Control equipment. Regula 1.4. lindab we simplify construction

Similar documents
Device connection and commissioning can only be carried out by qualified professionals. Always make the connections while the power is switched off.

Modbus Integration Integration for Modbus Functionality for VT8300 Series

Fan Coil Actuator FCA 2

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

Room Temperature Controllers. for heating and cooling systems

SRC-110 Series Zone Controllers with Modbus RTU

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

Control solutions Biofloor

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems

OP5U. Pre-programmed, configurable controller for simple applications

ELECTRONIC THERMOSTAT: T951

ELECTRONIC THERMOSTAT: T920

Analogue temperature controllers

Room Temperature Controllers. for heating and cooling systems

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

NRT 105: Electronic fan-coil controller, equiflex

Room Temperature Controllers. for heating and cooling systems

CONTROL Room. Room product for Swegon s WISE system for demand-controlled ventilation. Quick facts Room control against temperature, CO 2

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

About AB Industrietechnik

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

PROCESS & TEMPERATURE CONTROLLERS

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

VT8600 Series User Interface Guide Rooftop Unit, Heatpump and Indoor Air Quality Controller

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation

APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1

TAC 2112 Manual (GB),

APPENDIX APPENDIX A 1

Modbus communication module for TCX2: AEX-MOD

SE8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

Intelligent Compact Controller

Modbus VAV Controller Configuration Properties

User manual. KNX MultiController DALI. Article number: 5410x / 5411x. function Technology AS

Application Programs Descriptions

CR24-.. Single room controllers

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

SE7000 Series Application guide

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

Application Sheet Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Application Sheet Active chilled beam with variable fan, cooling coil and hot water radiator on triac output

SRC-200 Series Climate Controllers with BACnet MS/TP

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex

TLC3-BCR-U Series Thermostat

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Communicative heating controller

SRC-21x Series Climate Controllers with BACnet MS/TP

W7100A-E Discharge Air Controller

User Manual. KNX MultiLight Dali. Article number: function Technology AS. Picture: KNX MultiLight products

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components

DTAP. universal programmable controller. Универсален програмируем контролер

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature

Arcus-EDS. Application Description. SK0x-Txxx

SRC-110 Series Zone Controllers. BACnet MS/TP. Product sheet CT2.143 SRC-110-BAC

1 Digital input (24Vac or dry contact) Inputs

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

EY-EM 527: Remote I/O module, ecolink527

Smartzone LCD TOUCHPAD USER GUIDE.

MICRO-CONTROLLER X (48 48 mm)

KNX Room temperature controller

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry

OPTIVENT ULTRA VAV damper CONTROL UNIT FOR MODBUS 227VMZ-MB

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

Radiocontrol F. Floor Heating Controller Radio control system for floor heating

Series Valve Temperature Controller. Instruction Sheet

General Purpose Digital Controllers Specifications

SeeTool - Solutions for KNX

LK Wireless Room Control Cq

B850 Boiler House Energy Monitor

DC1010/DC1020/DC1030/DC1040

ECL-VAV-N. Features & Benefits

Room Temperature Controller with Built-in Room Sensor 1 Feb 2002

CONTROL MANUAL. Dry-Pic 09PE - 09VE

vacon 100 flow ac drives application manual

AEROCONNECT 1B NA C Control manual

OVEN INDUSTRIES, INC. Model 5C7-362

EY-EM 522, 523: Remote I/O module, ecolink522, 523

BACNET LISTE - CORRIGO VERSJON 3.7

ECP-103 Series. ECP-103 Series. 10-Point Free Programmable Controller. Applications. Features

Metasys Zoning Package Commissioning

Conductivity Transmitter N-LF V AC

NX Series Inverters. HVAC Pocket Programming Guide

Sentido KNX Manual. Sentido KNX. Manual. basalte bvba hundelgemsesteenweg 1a 9820 merelbeke belgium

the compact PCD7.L79xN room controller

Technical manual GS 4x.00 knx application description air quality sensor

B850 Boiler House Energy Monitor

Room Controller Thermostat

Analog outputs (option) Output 1 + 2: 0(4) 20 ma or 0 10 V

R PROFLAME Instruction Book Collection

BACnet PTEC Controller VAV with CO2 Monitoring, Parallel Fan and AOV or Floating Point Heating, Application 6682

General Specifications

R7420B. MicroniK 100 HONEYWELL TEMPERATURE CONTROLLER PRODUCT DATA GENERAL FEATURES

Self-learning Room Temperature Controller Receiver

Transcription:

Control equipment Regula..0 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).

Content Description Page Overview... Regula functions... Program description.... Water.... VAV.... ehybrid.... Change Over digital.... Change Over sensor.... Pascal VAV supply.... Pascal VAV exhaust.... Pascal VAV Water... Operating modes... Display handling and indications... Parameter menu... CO sequence... 0 Occupancy button... 0 Presence detector... 0 Electrical Wiring diagrams... Regula Secura... Regula Connect basic... Regula Connect Multi... Technical data, actuators and valves... Accessories... 0 Calculation of the transformer... 0

Control equipment Regula. Overview Use Customized control equipment for water and airborne climate systems with individual regulation. Regula Duo controls heating and cooling in sequence. Regula Combi can control heating and cooling in sequence, VAV in combination with heating and cooling, Change-Over systems, as well as communicate with Modbus/EXOline/Bacnet Master systems. Regula Connect Basic, Multi and Pascal are connection cards for the flexible connection of facade systems and chilled beams. For further informations on the Regula connect Pascal, please see the Lindab Pascal catalogue. Regula Secura is a condensation guard for installation in façade systems and chilled beams, which prevents condensation forming. Regula Duo and Regula Combi are available for installation on the wall. Regula Combi can be integrated in a chilled beam directly also. Regula Secura and the Regula Connect cards are integrated in or on our products. Regula Duo Worth noting Regula Combi is a microprocessor-based PI controller with pulsing ON/OFF signal. Regula Combi can control with ON/OFF and/or 0- V signal. Regula Combi can control chilled beams in combination with VAV devices. Regula Combi has pre-defined operating programs. Regula Combi is provided with inputs and outputs. Regula Combi communicates via Modbus, EXOline or Bacnet. Regula Secura prevents condensation. Regula Combi REGULA CONNECT Multi Rc LINK N = Neutral L = Load S = Signal Rc LINK RC in/out CO in - S CO in - S CO out - N CO out - L REGULA CONNECT Basic N = Neutral L = Load S = Signal Presence in - S Presence in - S Presence out - N Presence out - L Damper out - S Damper out - N Damper out - L Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link_s Cooling link_s Heating link_s Cooling link_s Supply in - N Supply in - V - L Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link - S Cooling link - S Heating link - S Cooling link - S Supply in - N Supply in V - L LINDAB LINDAB Regula Secura Regula Connect Basic Regula Connect Multi --0

