-wye-gnd, delta-delta, etc.): 4. Collector System Equivalent Model Collector system voltage = kv MVA Normal Rating = MVA MVA Emergency Rating = MVA R = ohm or pu on 100 MVA and collector kv base (positive sequence) X = ohm or pu on 100 MVA and collector kv base (positive sequence) B = μf or pu on 100 MVA and collector kv base (positive sequence) Attach a one-line diagram of the collector layout indicating conductor length, type, and size. 5. Inverter Step-Up Transformer Number of inverter step-up transformers: Individual Nameplate rating: MVA Individual Emergency rating: MVA Nominal voltage for each winding (Low /High): / kv Available taps: (indicate fixed or with LTC), Operating Tap: Positive sequence impedance (Z1) %, X/R on transformer self-cooled MVA Winding connection vector group (delta-wye-gnd, delta-delta, etc.): 6. Inverter and PV Module Data Number of Inverters: Nameplate Rating (each Inverter): / kw/kva Describe Inverter reactive capability control mode (i.e. voltage control, power factor, voltage droop control, etc): Describe Inverter reactive capability control range maximum and minimum values: Provide Reactive Capability Curve (Plot of Reactive Capability vs. Real Power) PV Inverter Short Circuit Current: Inverter Manufacturer and Model #: PV Module Manufacturer and Model #: 7. Plant Reactive Power Compensation Provide the following information for plant-level reactive compensation, if applicable: 9

Individual shunt capacitor and size of each: MVA Dynamic reactive control device, (SVC, STATCOM): Control range MVAr (lead and lag) Control mode (e.g., voltage, power factor, reactive power): Regulation point or bus Description of control strategy Operating characteristic Automatic control model pickup levels and time delay setpoints Indicate if the project includes a plant controller 8. Photo-Voltaic Generator Dynamics Data Provide dynamic models for transient stability analysis in PSLF format using models approved for use by WECC listed in the WECC Approved Dynamic Model Library found at www.wecc.biz. Provide low/high voltage-ride-thourgh dynamic models using an approved PSLF format or the equipment low/high voltage protection settings. Provide over/under frequency-ride-thourgh dynamic models using an approved PSLF format or the equipment over/under frequency protection settings. Please reference the WECC Solar Plant Dynamic Modeling Guidelines found at www.wecc.biz for additional information regarding the dynamics modeling needs of Idaho Power and WECC. Small Generating Facility Characteristic Data (for inverter-based machines) Max design fault contribution current: Instantaneous or RMS? Harmonics Characteristics: Start-up requirements: 10

General Information Enclose copy of site electrical one-line diagram showing the configuration of all Small Generating Facility equipment, current and potential circuits, and protection and control schemes. This one-line diagram must be signed and stamped by a licensed Professional Engineer if the Small Generating Facility is larger than 50 kw. Is One-Line Diagram Enclosed? Yes No Enclose copy of any site documentation that indicates the precise physical location of the proposed Small Generating Facility (e.g., USGS topographic map or other diagram or documentation). Proposed location of protective interface equipment on property (include address if different from the Interconnection Customer's address) Enclose copy of any site documentation that describes and details the operation of the protection and control schemes. Is Available Documentation Enclosed? Yes No Enclose copies of schematic drawings for all protection and control circuits, relay current circuits, relay potential circuits, and alarm/monitoring circuits (if applicable). Are Schematic Drawings Enclosed? Yes No Applicant Signature I hereby certify that, to the best of my knowledge, all the information provided in this Interconnection Request is true and correct. For Interconnection Customer: Signed Date: Printed 11