Energy Division. Bowthorpe LV/MV Surge Arresters

Similar documents
Our experience. Our products

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

Transformers connected via a cable Overvoltage protection

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Tab 8 Surge Arresters

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

Effective February 2017 Supersedes January 2012 (CP1122)

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters

Selection of MO surge arresters Overvoltage protection

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

EE 1402 HIGH VOLTAGE ENGINEERING

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester

Insulation Co-ordination For HVDC Station

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

TECHNICAL SPECIFICATION

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Protection against unacceptable voltages in railway systems

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

High voltage engineering

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

TECHNICAL SPECIFICATION

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Capacitive voltage transformers

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Earthing of Electrical Devices and Safety

VI 3 - i TABLE OF CONTENTS

Arrester 2050 JONATHAN WOODWORTH

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

ABSTRACTS of SESSION 6

APPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems

7P Series - Surge Protection Device (SPD) Features 7P P P

ENERGY /// POLYMERIC SURGE ARRESTERS (IEEE) BOWTHORPE EMP POLYMERIC SURGE ARRESTERS (IEEE)

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Electric Stresses on Surge Arrester Insulation under Standard and

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

TS RES - OUTSTANDING ISSUES

35 kv Class M.O.V.E. DirectConnect elbow arrester

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company

Substation Preventive Maintenance

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Capacitive voltage transformers

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

MEDIUM VOLTAGE TERMINATIONS CATALOGUE 2017

Modeling insulation in high-voltage substations

Lightning performance of a HV/MV substation

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

INTERNATIONAL STANDARD

Underground System Design TADP 547

HIGH VOLTAGE Insulation Coordination

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

INTERNATIONAL STANDARD

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

a Nexans company Catalogue 2012

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Tab 2 Voltage Stresses Switching Transients

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

CLU Arrester. Certified Test Report. IEEE Standard C

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

MEDIUM VOLTAGE TERMINATIONS CATALOGUE 2017

a Nexans company Catalogue 2012

Continuous C-III Series Units. ) 2ms Rectangular Wave 40 to 530 J Operating Ambient Temperature Range (T A

SPAE 010, 011 High Impedance Protection Relay

Overvoltage Protection of Light Railway Transportation Systems

MEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings

a Nexans company Catalogue 2014

Utility System Lightning Protection

Sales: Technical: Fax:

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

a Nexans company Catalogue 2009

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Spark Gap Surge Protectors For Lv Mains

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Type CP-S, CP-C & CP-A Switch mode

Transcription:

Energy Division Bowthorpe LV/MV Surge Arresters

Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early 1980's and since 1986 have a proven service experience across the globe, operating in the worlds toughest environments. Bowthorpe OCP silicone surge arresters have been designed and tested to meet our customers toughest environmental conditions and to meet the requirements of IEC60099-4. Our gapless zinc oxide polymeric arresters have been in service since 1994 and now the OCP ranges builds on this experience and know how. OCP is the latest gapless, zinc oxide arrester family from Bowthorpe. The OCP development was based on 25 years of internal experience in arrester design and manufacture within the Tyco Electronics Energy Division. The final OCP qualification was performed in independent laboratory facilities in Europe. OCP cores are manufactured using superior ZnO varistors, which display excellent thermal and current handling characteristics due to the guaranteed homogeneity of the varistor volume. This superior thermal behavior yields products with: Excellent TOV performance. Safe, non-shattering failure in the short circuit test by pre-failing to higher fault currents. High energy handling capability. Bowthorpe DLA/OCP benefits: Tested in accordance with IEC60099-4 at independent accredited laboratories Superior protection margins Direct molded housing to prevent moisture ingress Low residual voltages High-energy handling Superior TOV performance Safe non-shattering short circuit behavior to higher current levels Maintenance free Hydrophobic silicone housing: (Tracking and erosion resistant) Excellent cantilever and tensile performance Excellent mechanical, vibration and impact withstand capability Quality design and manu facturing, ISO 9001 and 14001 compliant TRUST Bowthorpe Surge Arresters TVC DLA1 OCP2 Uc 4.8kV 3-29kV 3-41kV I N 5kA 10kA 10kA Long duration energy (2 shots / kj/kv Uc) N/A 2.9 kj/kv Uc 6.0 kj/kv Uc Long duration waveform 250A / 2ms 250A / 2ms 530A / 2ms 10 second TOV, (U TOV / Uc) 1.5 1.43 1.35 High current short circuit 16kA 25kA 40kA Core technology TVC OCP OCP Please contact your local sales representative for higher Uc arresters. 2