Control equipment Regula. Regula Duo Function Regula Duo is used for room individual temperature control, where the desired temperature can be adjusted easily within ± C using the control knob. The standard ting is C. The point for the desired value can be adjusted with a potentiometer between and C. Regula Duo is available for installation directly on the wall. Regula Duo controls cooling and heating. A maximum of actuators can be connected to the same control centre. The actuators are mounted on heating and cooling valves that open and close the heating or cooling circuits, respectively, depending on whether the room needs to be heated or cooled. The control signal governing this process is transmitted by Regula Duo, which compares the desired value (the desired temperature) and the actual value (the actual temperature) using built-in or external temperature sensor. The system continuously strives to equalise these temperature values as quickly as possible. Regula Combi Function Regula Combi is a zone controller for integrated installation in products or directly on the wall. Regula Combi has a built-in temperature sensor and can use input from presence sensor, CO sensor, condensation detector and an external temperature sensor (for Change Over systems). For thermal on/off actuators Regula Combi controls digitally with time proportional pulses. By pulsing, the opening degree of the actuator (and its valve) is varied. The period time (s) is the sum of the on and off output times on the output. The controller varies the on and off output times proportionally depending on the output signal demand to the actuator. Alternatively 0-V output can be chosen. A maximum of actuators can be connected to the same controller. Through its three outputs, Regula Combi can control only heating and/or cooling, as well as heating, cooling and forced cooling in sequence. The controller has four inputs. One for presence sensor, one for CO (0-V), one for condensation detector and one for an external temperature sensor (PT00). Regula Combi has predefined programs which can be selected in the Service menu in the display. The temperature point value can be adjusted up and down from the basic point values via the display (default +/- C) in steps of 0. C. On cooling demand it will control according to the cooling point, and on heating demand it will control according to the heating point. The point change takes place halfway between the points with a hysteresis of 0. C. Regula Combi can also be to operate Change Over systems, where the change over happens either via a digital signal or via an external temperature sensor in the heating/cooling media. The display has indications for heating/cooling state, actual temperature and point temperature when pressing increase/decrease buttons, and icons for the operating modes. Regula Secura Function Regula Secura is a condensation guard for both chilled beams and facade systems, which works together with electronic control systems such as Regula Combi or any other equipment with thermoelectric actuators. If there is condensation on the supply pipe, Regula Secura s humidity sensor gives a signal that cuts the power to the cooling. Regula Connect Basic and Multi Function Regula Connect Basic and Multi are two connection cards that provides flexible connection for chilled beams or facade systems. Regula Connect Basic and Multi consists of a connection card with connectors for main cables, thermostat cables and terminal blocks for actuator cables. Regula Connect Multi also offer connectors for CO and presence sensors plus a damper output for air flow regulation. Regula Combi Predefined programmes The controller has predefined programs which is selectable in the Parameter menu (Service) on the display. The parameter menu is accessed by simultaneously holding the increase and decrease buttons depressed for about seconds and then pressing the increase button twice, then the Service indication will be displayed. First the display will show the parameter number 0. By pressing the Occupancy button the 0 will be replaced by the program number. Scroll between programs by using the increase and decrease buttons. To acknowledge and store a program value, press the Occupancy button again, the display then returns to showing the parameter number 0. Otherwise to retrieve the original value, i.e. the value before change, press the increase and decrease buttons at the same time, then the original value is shown on the display.. Water (default). VAV. ehybrid. Change Over digital. Change over sensor. Regula Connect Pascal VAV supply. Regula Connect Pascal VAV exhaust. Regula Connect Pascal VAV water As a supplement program 0 can be chosen. This will apply the standard mode of Regin Regio Midi RC-CDOC and will activate the full parameter list with Regins default tings. --0

Control equipment Regula. Program descriptions. Water The regulation of temperature takes place in sequences with heating, cooling and forced (cooling) ventilation by signals from the universal outputs UO (heating), UO (cooling). The proportional part of the temperature regulation is shown diagram. Set points are adjustable. The universal output UO (forced cooling ventilation) will be activated with signal by pressing the Occupancy button (Bypass operating mode). The universal outputs for UO and UO are default to thermal on/off actuators. Heating and cooling actuators (UO and UO) are exercised every h. Operating mode Standby occurs after 0 min (adjustable) if a presence sensor is connected and signal is given, then the neutral zone increases with +/- C (to heating point C and cooling point C). UO UO 0 0 Diagram a Water program variants a) Water Heating/Cooling and separate VAV forced Cooling Parameter changes: P to value = Heating/Cooling/ VAV. UO is default 0-V but with Min flow at Y output P =, so the signal is V. If UO ascends to signal, Bypass operating mode will be activated for min (adjustable). Bypass can also be activated by pressing the Occupancy button once. Off mode will result in signal and thus closing the damper. If connecting a CO sensor (CORT) then activate the analogue input AI by changing P to value = CO- sensor. UO will be affected according to the CO sequence. CO levels are with P and P. The major requirement from the second part of the cooling sequence and the CO sequence will control the UO signal. UO UO UO VAV 0 0 Diagram b b) Water Heating/Cooling and separate on/off damper Parameter changes: P to value =Forced vent. Digital, P to value =Occupied and P to =Bypass. By connecting a relay sensor (presence, switch or CORT-R) to digital input DI, Regula Combi will switch between Occupied and Bypass. (For CORT-R CO levels are in the sensor). At Bypass UO will open the on/ off damper with V AC. (Note that Neutral and Load on the on/off damper must be switched). Bypass can also be activated by pressing the Occupancy button once. c) Water Heating/Cooling with VAV as first Cooling sequence Parameter changes: P to value =Heating/Cooling/ VAV, P to the desired max UO output at heating e.g. and P to =Y activates before Y. With a VAV damper mounted on the supply duct to an active chilled beam, it is recommendable to have VAV as the first cooling sequence. The VAV damper could also be on a separate duct. UO is default 0-V but with Min flow at Y output P=, so the signal is V. When there is heating on UO, the VAV output UO will follow the UO signal to the desired max output at heating, e.g.. If UO ascends to signal, Bypass operating mode will be activated for min (adjustable). Bypass can also be activated by pressing the Occupancy button once. Off mode will result in signal and thus closing the damper. If connecting a CO sensor (e.g. CORT) then activate the analogue input AI by changing P to value =CO- sensor. UO will be affected according to the CO sequence. CO levels are with P and P. The major requirement from the second part of the cooling sequence and the CO sequence will control the UO signal. --0

Control equipment Regula. UO UO VAV UO 0 0 Diagram c. VAV The regulation of temperature takes place in sequences with heating and cooling by signals from the universal outputs UO (heating) and UO (cooling). The proportional part of the temperature regulation is shown in diagram. Set points are adjustable. The universal outputs UO and UO will be activated with signal by pressing the Occupancy button (Bypass operating mode). The universal outputs for UO, UO and UO are default to 0-V. Heating and cooling actuators (UO and UO) are exercised every h. The min flow at cool output (UO) is to (default), so the cooling sequence will result in signals from 0-. By pressing the Occupancy button for more than seconds operating mode Off will occur, that will change the UO signal to regardless of cooling or heating demands. This match Lindab volume flow regulator functions. Operating mode Standby occurs after 0 min (adjustable) if a presence sensor is connected and signal is given, then the neutral zone increases with +/- C (to heating point C and cooling point C). Bypass operating mode with UO and UO = signal will be activated for min (changeable) by pressing the occupancy button once (for less than seconds). UO UO 0 0 Diagram VAV program variants a) VAV with CO sensor Parameter changes: P to value = CO-sensor. When connecting a CO sensor (e.g. CORT) activation of the analogue input AI is needed. UO will be affected according to the CO sequence. CO levels are with P and P. The major requirement from the cooling sequence and the CO sequence will control the UO signal. b) VAV with air duct heating Parameter changes: P to value = Heating/Cooling with VAV-control, P to the desired max UO output at heating e.g.. --0

