Reducing Total Harmonic Distortion with Variable Frequency Drives

Similar documents
Harmonics White Paper

Low Pass Harmonic Filters

Technical Paper. Harmonic Distortion in Data Centers

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

HARMONICS CAUSES AND EFFECTS

Economical Solutions to Meet Harmonic Distortion Limits[4]

Effective Harmonic Mitigation with Active Filters

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Drives 101 Lesson 5. Power Input Terminology for a VFD

Figure 1 Typical Inverter Block Diagram

VARIABLE FREQUENCY DRIVE

AC Drives and Soft Starter Application Guide

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Open-Delta Systems Affect Variable Frequency Drives

22.0 Harmonics in Industrial Power Systems

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Caution - leakage currents! Leakage currents in fault-current protected environments

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

VFDs and Harmonics in HVAC Applications

Matrix Drives Boost Power Quality and Energy Savings

Introduction to Rectifiers and their Performance Parameters

Application Guidance Notes: Technical Information from Cummins Generator Technologies

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Dynamic Harmonic Mitigation and Power Factor Correction

MIRUS International Inc.

How adjustable speed drives affect power distribution

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Harmonic Filters and Reactors

APPLICATION GUIDE. Harmonics in HVAC applications

Understanding Power Quality

Thyristorised Automatic Power Factor

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

7/15/2002 PP.AFD.08 1 of 28

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

AGN 026 Harmonic Voltage Distortion

ZENER ELECTRIC PTY LTD

Generator Advanced Concepts

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

Power Factor. Power Factor Correction.

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

An easy-to-use Precision Power Analyser. The touch of a button gives direct readout of true power and a host of other useful measurements.

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Active Harmonic Filter (AF3)

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

CHAPTER 4 HARMONICS AND POWER FACTOR

AC Sources for IEC 1000 Harmonics and Flicker Testing

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

NJWA - Harmonics and Drives Proper System Design

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

Harmonic Filters for Single Phase Equipment

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

FCL VOLTAGE & FREQUENCY CONVERTERS. FCL H SERIES - SINGLE PHASE - 2 to 30 kva H SERIES MODELS. AC SINGLE PHASE 2 TO 30 kva STATIC VARIABLE AC

Voltage and Current Waveforms Enhancement using Harmonic Filters

What does Power Factor mean?

Simulation & Hardware Implementation of APFC Meter to Boost Up Power Factor Maintain by Industry.

HARMONIC MITIGATIONCASE STUDY

Reduce harmonics in HVAC&R inverters through C-Less technology

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Analysis of Harmonic Distortion in Non-linear Loads

International Journal of Advance Engineering and Research Development

DC CIRCUITS Part I of III Parts. Part II installation. Part III troubleshooting

v o v an i L v bn V d Load L v cn D 1 D 3 D 5 i a i b i c D 4 D 6 D 2 Lecture 7 - Uncontrolled Rectifier Circuits III

Tuningintobetter power quality

Power Quality Monitoring and Power Metering Tutorial

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Est Static Frequency Converter. SFX 10kVA - 10MVA

Harmonic Distortion and Variable Frequency Drives

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

How Harmonics have led to 6 Power Factor Misconceptions

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Automatic Power Factor Correction by Using Synchronous Condenser with Continuous Monitoring.

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers

ABB n.v. Power Quality Products, October 2014

Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants

Fundamentals of AC Power Measurements

Learning Module 20: Adjustable Frequency Drives. 101 Basic Series

Application Note. Motor Bearing Current Phenomenon. Rev: Doc#: AN.AFD.17 Yaskawa Electric America, Inc August 7, /9

SHUNT ACTIVE POWER FILTER

UNDERSTANDING POWER QUALITY

Thermal Imaging, Power Quality and Harmonics

Est Static Frequency Converter. SFX 10kVA - 10MVA

Reliable power onboard and offshore

USE OF INVERTERS WITH COPELAND STREAM COMPRESSORS

POWER FACTOR CORRECTION AND ITS PITFALLS

GE Energy. Matrix Harmonic Filter Series D

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

VARIABLE FREQUENCY DRIVE

Distributed Energy Engineering

Transcription:

Reducing Total Harmonic Distortion with Variable Frequency Drives Low Harmonic Technology in Optidrive Eco

Overview Overview Both AC line chokes and DC link chokes have historically been used with Variable Frequency Drives (VFDs) as a method to reduce the harmonic distortion generated. An alternative method which can provide even better results is by reduction of the DC link capacitance. This paper provides an overview of the relative advantages and disadvantages of each method. Benefits of a reduced DC link capacitance compared to an AC or DC choke solution 1

Background Background Typical VFD Circuit Design DC Choke Input Recifier Pre-Charge DC Capacitors Output Stage (optional) The vast majority of VFDs in use around the world today are based around a broadly similar circuit design, as shown opposite: B C This consists of an input rectifier stage, which converts the incoming AC supply (either single or three phase) into a rectified DC supply. Capacitors are then added to smooth this supply and provide a stable DC voltage which can then be converted back to AC to provide power to the motor at variable frequency. L1 L2 L3 A The pre-charge circuit is used to provide soft charging of the DC capacitors only during the period when the drive is first powered on, after which it is bypassed. U V W Fig. 1 Typical VFD circuit design Circuit Characteristics The diagrams to the right show the typical voltage waveforms present at the indicated points on the circuit in Fig. 1: A When no load is present on the output, the DC capacitors will maintain the internal DC voltage level at point C close to the peak of the sinusoidal AC supply voltage. As load increases on the output, the capacitors are required to charge through the input rectifier and discharge through the output stage to maintain the output current to the motor, the DC voltage across the capacitors will ripple slightly. B C Fig. 2 Typical voltage waveform characteristics at the circuit points highlighted in Fig. 1 2

Background From the diagrams in Fig. 2, it can be seen that for a large part of the time, the DC link voltage level is higher than any of the rectified incoming AC supply phase voltages, and thus no current flows through the input rectifier. Current is in fact only drawn from the supply at close to the peak of the AC sinewave. This means that the current flow into the drive is not sinusoidal, like the current in an AC motor, but is a much more complex waveform. The nature of this waveform then depends largely on: The impedance of the incoming AC supply The impedance within the drive The total DC link capacitance The load on the output In a worst case situation Where: Supply impedance is very low (e.g. no AC line choke is fitted, and the capacity of the supply is large relative to the drive) The current flow at point A (input line current) will appear similar to this: A Drive impedance is very low (e.g. no internal DC link choke is fitted) DC link capacitance is high (a large amount of capacitance makes it easier to maintain a stable output voltage and absorb any regenerated energy from the load) Fig. 3 Typical current waveform characteristic at circuit point A in Fig. 1 Output load is high 3

Background Supply Current Harmonics All non-sinusoidal waveforms contain harmonics. Fourier theorem shows that a non-sinusoidal waveform consists of multiples of the fundamental frequency, which when combined together create the resulting waveform, e.g. on a 50Hz supply, the 3 rd harmonic would be 3 x 50 = 150Hz. Any waveform may be represented by overlaying multiple waveforms consisting of sine waves at harmonics of the base frequency. These harmonic currents are created in the supply by any non-linear load any load which does not draw current from the supply in a sinusoidal fashion. This includes equipment such as Switch Mode Power Supplies, Welders, UPS, Electronic Lighting and VFDs. As the level of harmonics increases within the supply, there can be unwanted side effects, such as conductor and transforming heating. In addition, the harmonic current levels can cause voltage distortion on the supply, which may also cause unwanted effects on other electrical equipment connected to the same mains supply. For this reason, it is desirable to keep the total level of harmonics present as low as possible, in order to minimise these effects. As the use of VFDs has become more prevalent, there has been an increasing focus on supply quality, to ensure that the level of harmonic distortion present on the supply does not become excessive, and cause unwanted side effects. In addition, Fig. 3 also shows that this current waveform has a high Crest Factor the relationship between the peak value and the RMS or average value in some cases, more than 2.5 times, which can cause further heating of supply conductors and nuisance tripping of protection devices such as circuit breakers. VFD Power Factor When looking at the Power Factor of a VFD, it is important to remember that there are two different definitions of Power Factor. These are commonly referred to as:- Displacement Power Factor The phase angle between the voltage and current measured at the load input Real or True Power Factor A measure of kw / KVA for a given load. With a linear load (e.g. any load that has a purely sinusoidal input current), such as a motor, which creates no harmonic distortion, the two measurements will be identical. However for non-linear loads such as VFDs, which do not have a sinusoidal input current, the Displacement Power Factor will be close to unity (as there is little phase angle difference between voltage and current) however the Real Power Factor (which includes the harmonic current content) will be much lower. This leads to some electricity supply companies imposing penalties on users with poor power factor. Improving the Real Power Factor will reduce the total input current, reducing the loading on transformers. By selecting products with high power factor at the design phase of a project, it can be possible to make significant overall cost savings, by reducing the total current leading to reduced transformer size, reduced busbar size, reduced cable sizes and so on. 4