At the core of the Bowthorpe OCP design is our improved ZnO varistor disk, which has superior thermal and electrical characteristics and stability. The resulting new varistor and OCP design combination has resulted in superior energy handling and TOV performance. The construction of the OCP design comprises of: 1 ZnO, (Zinc Oxide) varistors 2 Bowthorpe proprietary silicone housing 3 Flame retardant FRP structure 4 Corrosion resistant aluminium fittings The crimped structural construction ensures light weight product with optimal mechanical strength. The manufacturing process ensures void free construction and optimum interface sealing. This is achieved by bonding the silicone housing directly to the ZnO discs and aluminium fittings using a Bowthorpe proprietary bonding solution. 1 2 3 The silicone housing was developed using the knowledge accumulated over 35 years of internal materials science expertise and experience, resulting in an optimum shed profile and a material with excellent tracking and erosion resistance. Features of our new hydrophobic silicone OCP design are: Alternating sheds for superior pollution flash over resistance Superior TERT performance Constant voltage: 4.5kV, >360min - Stepped voltage: >300min - All eventual failures by erosion only, ie no tracking in step voltage test Housing tested to IEC 1000hr salt fog test 4 Excellent hydrophobicity Safe short circuit failure Superior TERT performance 3

Bowthorpe EMP, TVC Transient Voltage Clampers Introduction In the UK where severe lightning is often accompanied by poor pole earthing resistance, the secondary LV distribution system is subjected to high voltage surges due to lightning current seeking alternate ground paths through the low-voltage circuits. The typical mode of failure of a pole mounted transformer is for the low voltage winding to flash over to the transformer tank due to the relatively high voltage developed across the pole earth resistance. The high voltage arrester does not prevent this type of failure. However, to remove this source of failure (or back flash over) a TVC may be placed between the neutral bushing and the tank. Background Construction Transient Voltage Clampers are designed under the same principle as LV voltage surge arresters; however applications are more specific. M 12 Stainless Steel Termination What is a Transient Voltage Clamper, TVC? A TVC is used to protect against the internal failure of a pole mounted transformer (PMT) due to back flashover between the transformer tank and the LV winding bushing. A back flashover on a PMT will cause permanent damage to the transformer internal solid insulation. Zinc Oxide Varistor Core Conditions of Use? 1) TVC s are useful when there is very high resistivity pole grounding conditions e.g. hot, sandy, rocky ground. Under these soil conditions an earth resistance of 10 ohms or less may be difficult to achieve; resistance maybe variable throughout the year. 2) TVC s are useful when the LV earth downstream from the PMT is lower than at the pole earth resistance. 3) Best used in conjunction with HV and LV surge arresters (cannot be used instead). UV Stable Tracking Resistant Housing Current-voltage characterisitc for Zno varistor Principle of Operation TVCs incorporate a gapless metal oxide varistor, MOV design that under steady state conditions maintains the line-to-ground voltage across the TVCs terminals. When overvoltages occur, the TVC conducts current to earth, limiting the overvoltage to below the required protection levels. Upon passage of the overvoltage condition, the TVC returns to a highly non-linear steady state condition that conducts very minimal 10 s of Hz power current. Voltage (V/mm) Pre-breakdown region Protection against Lightning over-voltages Protection against Switching over-voltages 20 C 60 C 120 C Breakdown region Continuous operating voltage Current (Amps/mm 2 ) Rated voltage High current region 4

Bowthorpe EMP, TVC Transient Voltage Clampers Application Diagram Lightning Strike - 5 ka HV Winding LV Winding Single / 3 Phase Distribution Line Surge Arrester on HV side Neutral Bushing TVC-1 Tank of Transformer 10 Ohms Ground at Pole Mounted Transformer Ground at Consumer Premises Example Problem: A moderate lightning current of 5kA flowing to earth into a resistance of 10 ohms will raise the tank of the transformer to 50kV as V = IR. Typically the impulse breakdown voltage of the LV winding to the transformer case is 30kV. The tank voltage due to 10 ohms earth resistance can cause a breakdown between the tank and a low voltage bushing of the transformer. Any back flashover will drive high current through the low voltage windings when striking the phase connections. These high currents are driven by the power frequency flow current. Solution: To remove the back flashover a suitable device must be connected between the neutral bushing and the tank of the transformer, hence a TVC should be installed. In order to be compatible with standard auto recloser operations in the event of a fault, the device must be able to withstand the phase to earth voltage for at least 10 seconds. LV and HV surge arresters cannot be used instead of a TVC. LV Surge arresters: The LV arrester should be used in lightning prone exposed areas to give additional protection. They should be installed on the low voltage system, on the first pole down stream from the transformer. HV Surge arresters: The HV arrester should be fitted to the high voltage bushings (connections under 300mm in length to limit voltage drop). The installation of the HV arrester prevents damage to the insulation on the HV winding and the transformer case. Note: The HV arrester will not stop back flashovers across the low voltage bushings, but will limit the power follow-current, hence this is the reason why TVC s should be used. Tips: To reduce the voltage on the tank of the transformer, it is advisable to have low values of earthing resistance connected to the tank, approximately 5 ohms or less. To achieve an optimum overvoltage protection, connecting leads should be as short as possible. 5