Control equipment Regula. This will activate a heating function for UO. It will allow UO to follow the heating signal UO to a free chosen max level (P) when there is heating demand. This should only be used when having heated air (above room temperature) in the duct by connecting UO to a duct heater. When the heating function on UO is activated, forced cooling ventilation by pressing the Occupancy button will not lead to signal on UO. UO UO 0 0 Diagram b c) RCW- blade control Parameter changes: P to value C, P to value C, P to value 0s and P to value =External sensor. Regula Combi can control the RCW- blade angels when connecting the -V modulating motor to UO. A duct sensor (TG-K/PT00 or TG-KH/PT00) must be mounted in the supply duct and connected to the analogue input AI. The blade angles will then be controlled according to diagram c. UO. ehybrid The regulation of temperature takes place in sequences with heating and cooling by signals from the universal outputs UO (heating) and UO (cooling). The sequence of UO is depending on whether there is occupancy or not. At operating mode Occupied UO =. At Standby UO is following the cooling signal UO and the heating signal UO to a changeable max limit (default is, so as default the UO damper will stay half open at full heating demand). See the proportional part of the temperature regulation sequences in the diagrams. Set points are adjustable. The universal outputs for UO and UO are default to thermal on/off actuators. UO is default to 0-V. Heating and cooling actuators (UO and UO) are exer cised every h. Operating mode Standby occurs after 0 min (adjustable) if a presence sensor is connected and signal is given, then the neutral zone increases with +/- C (to heating point C and cooling point C). UO 0 0 Diagram (Occupied) UO UO VAV UO UO UO VAV 0 + 0 0 Diagram c 0 Diagram (Standby) --0

Control equipment Regula.. Change Over digital Change-over is a function, which makes it possible to use the same pipe/duct for both heating and cooling, depending on requirements during for example summer (cooling output) and winter (heating output). Sequences for temperature, CO and occu pancy functions are as Program Water. Universal outputs for UO and UO are default to 0-V. UO is not active. When using the digital signal input DI (potential-free contact), closing the contact switches the change-over function and s the output UO to cooling sequence. On open contact, the change-over function s the output UO to heating. UO 0 0 Diagram Winter DI open UO Summer DI closed. Change Over sensor Change-over is a function, which makes it possible to use the same pipe/duct for both heating and cooling, depending on requirements during for example summer (cooling output) and winter (heating output). Sequences for temperature, CO and occupancy functions are as Program Water. Universal outputs for UO and UO are default to 0-V. UO is not active. A sensor (PT00) must be connected to the analogue input AI. The Pt00-sensor connected to AI must be mounted so that it senses the temperature in/on the heating/ cool ing media. The change-over function will measure the difference between the room and media temperature. As long as the heat valve is more than 0 % open, or every time a valve exercise is performed, the difference between the media and room temperature will be calculated. If the temperature difference is lower than the configured value (differs for Heating and Cooling mode), the control mode will change. The default tings for the difference between Heating and Cooling change-over are K (P) and K (P) respectively. UO UO Winter Tm>Tr Summer Tm<Tr 0 0 Diagram --0

Control equipment Regula.. Pascal VAV Supply The regulation of temperature takes place in sequences with heating and cooling by signals from the universal outputs UO (heating) and UO (cooling), and the volume flow regulator (MBBV or VRU-) must be connected to the cooling output. Heating output UO is exercised every h (P). Cooling output UO is exercised every h (P) for 0 s, i.e. opening ( V) for s and closing (, V) for s (P). For easy commissioning all air flow tings for ventilation in the room are in Regula Combi (and not in the volume flow regulator). The cooling part of the temperature sequence will then result in variable output signals, which depend on four different air flow tings: Minimum air flow at presence/occupied (AirflowMinOcc) Maximum air flow at presence/occupied (AirflowMaxOcc) Standby air flow (AirflowStandby) when there is no presence, and a size dependable air flow (AirflowNominal). Normally AirflowNominal should not be changed manually. UO AirflowNom UO AirflowMaxOcc UO AirflowMinOcc AirflowStandby 0 0 Diagram --0

Control equipment Regula. All air flows are in the Service parameter menu (in l/s). Product System Size of damper Size Airflow Standby Airflow MinOcc Airflow MaxOcc Airflow Nominal MBBV (0,m/s;,V) VRU (0,m/s;,0V) (m/s;,v) (m/s;,v) (m/s,v) Other Supply / Exhaust 0 Unknown 0,0 0,0 0,0 0,0 MBBV-S- Supply MBBV-S- Supply 0 0 MBBV-S-00 Supply 00 0 MBBV-S-0 Supply 0 0 MBBV-S- Supply VRU-0 Supply / Exhaust 0 VRU- Supply / Exhaust VRU- Supply / Exhaust 0 0 VRU-00 Supply / Exhaust 00 0 VRU-0 Supply / Exhaust 0 VRU- Supply / Exhaust VRU-00 Supply / Exhaust 00 0 0 VRU-00 Supply / Exhaust 00 VRU-0 Supply / Exhaust 0 0 Table : Default values for Airflows. Note! Flow per MBBV/VRU. Note: If more than one volume flow regulator is controlled by the same Regula Combi, the size of the volume flow regulators must be the same. Every volume flow regulator size has predefined default values for AirflowNominal, AirflowMaxOcc, AirflowMinOcc and AirflowStandby. These values can of course be changed, but are re to default values if the parameter for size is changed. An external CO sensor with relay (CORT-R) can be connected at DI and C+. When the limit for CO level is exceeded, and the relay connects DI with C+ the UO (cooling) signal will increase successively (by 0.V, %, for every minute) until the CO level is beneath the lower limit with hysteresis. When it reaches this level the UO will decrease successively (by 0.V, %, for every minute) until the output UO is controlled by temperature again. Damper position is registered in Regula Combi as a -V (DC) signal through AI, and via EXOline it is used in Regula Master for fan optimization. Also the air flow point from Regula Combi is collected in Regula Master (via EXOline) and is used for exhaust regulation. In program the modes Off, Unoccupied, Standby, Occupied and Bypass are used. The pre operating mode can be to Standby or Occupied (default Occupied). Off can be reached by pressing the occupancy button for more than sec. This will close the volume flow regulator damper (with 0 V). In mode Unoccupied Regula Combi will use the points Heating point at Unoccupied (default C) and cooling point at Unoccupied (default 0 C). Any point displacement is not active in Unoccupied mode. So if the actual temperature is lower than cooling point at Unoccupied (default 0 C) AirflowMinOcc is transmitted from the cooling output. By connecting a presence detector to Regula Combi at DI and C+, Standby will occur if there is no presence in the room. Requirement for Standby function is that the pre operating mode must be to Standby and DI to Normally Open (P0=0). When Standby is active a signal corresponding to the airflow ting AirflowStandby will be transmitted from the cooling output, however if the room temperature exceeds basic cooling point (default C ) + point displacement + Neutral zone at Standby (default ), the cooling output will vary between AirflowStandby and AirflowMaxOcc. If no presence detector is connected or if the presence detector indicates presence, mode Occupied will occur. In Occupied mode cooling output will vary between AirflowMinOcc and AirflowMaxOcc. Bypass can be reached by pressing the occupancy button, and a signal corresponding to AirflowMaxOcc will be transmitted from the cooling output UO. The mode (state) of a SRC can be changed from LRM/ SRM and by EXOline / Modbus commands via GRM/ SRM. However to access Bypass from Unoccupied/Off and vice versa, it is necessary to use Occupied as a temporary mode. --0