Methods Methods to Improve Power Factor and Reduce Harmonic Distortion There are several measures that may be taken in order to reduce these harmonic current levels. Assuming that the basic supply network and load remain the same, these are: Increase the supply source impedance by adding an AC line choke Adding DC link chokes Reduce the total level of DC link capacitance Use higher pulse number rectifiers Add harmonic filtering Use complex rectifier solutions, typically referred to as Active Front End where the supply current may be controlled 5

Methods AC Line Chokes Adding an AC line choke in the main supply to a VFD provides a simple method of adding additional supply impedance. This impedance increases with frequency, and so is an effective step to reduce harmonic distortion and improve Real Power Factor. AC line chokes in general can be easily added to existing installations. Typically, AC line chokes are selected based on a % impedance this is the % of voltage drop across the choke when operating at rated load, e.g. if a choke is designed for example as 50A, 4% impedance, and is used with a 400 Volt supply, when the line current is 50A, the voltage drop across the choke will be 400V x 4% = 16 Volts. As AC line chokes are mounted upstream of the drive input, they provide excellent protection to the drive from mains borne spikes, which can be beneficial when drives are used in areas with poor supply quality, areas prone to lightning strikes, or where the input rectifier has inadequate rating or alternative protection in this case, the AC choke provides protection of the drive rectifier. Modern VFDs will incorporate rectifiers which are more resilient and are designed with sufficient capacity to no longer require this upstream protection, hence this benefit mainly applies to older drives. There should be no necessity to add an AC line choke as a band aid solution upstream of a correctly designed VFD with good quality components correctly selected for the intended purpose. AC line chokes add impedance in the incoming supply line to the drive. As this impedance is inductive, this highlights the key characteristics of the choke The stated line impedance % is only achieved when the choke is operating at rated current capacity, and is reduced at any load below this Considering the first point, VFDs are used when it is desired to be able to operate the motor over a range of frequencies and speeds. This means that the occasions when the motor operates at rated speed and load are infrequent; otherwise there would be no reason to install the drive. In applications such as fans and pumps, this ability to vary the drive output frequency and control motor speed provides significant energy saving opportunities, whereby a small reduction in output frequency provides a much greater reduction in the consumed power. Consider a Variable Torque Application, where the power consumed is proportional to the cube of the speed. If the motor speed is reduced from 100% to 90% of rated speed, the consumed power will reduce to 90% x 90% x 90% = 72.9%. Relating this back to the drive input, the supply voltage remains the same, thereby if the power reduces, the consumed current also reduces by the same amount. If a line choke were used, selected for 4% impedance at the full rated load of the drive, when speed is reduced by 10%, the line current is now only 72% of the maximum level, and hence the effectiveness of the choke is reduced. Further reduction in speed will provide further reductions in effectiveness of the choke. In addition, the drive system efficiency is also reduced, by the % impedance of the choke at the operating load. This means for a 4% choke, up to a 4% reduction in overall efficiency can be expected. Modern VFDs are typically around 98% efficient, hence adding a 4% choke will reduce this to 94% at full rated load. AC line chokes therefore make sense where protection of the drive input takes precedence over the drive system efficiency, or where it is desired to improve Real Power Factor or reduce harmonic distortion for an existing drive installation. By adding line impedance and reducing the voltage at the drive input, overall drive system efficiency is reduced by the % impedance of the choke As a consequence of the voltage drop, the torque available at the motor shaft will be reduced 6