Bowthorpe EMP Distribution Lightning Arresters DLA1 series Application: Protection of MV networks and equipment from lightning and switching surge related over-voltages in areas with relatively high iso-keraunic levels. Suitable for both outdoor and indoor use to protect transformers and cable end terminations. Generic technical data: DLA1 series Rated discharge current (8/20µs): 3-29kV Uc 10kA Line discharge class 1 according to IEC 60099-4 Long duration current impulse (2000µs): 250A High current short circuit: (pre-failing method) 25kA (Safe non-shattering failure mode) Energy 2 Long duration impulses: 2.9kJ/kVUc Bowthorpe DLA1 benefits: Tested in accordance with IEC60099-4 at independent accredited laboratories Superior protection margins Direct molded housing to prevent moisture ingress Low residual voltages High-energy handling Superior TOV performance Safe non-shattering short circuit behavior to higher current levels Maintenance free Hydrophobic silicone housing: (Tracking and erosion resistant) Excellent cantilever and tensile performance Excellent mechanical, vibration and impact withstand capability Quality design and manu facturing, ISO 9001 and 14001 compliant TRUST Bowthorpe Surge Arresters TOV of DLA1 with single shot high current prior energy 1.55 1.50 1.45 TOV Curve 1.40 1.35 Uw / Uc 1.30 1.25 1 10 100 1000 10000 Time (s) Temperature of samples (pre-heated): 60º C according to IEC 60099-4, Ed 2.0 2004. TOV Curve applies to an arrester which has a pre-stress applied prior to TOV verification. This pre-stress is equivalent to one high current impulse as per the operating duty test. Uw = TOV withstand voltage; Uc = continuous operating voltage 6

Bowthorpe EMP Distribution Lightning Arresters DLA1 series DLA1 U continuous U rated U residual in kv when tested to the following impulse waveforms kv(r.m.s) kv(r.m.s) Lightning (8/20µs) Steep lightning (1/20µs) Switching (30/60µs) 5kA 10kA 20kA 10kA 125A 500A 3 3 3.7 9.80 10.50 11.89 11.49 7.63 7.97 4 4 5.0 13.07 14.00 15.85 15.32 10.17 10.62 5 5 6.2 16.34 17.50 19.81 19.15 12.71 13.28 6 6 7.5 19.61 21.00 23.77 22.98 15.25 15.94 8 8 10.0 26.14 28.00 31.70 30.64 20.34 21.25 9 9 11.2 29.41 31.50 35.66 34.47 22.88 23.90 10 10 12.5 32.68 35.00 39.62 38.30 25.42 26.56 12 12 15.0 39.22 42.00 47.54 45.96 30.50 31.87 15 15 18.7 49.02 52.50 59.43 57.45 38.13 39.84 18 18 22.5 58.82 63.00 71.32 68.94 45.76 47.81 20 20 25.0 65.36 70.00 79.24 76.60 50.84 53.12 21 21 26.2 68.63 73.50 83.20 80.43 53.38 55.78 22 22 27.5 71.90 77.00 87.16 84.26 55.92 58.43 24 24 30.0 78.43 84.00 95.09 91.92 61.01 63.74 29 29 36.0 94.80 101.50 114.90 111.10 73.70 77.00 DLA1-xxS; Standard housing parameters DLA1 Impulse Power frequency Flash Creepage Height voltage voltage withstand, over L 1.2/50µs wet distance (kv) (kv) (mm) (mm) (mm) 3 106 47 176 379 183 4 106 47 176 379 183 5 106 47 176 379 183 6 106 47 176 379 183 8 106 47 176 379 183 9 106 47 176 379 183 10 106 47 176 379 183 12 106 47 176 379 183 15 128 57 214 503 220 18 154 68 254 629 260 20 154 68 254 629 260 21 180 80 293 755 299 22 180 80 293 755 299 24 180 80 293 755 299 29 205 91 334 882 334 Tested in accordance with IEC 60099-4, Ed 2.0 2004 L DLA1-xxL; Extended housing parameters DLA1 Impulse Power frequency Flash Creepage Height voltage voltage over L 1.2/50µs withstand, wet distance (kv) (kv) (mm) (mm) (mm) 3 128 57 214 503 214 4 128 57 214 503 214 5 128 57 214 503 214 6 128 57 214 503 214 8 128 57 214 503 214 9 128 57 214 503 214 10 128 57 214 503 214 12 128 57 214 503 214 15 154 68 254 629 254 18 180 80 293 755 293 20 180 80 293 755 293 21 205 91 334 882 334 22 205 91 334 882 334 24 205 91 334 882 334 97mm 119mm Notes: Mechnical strength data: Cantilever Nm 250 Tensile kn 2 Torque Nm 50 For accessory and ordering information, please refer to page 11 7