Control equipment Regula. Pascal VAV supply program variants a) Pascal VAV supply and CO Pulse sensor Parameter changes: P to value = CO Pulse sensor. If actual CO values are to be registered in a top level system then a Regula Pulse together with the modulating CO sensor (e.g. CORT) has to be connected to Regula Combi via Regula Connect Pascal. More Regula Pulse sensors must not be parallel connected with linked Regula Connect Pascal cards. Actual CO values will be registered in steps of ppm. b) Pascal VAV supply with air duct heating Parameter changes: P to value = Heating/Cooling with VAV-control, P to the desired max UO output at heating e.g.. This will activate a heating function for UO. It will allow UO to follow the heating signal UO to a free chosen max level (P) when there is heating demand, though UO will still be limited by AirflowMinOcc and AirflowMaxOcc. This should only be used when having heated air (above room temperature) in the duct by connecting UO to a duct heater. When the heating function on UO is activated, forced cooling ventilation by pressing the Occupancy button will not lead to signal on UO. UO AirflowMinOcc AirflowMaxOcc AirflowNom AirflowStandby UO UO 0 0 Diagram b c) Pascal VAV supply with Change Over digital Parameter changes: P to value = Change-over sensor. (This will automatically also change P to value = Heating or Cooling via change-over). Then it is possible to use Pascal for a change over system, where the same duct for both heating and cooling is used, depending on requirements during for example summer (Cooling) and winter (Heating). When using the digital signal input DI (potential-free contact), closing the contact switches the change-over function and s the output UO to Heating sequence. On open contact, the change-over function s the output UO to Cooling. Sequences are shown in the diagram. UO AirflowMinOcc AirflowMaxOcc AirflowNom AirflowStandby Winter Summer DI open DI closed 0 0 Diagram c d) Pascal VAV supply with Change Over sensor Parameter changes: P to value = Change-over sensor. Then it is possible to use Pascal for a change over system, where the same duct for both heating and cooling is used, depending on requirements during for example summer (Cooling) and winter (Heating). A duct sensor (e.g. TG-K/PT00 or TG-KH/PT00) must be mounted in the supply duct and connected to the analogue input AI. The sensor must be able to sense the supply temperature in the duct. The change-over function will measure the difference between the room and supply temperature. As long as the damper is more than 0 % open, or every time an exercise is performed, the difference between the supply temperature and room temperature will be calculated. If the temperature difference is lower than the configured value (differs for Heating and Cooling mode), the control mode will change. The default tings for the difference between Heating and Cooling change-over are K (P) and K (P) respectively. Sequences are shown in the diagram. UO AirflowMaxOcc AirflowNom UO UO UO UO AirflowMinOcc AirflowStandby Winter Summer Tm>Tr Tm<Tr 0 0 Diagram d --0

Control equipment Regula.. Pascal VAV exhaust The Pascal VAV exhaust program is quite simple, since there is no regulation of room temperature. This program simply collects the exhaust air flow value sent by Regula Master via EXOline and translates it to a corresponding -V air flow control signal for the exhaust volume flow regulator at UO. In program there is no temperature regulation. The controller serves as a translator for the exhaust flow signal that is send from Regula Master (via EXOline). The exhaust flow signal is converted and transmitted to the cooling output depending on number of dampers (P) and the chosen volume flow regulator size (P). Every volume flow regulator size has predefined default values for AirflowNominal (P). This value can be changed, but is re to default value if the parameter for size is changed. The exhaust damper position is registered (via EXOline) and used in Regula Master for fan optimization.. Pascal VAV water The Pascal VAV water program is identical with program but with the cooling sequence split in two, with the first half (UO) for VAV and the second half (UO) for cooling actuator. The program is designed to make it possible to combine Pascal VAV functionality with an active chilled beam, and making sure that there will be full (max) air flow on the active chilled beam before the cooling water is active. The cooling actuator for the chilled beam on UO must be for 0-V. The proportional part of the temperature regulation is shown in diagram. UO AirflowNom AirflowMaxOcc UO VAV UO VAV UO Water AirflowMinOcc AirflowStandby 0 0 Diagram Pascal VAV water program variants a) Pascal VAV water with heating actuators in beam If there is heating in the (chilled) beam, it can be necessary to increase the air flow to the beam at heating need. UO AirflowNom UO VAV UO Water AirflowMaxOcc UO VAV AirflowMinOcc AirflowStandby 0 0 Diagram a --0

Control equipment Regula. Operating modes Regula Combi is based on Regin Regio Midi RC-CDOC which has five different operating modes: Off, Unoccupied, Standby, Occupied and Bypass. Operating mode Off Operating mode off means that the controller is not heating or cooling. However, the temperature must not drop below a minimum temperature ( C). If it does, the controller will start heating. In the display the background lighting is not lit, and only OFF is shown in the display. (Off can be reached by pressing the Occupancy button for more than seconds.) Operating mode Unoccupie Operating mode Unoccupied means that the room where the controller is placed is not used for an extended period of time, for example during holidays or long weekends. Both heating and cooling are deactivated within a temperature interval with configurable min/max temperatures (default min = C, max = 0 C). In the display the background lighting is not lit, but the current room temperature (or point depending on the configuration) is shown in the display. OFF is also shown in the display. Operating mode Standby Operating mode Standby means that the room is in energy save mode. The controller is prepared to change operating mode to Occupied (comfort) if someone enters the room (presence). The room temperature is controlled around the applicable heating and cooling points, with an extended temperature interval (default +/- C). For example, with the default heating point = C and the default cooling point = C, the controller will allow the temperature in the room to be between C and C without giving output signals. In the display the background lighting is lit (dimmed). STANDBY and the current room temperature (or point depending on the configuration) are shown in the display. Operating mode Occupied Operating mode Occupied means that the room is in use and is therefore in a comfort mode. The controller regulates the room temperature around the heating point (default C) and the cooling point (default C). The points can be adjusted +/- C locally with the increase/decrease buttons. In the display the background lighting is lit (dimmed), and the occupancy indication is shown (see Display handling and indications). The current room temperature (or point depending on the configuration) is also shown in the display. Operating mode Bypass Operating mode Bypass means that the controller controls the room temperature in the same way as in operating mode Occupied, but the output for forced ventilation is active with full signal (). After a configurable time (default min) in Bypass, the controller automatically returns to the pre operating mode. Bypass is activated when the Occupancy button is pressed once (for less than sec), or if cooling signal is needed (because of too high room temperature or CO level). The operating mode is useful for example in conferencerooms, where many people are present at the same time for a certain period of time. In the display the background lighting is lit (dimmed). The occupancy indication and the symbol for forced ventilation are shown (see Display handling and indications).the current room temperature (or point depending on the configuration) is shown in the display. In programs (-) with Standby as default the digital input DI for presence sensor is default to NC (normally closed) in Regula Combi, so the controller will immediately change to Occupied if no presence sensor is connected or if the presence sensor indicates occupancy. --0