Methods DC Link Chokes DC link chokes have been utilised in VFD design for many years, and provide similar benefits to AC line chokes, in terms of improving real power factor and reducing harmonic distortion. The key reason why DC chokes are used, as compared to AC chokes, is that by mounting the choke in the DC link of the drive, effectively the choke can be single phase as opposed to a 3 phase AC line choke, and the required inductance can be reduced, due to the choke being after the input rectifier and so the effective supply frequency is increased by six (each incoming AC supply phase has two peaks, and when all three phases are rectified, the DC ripple frequency is therefore six times the AC line frequency). This allows a reduction in size, weight and overall cost of the choke. In general, DC link chokes provide similar benefits to AC line chokes, in terms of reducing harmonic currents and improving Real Power Factor, however as the choke is now mounted after the input rectifier, no additional protection against spikes on the AC supply is provided. In general, this is not a concern, as drives designed with internal DC link chokes will have a rectifier circuit designed, rated and protected to ensure it is not easily damaged in this way. DC link chokes will have an overall negative impact on drive system efficiency. As the inductance is typically lower than an AC choke, the increase in losses is relatively lower, however there is still an overall drive system efficiency reduction when a DC link choke is used, particularly with non-linear or saturated chokes (sometimes referred to as Swinging chokes), where the inductance can change with current. In addition, the choke effectiveness, as with an AC line choke, is reduced with reducing load. Swinging chokes attempt to counter this by utilising a design which improves effectiveness at part load, however the effectiveness is still reduced at part load. Optidrive Eco Reduced DC Link Capacitance It can be seen from the description earlier that the design of a VFD with large DC link capacitance will always lead to high levels of harmonic currents. Historically, the large capacitance was necessary to provide a stable DC power supply inside the VFD which could be used to create the three phase output for the motor. The reduced DC link capacitance is achieved by using film capacitor technology as opposed to the electrolytic capacitors used in conventional VFDs. Additional benefits of the film capacitor technology include a longer capacitor lifetime and removing the need for capacitor reforming. Recent technology advances now allow significant reduction in the DC link capacitance of a VFD whilst improving overall efficiency, at the same time, this technology, also maintains excellent motor control whilst providing a significant reduction in full and part load harmonics. There are limitations, in that the technology can only be readily applied up to around 100 Amps load current at present, as above this current, the heat losses from the IGBT are too great, and result in unacceptable efficiency reduction, however below this point, the gains are significant. The benefit to reducing the DC link capacitance is a significant reduction in supply current harmonics at full and part load, which is of much more practical benefit since the majority of operation will be at part load. In addition, there is no reduction in the reliability of the design or resistance to mains voltage fluctuations, spikes or notches compared to a drive designed with a DC link choke, since the DC choke is not effective in these areas. By utilising higher PWM switching frequency, there are additional benefits such as reduced audible noise from the motor without derating. Improvements in modern day IGBTs allow the use of the higher switching frequencies required to achieve the necessary control without sacrificing overall efficiency. 7

Comparison Harmonic Method Reduction Comparison The graph to right shows the typical ithd values at full and part load. 1.2 1 It can be clearly seen that the reduced DC link capacitance significantly reduces the total harmonic distortion at full load, and has a much greater benefit at part load compared to a conventional DC choke or swinging choke. This results in reduced overall input current and reduced transformer heating effect. ithd(%) 0.8 0.6 0.4 0.2 0 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% With DC Choke With Swinging Choke With Reduced Capacitance (Optidrive Eco) % Rated Current Fig. 4 Typical ithd values at full and part load Power Factor 1 Optidrive Eco offers improved power factor over conventional VFDs under all loads: Power Factor 0.8 0.6 0.4 Conventional VFD Optidrive Eco 0.2 0 0% 20% 40% 60% 80% 100% Input Current/In Fig. 5 Power factor comparison Minimising Current Peaks 100% load Optidrive Eco input current waveform compared to the same conditions for a conventional VFD: The reduction in peak input currents result in lower stress on the rectifier stage. Conventional VFD Optidrive Eco Fig. 6 Current waveform comparison at 100% load 8

2015 Invertek Drives Ltd. All rights reserved. 85-RTHDE-IN V1.0