Bowthorpe EMP Open Cage Polymeric arresters OCP2 series Application: Protection of MV networks, sensitive equipment and substations from lightning and switching surge related over-voltages in areas with relatively high iso-keraunic levels. Generic technical data: OCP2 series Rated discharge current (8/20µs): 3-41kV Uc 10kA Line discharge class 2 according to IEC 60099-4 Long duration current impulse (2000µs): 530A High current short circuit: (pre-failing method) 40kA (Safe non-shattering failure mode) Energy 2 Long duration impulses: 6.0kJ/kVUc Bowthorpe EMP OCP benefits: Tested in accordance with IEC60099-4 at independent accredited laboratories Superior protection margins Direct molded housing to prevent moisture ingress Low residual voltages High-energy handling Superior TOV performance Safe non-shattering short circuit behavior to higher current levels Maintenance free Hydrophobic silicone housing: (Tracking and erosion resistant) Excellent cantilever and tensile performance Excellent mechanical, vibration and impact withstand capability Quality design and manu facturing, ISO 9001 and 14001 compliant TRUST Bowthorpe Surge Arresters TOV for OCP2 with prior energy 1.6 1.5 1.4 TOV Curve 1.3 1.2 Uw / Uc 1.1 1.0 1 10 100 1000 10000 100000 Time (s) Temperature of samples (pre-heated): 60 C according to IEC 60099-4, Ed 2.0 2004. TOV Curve applies to an arrester which has a pre-stress applied prior to TOV verification. This pre-stress is equivalent to two long duration current impulses having duration of 2000µs and total energy equal to 6.0 kj/kv Uc. Uw = TOV withstand voltage; Uc = continuous operating voltage 8

Bowthorpe EMP Open Cage Polymeric arresters OCP2 series OCP2 U continuous U rated U residual in kv when tested to the following impulse waveforms kv(r.m.s) kv(r.m.s) Lightning (8/20µs) Steep lightning (1/20µs) Switching (30/60µs) 5kA 10kA 20kA 10kA 125A 500A 3 3 3.7 9.18 9.72 10.84 10.10 7.37 7.76 4 4 5.0 12.24 12.96 14.46 13.47 9.83 10.35 5 5 6.2 15.30 16.20 18.07 16.84 12.29 12.94 6 6 7.5 18.36 19.44 21.68 20.21 14.75 15.53 8 8 10.0 24.48 25.92 28.91 26.94 19.66 20.70 9 9 11.2 27.54 29.16 32.53 30.31 22.12 23.29 10 10 12.5 30.60 32.40 36.14 33.68 24.58 25.88 12 12 15.0 36.72 38.88 43.37 40.42 29.50 31.06 15 15 18.7 45.90 48.60 54.21 50.52 36.87 38.82 18 18 22.5 55.08 58.32 65.05 60.62 44.24 46.58 20 20 25.0 61.20 64.80 72.28 67.36 49.16 51.76 21 21 26.2 64.26 68.04 75.89 70.73 51.62 54.35 22 22 27.5 67.32 71.28 79.51 74.10 54.08 56.94 24 24 30.0 73.44 77.76 86.74 80.83 58.99 62.11 29 29 36.3 88.74 93.96 104.81 97.67 71.28 75.05 OCP2-xxS; Standard housing parameters OCP2 Impulse Power frequency Flash Creepage Height voltage voltage withstand, over L 1.2/50µs wet distance (kv) (kv) (mm) (mm) (mm) 3 145 47 176 380 183 4 145 47 176 380 183 5 145 47 176 380 183 6 145 47 176 380 183 8 145 47 176 380 183 9 145 47 176 380 183 10 145 47 176 380 183 12 145 47 176 380 183 15 165 57 214 505 220 18 180 70 254 632 260 20 180 70 254 632 260 21 200 80 293 758 299 22 200 80 293 758 299 24 200 80 293 758 299 29 230 95 334 885 340 Tested in accordance with IEC 60099-4, Ed 2.0 2004 L OCP2-xxL; Extended housing parameters OCP2 Impulse Power frequency Flash Creepage Height voltage voltage withstand, over L 1.2/50µs wet distance (kv) (kv) (mm) (mm) (mm) 3 165 57 214 505 220 4 165 57 214 505 220 5 165 57 214 505 220 6 165 57 214 505 220 8 165 57 214 505 220 9 165 57 214 505 220 10 165 57 214 505 220 12 165 57 214 505 220 15 180 70 254 632 260 18 200 80 293 758 299 20 200 80 293 758 299 21 230 95 334 885 340 22 230 95 334 885 340 24 230 95 334 885 340 97mm 119mm Notes: Mechnical strength data: Cantilever Nm 350 Tensile kn 2 Torque Nm 50 For accessory and ordering information, please refer to page 11 9