Control equipment Regula. Display handling and indications Regula Combi has an Occupancy button, as well as an INCREASE button and a DECREASE button to increase and decrease the point. Example: The control point is C and the added displacement is +. C. This means that the value. C will be shown in the display. HEAT or COOL will flash depending on which of the point values is the control point when you enter the point menu, i.e. depending on which point you are changing. The displacement is added to both the heating and cooling point. Room temperature Setpoint OFF STANDBY SERVICE COOL HEAT Occupancy button INCREASE button DECREASE button Forced ventilation Changeable value Occupation ventilation Current room temperature in ºC to one decimal point Parameter menu It is possible to different parameter values in the parameter menu. The parameter menu is accessed by simultaneously holding the INCREASE and DECREASE buttons depressed for about seconds and then pressing the INCREASE button twice. The Service indication will be displayed. First the display will show the parameter number 0 (which chooses program). Scroll between parameters by using the INCREASE and DECREASE buttons. Press the Occupancy button to select the desired parameter. The parameter number will be replaced by the parameter value. The value can be changed using the INCREASE and DECREASE buttons. If a button is held depressed the value will start scrolling, first slowly and then with increasing speed in steps with seconds between steps. To retrieve the original value, i.e. the value before change, press the INCREASE and DECREASE buttons at the same time. The original value is shown on the display. To acknowledge and store a parameter value, press the Occupancy button again, the display then returns to showing the parameter number. After a certain time, about minute, or when the INCREASE and DECREASE buttons are pressed at the same time while in the menu, the display returns to the normal view. Exit is shown on the display after the last parameter. The parameter menu is exited by pressing the Occupancy button while in Exit. Pressing INCREASE goes to the first parameter and pressing DECREASE goes to the last parameter. In the Parameter list the numbers of selectable parameters will vary depending on which program is activated. The defaults for all programs are shown in the parameter list. Not all parameters are selectable in all programs. STANDBY: Standby indicator OFF: Unoccupied (the temperature is shown) or OFF indication (only OFF is shown). COOL-HEAT: shows if the unit controls according to the heating or cooling point. SERVICE: Is shown when parameters are, flashes when there is something wrong with the controller. There are numerous possibilities of what to be shown in the display (with parameter ), also at point adjustment (with parameter ). --0

Control equipment Regula. Parameterlist N/A: Not Available or Not Applicable Grey: Not Selectable Par no Description 0 FS Regin 0 Lindab Program N/A Basic heating point C N/A Basic cooling point C N/A Neutral zone at standby, Heating point = Basic sp. heating- by default Cooling point = Basic sp.cooling+ by default C N/A Heating point at Unoccupied C C C C C C C N/A C Cooling point at Unoccupied 0 C 0 C 0 C 0 C 0 C 0 C 0 C N/A 0 C Frost protection point C C C C C C C N/A C P-band for room controller C N/A I-time for room controller 00 s 00 00 00 00 00 00 N/A 00 The difference between the temperature in the room and the media temperature for change-over to cooling The difference between the temperature in the room and the media temperature for change-over to heating Control mode: 0=Heating = Heating / Heating = Heating or Cooling via change-over = Heating / Cooling = Heating / Cooling with VAV-control and forced ventilation = Heating / Cooling with VAVcontrol = Cooling = Cooling / Cooling = Heating / Cooling/VAV (C-models, except RC-CDFOC) Time in Bypass mode min K N/A N/A N/A N/A N/A N/A K N/A N/A N/A N/A N/A N/A N/A N/A Disconnect timer with Occupancy/Unoccupancy min 0 0 0 0 0 0 N/A 0 Switch-on delay for Occupancy 0 min 0 0 0 0 0 0 N/A 0 State connected sensor on AI: 0=Internal sensor =External room sensor =Change-over sensor (RC-CDOC/CDFOC) State connected sensor on UI: (All models except RC-CDOC/CDFOC) 0=None =Change-over digital =Change-over analogue State connected sensor on DI: =Window contact = No function = Presence detector =Change-over sensor (RC-CDOC/CDFOC) State connected sensor on DI: =Window contact =Condensation detection =No function =Changeover sensor (RC-CDOC/CDFOC) =Relay sensor (CO) =CO Pulse sensor 0 State connected function on UO: 0=None =Thermal actuator heat = None =Heating actuator 0... V = None =On/off actuator heat = None State connected function on UO: 0= None = None =Thermal actuator cool = None =Cooling actuator 0 V = None =On/off actuator cool 0 0 0 0 0 0 N/A 0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A --0

Control equipment Regula. Par no Description State connected function on UO: 0= None =Forced vent. digital =Analogue output (OEM) =None =Ordinary analogue output =None =Control of EC fan (RC-C-models) Y output in manual mode (only if Y is configured as an analogue output; not available for RC-CDFOC) State output signal range for Y-actuators: 0=0 V = V = V = 0 V State output signal range for heating actuators: 0=0 V = V = V = 0 V 0 State output signal range for cooling actuators: 0=0 V = V = V = 0 V Period time for heating actuators with thermal actuator Period time for cooling actuators with thermal actuator Run time for heating actuators with increase/ decrease actuators (used for exercising) Run time for cooling actuators with increase/ decrease actuators (used for exercising) 0 FS Regin N/A 0 % 0 0 0 0 0 0 N/A 0 0 0 0 0 0 0 0 N/A 0 0 0 0 0 0 0 0 N/A 0 0 0 0 0 0 0 0 N/A 0 0 s 0 0 0 0 0 0 N/A 0 0 s 0 0 0 0 0 0 N/A 0 s N/A s N/A Neutral zone for increase/decrease actuators % N/A N/A N/A N/A N/A N/A N/A N/A Time in hours between exercise of heating actuators h N/A Time in hours between exercise of cooling actuators h N/A Hysteresis for on/off actuators and heating K N/A N/A N/A N/A N/A N/A N/A N/A Hysteresis for on/off actuators and cooling K N/A N/A N/A N/A N/A N/A N/A N/A 0 Minimum limit for the heat output 0 % N/A N/A N/A N/A N/A N/A N/A N/A The fan will never stop 0=OFF =ON 0 N/A N/A N/A N/A N/A N/A N/A N/A Select if point or actual value is to be shown in the display. 0=Actual value =Heat point =Cool point =Average value of heating and cooling point =Only point off = CO concentration in the room in ppm (RC-CDOC/CDFOC) =Heating point +point off =cooling point+point off =Average of heating and cooling point+point off =The calculated flow in the duct in l/s (RC-CDOC/CDFOC) 0 0 0 0 0 0 0 N/A 0 Highest permitted point adjustment upwards C N/A Highest permitted point adjustment downwards C N/A Pre operating mode: 0=Off =Unoccupied =Stand-by =Occupied. Forced ventilation is not in Occupied mode. State operating mode by pressing the occupancy button for s: 0=Off =Unoccupied. Select operating mode for central control: 0=Off =Unoccupied =Stand-by =Occupied =No central control Min flow at cool output when control mode Heating/ Cooling with VAV-control is selected. Min flow at Y output when control mode Heating/ Cooling/VAV is selected N/A 0 0 0 0 0 0 N/A 0 N/A 0 % 0 0 N/A N/A N/A 0 N/A 0 --0

Control equipment Regula. Par no Description Max flow on Y output when control mode Heating / Cooling with VAV-control is selected and in heating mode. Max flow on Y output when control mode Heating/ Cooling/VAV is selected and in heating mode. 0 Configuration of fan control: 0=No control =Fan is controlled by heating demand =Fan is controlled by cooling demand =Fan is controlled by both heating and cooling demand Start signal in % for fan speed on heating or cooling control 0 FS Regin 0 % 0 0 0 N/A N/A 0 N/A 0 N/A N/A N/A N/A N/A N/A N/A N/A % N/A N/A N/A N/A N/A N/A N/A N/A Start signal in % for fan speed N/A N/A N/A N/A N/A N/A N/A N/A Start signal in % for fan speed N/A N/A N/A N/A N/A N/A N/A N/A Hysteresis for start/stop of fans % N/A N/A N/A N/A N/A N/A N/A N/A State number of speeds for the fan (, or ) N/A N/A N/A N/A N/A N/A N/A N/A Temperature compensation on AI 0 C 0 0 0 0 0 0 N/A 0 Temperature compensation on UI 0 C N/A N/A N/A N/A N/A N/A N/A N/A Temperature compensation on internal room sensor 0 C 0 0 0 0 0 0 N/A 0 Filter factor for analogue temperature inputs 0, 0, 0, 0, 0, 0, 0, N/A 0, 0 State NO/NC digital input : 0=NO (Normally open) =NC (Normally closed) State NO/NC digital input : 0=NO (Normally open) =NC (Normally closed) State NO/NC universal input : 0=NO (Normally open) =NC (Normally closed) Manual/Auto Heating output: 0=Off =Manual =Auto 0 0 0 N/A 0 0 N/A 0 N/A N/A N/A N/A N/A N/A N/A N/A N/A Manual/Auto cooling output: 0=Off =Manual =Auto N/A Manual/Auto Y forced ventilation output: 0=Off =Manual =Auto For C models (except CDFOC), manual mode means that Y puts out what is stated in parameter if Y is configured as an analogue output. When Y is configured as a Digital output (including for C models) or does not exist, this parameter constitutes the Manual/Auto mode for the forced ventilation. Manual/Auto control of change over mode: 0=Heat control =Cool control =Automatic change over depending on analogue sensor input or digital input N/A N/A N/A N/A N/A N/A Heating output in manual mode 0 % 0 0 0 0 0 0 N/A 0 Cooling output in manual mode 0 % 0 0 0 0 0 0 N/A 0 Controller Modbus address 0 Parity but Modbus communication: 0=No parity =Odd parity =Even parity Modbus time out for character (t.), in ms. Should be, times a character, i.e. at least ms. Answer delay in Modbus (t.), in ms. Should be, times a character, i.e. at least ms. Selection of heating output function (NO/NC): 0=NC (Normally closed) =NO (Normally opened) N/A N/A N/A N/A N/A N/A ms N/A N/A N/A ms N/A N/A N/A 0 0 0 0 0 0 0 N/A 0 --0

Control equipment Regula. Par no Description Setpoint display at point adjustment.: 0=The off is shown in the display =The active point + off is shown in the display. Heat or Cool is shown depending on whether heat or cool is active when entering the menu =Heat point + off is shown in the display =Cooling point + off is shown in the display Sequence order for Y and Y: 0=Y activates before Y =Y activates before Y Forced ventilation, control function: 0=Not active =Forced ventilation at output of heat or cool =Forced ventilation at Cool output Operating mode at presence detection (DI): =Occupied =Bypass 0 FS Regin EXOline PLA-address EXOline ELA-address 0 Selection of cooling output functions (NO/NC): 0=NC =NO State the connected sensor at AI: (Only RC-CDOC/CDFOC) 0=None =No function = CO-sensor =No function =0 (Damper position) =Flow calculation =0 V 0 N/A 0 0 0 0 0 0 0 N/A 0 0 0 0 N/A 0 N/A 0 0 0 0 0 0 0 N/A 0 0 0 0 0 0 N/A Flow at 0 V input in AI 0 l/s 0 0 0 0 0 0 N/A 0 Flow at V input in AI 0 l/s 0 0 0 0 0 0 N/A 0 Minimum runtime when calculating for change over 00s N/A N/A N/A N/A N/A N/A N/A N/A Alarm limit for high room temperature 0 C N/A N/A N/A N/A N/A N/A N/A N/A Alarm limit for low room temperature C N/A N/A N/A N/A N/A N/A N/A N/A Activate presence if CO level is higher (RC-CDOC/ CDFOC) Deactivate presence if the CO level is lower than the limit minus this hysteresis (RC-CDOC/CDFOC) 00 ppm ppm N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 0 Filter factor for CO-input (RC-CDOC/CDFOC) 0. 0, 0, N/A 0, 0, 0, N/A 0, CO-level at 0 V (RC-CDOC/CDFOC) 0 ppm 0 0 N/A 0 0 0 N/A 0 CO-level at V (RC-CDOC/CDFOC) 000 ppm Min limit for VAV-damper at CO-control (RC-CDOC/CDFOC) Max limit for VAV-damper at CO-control (RC-CDOC/CDFOC) This parameter defines the protocol to be used: 0=EXOline/Modbus =BACnet MS/TP BACnet MS/TP MAC address: 0-=master address -=slave address 00 ppm 00 ppm 000 000 N/A 000 000 000 N/A 000 00 00 N/A 00 00 00 N/A 00 00 00 N/A 00 00 00 N/A 00 0 0 0 0 0 0 N/A N/A N/A (00- ) Low figures of the BACnet device ID. 0- High figures of the device ID. BACnet MS/TP Max master. N/A N/A N/A (00- ) (00- ) (00- ) (00- ) (00- ) (00- ) (00- ) (00- ) --0