Bowthorpe EMP Open Cage Polymeric arresters OCP2 series OCP2 U continuous U rated U residual in kv when tested to the following impulse waveforms kv(r.m.s) kv(r.m.s) Lightning (8/20µs) Steep lightning (1/20µs) Switching (30/60µs) 5kA 10kA 20kA 10kA 125A 500A 29 29 36.3 88.74 93.96 104.81 97.67 71.28 75.05 30 30 37.5 91.80 97.20 108.42 101.04 73.74 77.64 31 31 38.8 94.86 100.44 112.03 104.41 76.20 80.23 33 33 41.3 100.98 106.92 119.26 111.14 81.11 85.40 36 36 45.0 110.16 116.64 130.10 121.25 88.49 93.17 39 39 48.8 119.34 126.36 140.95 131.35 95.86 100.93 40 40 50.0 122.40 129.60 144.56 134.72 98.32 103.52 41 41 51.3 125.46 132.84 148.17 138.09 100.78 106.11 OCP2-xxM; Standard housing parameters OCP2 Impulse Power frequency Flash Creepage Height voltage voltage withstand, over L 1.2/50µs wet distance (kv) (kv) (mm) (mm) (mm) 29 204 98 339 970 343 30 204 98 339 970 343 31 228 110 378 1125 383 33 228 110 378 1125 383 36 250 122 418 1279 423 39 250 122 418 1279 423 40 250 122 418 1279 423 41 250 122 418 1279 423 Tested in accordance with IEC 60099-4, Ed 2.0 2004 L OCP2-xxML; Extended housing parameters OCP2 Impulse Power frequency Flash Creepage Height voltage voltage withstand, over L 1.2/50µs wet distance (kv) (kv) (mm) (mm) (mm) 29 228 110 378 1125 383 30 228 110 378 1125 383 33 250 122 418 1279 423 36 250 122 418 1279 423 107mm 137mm Notes: Mechnical strength data: Cantilever Nm 350 Tensile kn 2 Torque Nm 50 For accessory and ordering information, please refer to page 11 10

Bowthorpe EMP OCP2 and DLA1 accessories OCP2 and DLA1 series naming and order query description: Example: OCP = Open Cage Polymeric OCP2 12S MEL For installation clearances phase-phase (a) and phase-ground (b) please refer to IEC 60071-2. Arrester type: DLA1 = 10kA, class 1 (3-29 kv) OCP2 = 10kA, class 2 (3-41 kv) b Uc (kv) 3-29 30-41 Standard creepage S M Extended creepage L* ML** * available up to Uc = 24 kv **available up to Uc = 36 kv a a Accessory selection M = Mounting bracket E = Earth connection L = Line connection Line lead accessories F M N Q V Arrester Type = Continuous Operating Voltage Uc in kv 03 04 05 06 08 09 10 12 15 18 20 21 22 24 29 30 31 33 36 39 40 41 DLA1 0 12 OCP2 All accessories use M12 stainless steel studs Mounting accessories A B C N T Ground lead accessories D F M N V Additional accessory options available on request. Please contact: surgearresters@tycoelectronics.com with your specific requirement. 11

Thank you for reading this data sheet. For pricing or for further information, please contact us at our UK Office, using the details below. UK Office Keison Products, P.O. Box 2124, Chelmsford, Essex, CM1 3UP, England. Tel: +44 (0)330 088 0560 Fax: +44 (0)1245 808399 Email: sales@keison.co.uk Please note - Product designs and specifications are subject to change without notice. The user is responsible for determining the suitability of this product.