Control equipment Regula. Par no Description COMbus speed: 0=00 =0 =00 =00 (only BACnet) COMbus re. When activated () it res the communication to default tings 0 FS Regin 0 0 0 0 0 0 N/A N/A N/A 0 (deactivated) 0 0 0 0 0 N/A N/A N/A Min limit for EC fan (%) % N/A N/A N/A N/A N/A N/A N/A N/A Max limit for EC fan (%) 0 % N/A N/A N/A N/A N/A N/A N/A N/A Model Version Major Version Minor Version Branch Revision Number of dampers N/A N/A N/A N/A N/A N/A Size of damper ( MBB-S- ) N/A N/A N/A N/A N/A N/A AirflowStandby ( Value changes when P size of damper is changed ) AirflowMinOcc ( Value changes when P size of damper is changed ) AirflowMaxOcc ( Value changes when P size of damper is changed ) AirflowNominal ( Value changes when P size of damper is changed ) ( Should NOT be changed manually ) 00 Pin Switch for UO (pin ) and UO (pin ): 0=No pin switch =output signals on pin and pin are switched N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 0 0 N/A N/A N/A 0 N/A 0 Y Period time N/A 0 s N/A N/A N/A N/A N/A N/A 0 0 Y Selection of cooling output functions (NO/NC) N/A 0 N/A N/A N/A N/A N/A N/A 0 0 CO pulse function, Period time N/A N/A N/A N/A N/A N/A s N/A --0

Control equipment Regula. All the Regio Midi parameters (with Regin defaults) can be accessed by selecting the value 0 at parameter 0. Furthermore all parameters can be accessed and changed via RegioTool or Modbus/EXOline/Bacnet communication. CO Sequence A CO sensor CTRT(-D) can be used as input for Regula Combi. The signal from the CO sensor to the Regula Combi is 0- V corresponding to 0-000 ppm. In the Regula Combi a lower and upper limit of CO is (default 00 and 00 ppm). These limits will affect the output signal (UO or UO) from Regula Combi. The CO limits are adjustable (parameter and ). Output signal actuator/signal from CO sensor V 0 Givare CombiUO/UO 0 00 00 00 00 00 0 0 0 0 000 ppm If you press the Occupancy button for less than seconds when the controller is in Off, Standby or Occupiedmode, the controller changes to Bypass mode. If you press the button for less than seconds when the controller is in Bypass mode, it changes operating mode to the Pre operating mode (default: Standby/Occupied). After a configurable time in Bypass (default min), the controller returns to the pre operating mode (default: Standby/Occupied). Presence detector For local control of the operating mode between the pre operating mode (Standby) and Occupied, a presencey detector can be connected. When presence is indicated, the controller changes operating mode to Occupied. In Occupied, there is a switch-off timer, which means that if there is no presence indication during this time (default 0 min), the controller will return to the pre operating mode (Standby). The off-delay must be at least minute. Pre operating mode Standby Presence Occupied Occupancy button When pressing the occupancy button for less than sec, the controller is to forced ventilation (Bypass). If the button is pressed again when forced ventilation is active, the controller will go to the Pre operating mode (default: Standby/Occupied). Shutdown (Off) <s <s Pre operating mode Standby/Occupied Bypass No presence + Timer Condensation detector There is a special input (CI) on the Regual Combi controller. This input is intended for the Regula Secura sensor, and functions internally as a digital input, i.e. condensation or no condensation. When condensation is detected, the signal from the room controller to the cooling actuator is blocked. Lindab recommends using the condensation input only when the Regula Combi unit is integrated into the beam and thereby only one cooling actuator is controlled by the Regula Combi. <s >s Timer If the Regula Combi unit is placed on the wall Lindab recommends using the Regula Secura instead that not involves the special input (CI) on the Regula Combi. When the Occupancy button is held depressed for more than seconds, the controller changes operating mode to Off, regardless of the current operating mode. 0 --0

Control equipment Regula. Electrical wiring diagrams Regula Duo Duo N * V AC P V AC Actuator heating * Actuator cooling * External sensor *= connectors for actuator Quick connection for heating and cooling actuators via Regula Connect Circuit diagrams Regula Combi The maximum number of actuators that can be connected to the digital output (ON/OFF) is for cooling and heating, respectively. When more than actuators for cooling or heating are connected, terminal blocks and 0 must be connected with a cable. 0 - V CO C G G0 0...V 0 AI AI DI DI/CI G G0 - - - VAC G G0 Y 0 +C AGnd A B GDO G0 UO UO UO 0 G G0 Y G G0 Y On/Off C 0 AI AI G G0 VAC CO G G0 0...V DI DI/CI - - - G G0 0 +C AGnd GDO G0 0 A UO B UO UO --0

Control equipment Regula. Electrical wiring diagrams Regula Combi G Supply voltage V AC G0 Supply voltage 0 V - No function. 0 GDO V AC out common for DO. Internally connected to terminal, G. G0 0 V common for UO. Internally connected to terminal, G0. UO Control output forcing (cooling). For a 0 V DC actuator, max ma. The actuator s 0 V control signal terminal is connected to terminal and its supply terminals to terminals 0 and. Make sure that the reference pole G0 is connected to the correct terminal on the actuator. Alternatively for a V AC thermal actuator, max.0 A. The thermal actuator is connected between terminals and 0, GDO. UO Control output heating. For a 0 V DC actuator, max ma. The actuator s 0 V control signal terminal is connected to terminal and its supply terminals to terminals 0 and. Make sure that the reference pole G0 is connected to the correct terminal on the actuator. Alternatively for a V AC thermal actuator, max.0 A. The thermal actuator is connected between terminals and 0, GDO. UO Control output cooling. For a 0 V DC actuator, max ma. The actuator s 0 V control signal terminal is connected to terminal and its supply terminals to terminals 0 and. Make sure that the reference pole G0 is connected to the correct terminal on the actuator. Alternatively for a V AC thermal actuator, max.0 A. The thermal actuator is connected between terminals and 0, GDO. 0 AI For temperature sensor, PT00. Measuring range 0 0 C. The sensor is connected between terminals 0 and, AGnd. AI For a 0... V CO sensor. Alternatively for a 0... V Damper position. DI Presence sensor. A potential-free contact is connected between terminals and 0, +C. Alternatively for a Window contact. DI/CI Condensation detector. The sensor is connected between terminals and, AGnd. Alternatively for a Change Over indicator, CO Relay sensor or CO Pulse sensor. 0 +C V DC out common for DI AGnd Analogue ground, reference for AI A RS-communication A B RS-communication B --0

Control equipment Regula. Technical data Model Regula Duo Regula Combi Supply voltage V AC ±% 0 V AC, 0 0 Hz Communication Outputs Inputs N/A temperature sensor RS, EXOline/Modbus/Bacnet. data bits, even parity, or stop bit. 00, 0, 00 bps. UO (either AO or pulsating DO) heating, cooling and forcing (cooling) AI for Temperature and CO/Damper position. DI for Presence/Window-contact and Condensation/Change-Over/CO-relay/CO- pulse. Installation In equipment box or surface mounted In equipment box or surface mounted. Analog Output signal N/A 0- V, max ma. Digital Output signal V / A on-off* Temperature range - ºC -0 ºC V, max.0 A (time proportional pulse output signal) ** Temperature point ºC (adjustable - ºC) Heating, Cooling ± C *** Dead zone ºC ºC ( by h/c points) Power consumption W. VA Electrical connection Screw-in plinth or quick connection Screw-in plinth Size, controller mm mm Casing ABS, white color Polycarbonate, RAL 0 Protection class IP 0 IP 0 Certification CE CE Ambient temperature 0 0 C 0 0 C Storage temperature -0 0 C - 0 C Ambient humidity Max 0 % RH Max 0 % RH Actuator exercise No Yes. min once every hours Indication, heating Red LED Heat in display Indication, cooling Blue LED Cool in display Adjustment of desired valve ± C using the control knob ± C (adjustable) * Max actuators for heating or cooling stages. ** Max actuators for heating or cooling stages. When more than actuators for cooling or heating are connected, terminal blocks and 0 must be connected with a cable. *** Basic heating point 0 C, Basic cooling point 0 C, Setpoint displacement +/-0 C --0

Control equipment Regula. Regula Secura Security against condensation Lindab has developed a condensation guard for both chilled beams and facade systems. The condensation guard is called Regula Secura. Since the control exercised by Regula Secura is based on actual condensation, a greater effect is obtained than with conventional humidity control. Conventional humidity control usually measures the mean humidity and s aside a safety margin for the water temperature, to avoid condensation. With Regula Secura, no margins are required for either the sensor tings or the thermal resistance in the piping. When condensation is formed on the supply pipes, the cooling valve temporarily shuts down the water flow through the affected product. The protection provided by Regula Secura is separate for each individual chilled beam or facade system. This prevents damp damage caused by condensation. The condensation guard continues to regulate the effect even below the dew point, so the performance of the chilled beam or the façade system is kept to the optimum. An example of a control sequence is shown in the diagram below. The use of Regula Secura on all beams and facade systems increases the protection against condensation for each individual product. This means that only units where condensation forms will be shut down until the condensation dries out, while all other units will continue working. This is particularly beneficial for room environments with variable climatic conditions, or where there is a risk of external moisture entering the room, for example through open windows. Function Regula Secura exercises control through the output signal to the actuator and is only active when there is a signal to the actuator to open the valve. When the control signal does not ask for cooling, there is no need to activate Regula Secura. Regula Secura has a sensor mounted on the supply pipe of the beam or the façade system. When the sensor indicates that condensation has formed on the supply pipe, Regula Secura closes the valve until the condensation has dried out. Regula Secura is compatible with electronic control devices such as Regula Combi or any other equipment with thermoelectric actuators. It is important to note that the valve and the actuator need to be closed in the event of a power cut. Regula Duo/ Regula Combi Regula Secura Condensation sensor Actuator with valve Schematic showing how to connect Regula Secura. Temperature ( C) / Air humidity (%) Condensation guard:. C below the dew point 0 0 0 0 0 0 0 00:00 0:00 0:00 0:00 0:00 :00 :00 Time (h) 00 00 00 00 00 0 Effect (W) Room temp. ( C) Supply temp. ( C) Relative humidity (%) Dew point ( C) Effect (W) The diagram shows a control sequence where the water temperature is. C below the dew point. Throughout the whole process, the control centre asks for cooling. It can be seen how Regula Secura controls using the ON/OFF feature. --0

Control equipment Regula. Regula Connect Basic Regula Connect Basic is a connection card that provides flexible connection for chilled beams or façade systems. Regula Connect Basic consists of a connection card with connectors for mains cables, thermostat cables and terminal blocks for actuator cables. The card has alternatives for the mains cable outputs, so the control signal can be transmitted to the next chilled beam or facade system in both directions or terminated at any point. A transformer is also connected to a free port. Regula Connect Multi In addition to the connectors available in Regula connect Basic, the Regula Connect Multi also offers connectors for CO and Presence sencors. Further more it is also possible to connect a damper on the Regula Connect Multi, for air flow control. The damper option is used to for forced ventilation and for the Lindab ehybrid system. REGULA CONNECT Basic N = Neutral L = Load S = Signal Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link_s Cooling link_s Heating link_s Cooling link_s Supply in - N Supply in - V - L LINDAB Regula Connect Basic Reconnecting control cables When moving, building new, or removing existing partitions, the control system can be reconnected (see picture below). This to allow the control centre to control the products in the room where it is installed. The unit's cable consists of four conductors, two for the supply voltage and two for the control signal to the heating and cooling actuators. REGULA CONNECT Multi Rc LINK N = Neutral L = Load S = Signal Rc LINK RC in/out The figures refer to the picture below. Connectors for heating output devices, such as heating circuit actuators. Connectors for cooling output devices, such as cooling circuit actuators. Connector for power and communication input from Regula Combi. - Connector for power and communication link between one or more beams. Connector for direct power via external transformer. Connector for CO sensor input. Connector for Presence sensor input. Connector for damper output. RC link. RC in/out. CO in - S CO in - S CO out - N CO out - L Presence in - S Presence in - S Presence out - N Presence out - L Damper out - S Damper out - N Damper out - L Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link - S Cooling link - S Heating link - S Cooling link - S Supply in - N Supply in V - L LINDAB Regula Connect Multi --0

L/NMV-D-MP-F Adaption Address Power Status L/NMV-D-MP-F Adaption Address Power Status lindab we simplify construction Control equipment Regula. REGULA CONNECT Basic N = Neutral L = Load S = Signal REGULA CONNECT Basic N = Neutral L = Load S = Signal Blu Blu Whi Grn Yel Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Blu Blu Whi Grn Yel Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Yel Heating link_s Cooling link_s Heating link_s Cooling link_s Supply in - N Supply in - V - L Whi Grn Yel Blu Heating link_s Cooling link_s Heating link_s Cooling link_s Supply in - N Supply in - V - L LINDAB LINDAB Transformator L N 0 V V BELIMO Made in Switzerland MP BUS REGULA CONNECT Multi Rc LINK N = Neutral L = Load S = Signal Rc LINK RC in/out BELIMO Made in Switzerland MP BUS REGULA CONNECT Multi Rc LINK N = Neutral L = Load S = Signal Rc LINK RC in/out TB 0 White/Orange Orange White/Green Blue White/Blue Green ends must White/wn be insulated{ wn CO in - S CO in - S CO out - N CO out - L CO in - S CO in - S CO out - N CO out - L Presence in - S Presence in - S Presence out - N Presence out - L Presence in - S Presence in - S Presence out - N Presence out - L Whi Blk Red Blu Blu Yel Whi Grn Yel Damper out - S Damper out - N Damper out - L Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link - S Cooling link - S Whi Blk Red Blu Blu Whi Grn Yel Whi Grn Yel Damper out - S Damper out - N Damper out - L Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link - S Cooling link - S Yel Heating link - S Cooling link - S Supply in - N Supply in V - L LINDAB Heating link - S Cooling link - S Supply in - N Supply in V - L LINDAB REGULA CONNECT Basic N = Neutral L = Load S = Signal REGULA CONNECT Basic N = Neutral L = Load S = Signal Blu Blu Yel Whi Grn Yel Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link_s Cooling link_s Heating link_s Cooling link_s Blu Blu Whi Grn Yel Whi Grn Yel Heating out - S Heating out - N Heating out - L Cooling out - S Cooling out - N Cooling out - L Heating in - S Cooling in - S Supply out - N Supply out - L Heating link_s Cooling link_s Heating link_s Cooling link_s Supply in - N Supply in - V - L Supply in - N Supply in - V - L LINDAB LINDAB --0