Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada

Similar documents
Wisconsin Contractors Institute Continuing Education

Article 250 Grounding & Bonding

American Electrical Institute

CONTINUING EDUC ATION

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

3.7 Grounding Design for EAST Superconducting Tokamak

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Device Interconnection

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Field Instrument Cable. Electrical Noise

Electrical Wiring: Commercial, Seventh Canadian Edition

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Sound System Interconnection Or: Dealing With Ground Loop Hums

Chapter 3 G rounding Grounding Electromagnetic Compatibility Compatibility Engineering by Henry W Ott.

RaneNote. Sound System Interconnection. 1 of 9 6/13/ :49 PM. Rane Technical Staff. [RaneNote 110 written 1985; last revised 5/02]

Wiring of the Main Distribution Panelboard

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Grounding for Power Quality

Downloaded from

6B.6 Substation Grounding

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

Busbars and lines are important elements

150Hz to 1MHz magnetic field coupling to a typical shielded cable above a ground plane configuration

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

Grounding and Bonding of Service Equipment

Outline. Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions

EC6011-ELECTROMAGNETICINTERFERENCEANDCOMPATIBILITY

1) The diagrams in the section Assembly notes were provided by Rittal GmbH Co. KG, Herborn and by Invensys Systems GmbH EUROTHERM, Limburg/ Lahn.

Overview of the ATLAS Electromagnetic Compatibility Policy

A. Product Description: Stranded conductor insulated wire.

Grounding Complications

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

ECE 528 Understanding Power Quality

THE FIELDS OF ELECTRONICS

RADIO AND TELEVISION SATELLITE EQUIPMENT

Grounding and Bonding

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5

EPG. by Chris C. Kleronomos

SECTION PANELBOARDS

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems

MIL-STD B METRIC 1 Feb 92 SUPERSEDING MIL-STD A 2 FEBRUARY 1984 MILITARY STANDARD GROUNDING, BONDING AND SHIELDING

2-Slot Desktop Chassis (DC) Extended Temperature

Chapter 16 PCB Layout and Stackup

CHAPTER 6 EMI EMC MEASUREMENTS AND STANDARDS FOR TRACKED VEHICLES (MIL APPLICATION)

Isolated RTD Modules Product Specifications and Installation Data

Solution of EMI Problems from Operation of Variable-Frequency Drives

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Lightning Strikes. Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS

Implement lightning survivability in the design of launch vehicles to avoid lightning induced failures.

EMC filters. Mounting instructions. Date: January 2006

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests

Tower Grounding Training For Telecommunications Networks

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Excel 15 S7760A COMMAND DISPLAY

6. Internal lightning protection

Minimizing Lightning and Static Discharge in Broadcasting

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

Understanding Noise Cut Transformers

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

Transmission of Electrical Energy

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

MV protection relay. Installation assistance guide. Sepam ranges

Control Cable installation: Best Practice

Overview of EMC Regulations and Testing. Prof. Tzong-Lin Wu Department of Electrical Engineering National Taiwan University

Split Planes in Multilayer PCBs

Fluke Clamp Meters Solutions for every need

TxBlock-USB Transmitter

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Installation instructions and notes on implementation of an intermeshed equipotential bonding system with EMClots

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motor Transformers and Distribution Systems

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Industrial and Commercial Power Systems Topic 7 EARTHING

Copper Sheathed Cable Sheath Currents

Common myths, fallacies and misconceptions in Electromagnetic Compatibility and their correction.

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Outdoor Installation 2: Lightning Protection and Grounding

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

EDBEMV!PZi. Ä!PZiä. Electromagnetic compatibility. Global Drive Basic information on controller applications in plants and machinery

Lightning Protection Guide. Rack-mountable Devices

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

RaneNote SOUND SYSTEM INTERCONNECTION

Collection of standards in electronic format (PDF) 1. Copyright

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Modular Plug Connectors compliant to Cat.6 A Standard

Suppression of Powerline Noise with Isolation Transformers

Transfer Functions in EMC Shielding Design

Unclassified Distribution A: Unlimited Public Release

Transcription:

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada and Philip Giddings Engineering Harmonics Toronto, Canada The original document and figures may be found in the Journal of the Audio Engineering Society, Volume 43 Number 6, June 1995. This version is Philip Giddings 1995 and was revised Feb. 15, 1996. Abstract The isolated star ground system is the most popular implementation of technical grounding for the purposes of grounding sensitive electronic equipment. This approach has been in practice for many years, and while it is not a perfect solution, it is the solution that presents the least compromises. This paper documents the current approach as implemented in a number of large installations and is part of an on-going AES effort to document appropriate practices with regard to the control of noise in audio systems. 1. Introduction The purpose of grounding is to provide safe, reliable and cost efficient power distribution. (Note that the cost element includes damage to the equipment due to a fault or lightning strike.) These are the goals of grounding from a power distribution viewpoint where electrical noise interference is not a consideration. In the case of sensitive electronic systems, such as audio, video and computer systems it is also necessary that the grounding system provide a stable and low impedance connection to earth to control electromagnetic interference (EMI). The isolated star ground system as documented in this paper serves all of these purposes: safety, reliability, cost efficiency and control of electromagnetic interference. Grounding is only one means of controlling electrical noise in audio and other technical systems. A systems approach to controlling noise is recommended and readers should see [1], [2], [3], [4], [5], [6] and the references contained therein. This paper discusses the grounding system installed in the facility up to but not including the electronic equipment. Grounding practices at electronic equipment and shields are discussed in the references. 2. System Concept The overall concept of the isolated star ground system is shown in Figure 1. From this

drawing we see that the technical ground wiring connections occur in four locations; these being the service entrance, the sub distribution panel, the area panels and the final equipment connections (branch circuits). These are discussed in the following paragraphs. The distribution of non-technical (safety) equipment ground is shown on all the drawings via the conduit system, as permitted by many electrical codes. In some cases, this is, or must be, supplemented with an added ground conductor to reinforce the integrity of the bonding of the conduit system. Of course, in the case of armored cable in the branch circuits, the third (ground) conductor is standard practice. Note that equipment racks and large technical units are not considered part of the equipment ground system. They are part of the technical ground system and are discussed later. The technical ground system is isolated from all metallic building structures. To this end all ground conductors are insulated (green or green with yellow trace or as required by code) and ground bars in the main and area ground boxes are isolated from their metal housings. 2.1. Service Entrance The wiring diagram for the Service Entrance ground is shown in Figure 1. At this point only, the technical ground is bonded to the main building ground connection which in turn is bonded to the neutral and the earth electrode. Typically the metallic structure of the building will have a connection to ground via contact with electrical conduits and other bonded elements. The main power distribution panel may be shared with regular power distribution systems in the service entrance as shown in Figure 2. For completeness regular power distribution has been shown to highlight wiring differences. 2.2. Sub The wiring diagram for the Main Technical ground is detailed in Figure 2. The Main Technical Ground is the central star point of a system. This is where the main technical ground bus resides. All technical grounds stem from this single point. The main technical ground and associated AC panel would typically be located at the main technical equipment center of the facility, such as a master control room in a broadcast centre. The main technical ground bus resides in a separate box below the technical sub distribution panel and, as mentioned earlier, it is totally isolated from its enclosure. 2.3. Area The wiring diagram for a typical Area Technical Ground is shown in Figure 3. Located throughout the facility or adjacent to the main equipment centres (such as studio control rooms) will be technical power branch panels fed from the technical power sub distribution

panel. The area technical grounds are wired in a similar manner to the main technical ground panel -- there is an isolated ground bus in a separate box located below the electrical panel. This isolated ground bus receives its ground reference from the ground bus in the technical sub distribution panel. The area technical ground bus provides the ground reference for the equipment or branch technical circuits in the adjacent area. 2.4. Equipment or Branch Circuits The wiring diagrams for the Equipment or Branch Technical Grounds are shown in Figures 3, 4 and 5. The branch circuits are AC isolated ground receptacles for the use of stand-alone or portable equipment and are detailed in Figure 3. The drawing shows the difference in the wiring practices between technical receptacles and regular receptacles. No more than two receptacles are looped together on a single conductor from the ground bus. In North America, isolated ground receptacles are salmon or orange colored and may have a triangle symbol on the front face identifying that the ground terminal is isolated from the casing and hence the box it is mounted in. Figures 4 and 5 demonstrate how the equipment racks and large technical units (such as audio consoles) must be isolated and receive their ground connection only from the incoming insulated technical ground conductor. All racks are mounted on an insulating plinth (base). In the case of a multiple rack installation they are bolted together to provide an equipotential plane. All stand- alone equipment must be isolated to prevent the possibility of inadvertent ground contact with metallic building structures. In the case of multiple equipment racks and audio consoles the separate ground conductor from the junction box to the equipment should have an overall protective sheathing to eliminate inadvertent insulation damage. Junction boxes "J" as shown in the figures must be isolated from the technical equipment housings and are wired to the technical equipment via insulated sheathed cable. 3. Conductor Termination In order to maintain the low impedance of the technical grounding system, conductor termination must be carefully executed. Bus bars should be heavy gauge copper. All hardware should be of stainless steel or brass. All wire termination lugs are copper or copper plated with either nickel or tin. Grounding conductors should be copper. To ensure long term reliability of ground connections, machine screws should be highly torqued. In humid or damp locations the entire assembly should be coated with a moisture proof barrier. Aluminum wire and termination hardware and aluminum bus bars should not be used. 4. Conductor Sizes 4.1. Safety Consideration The isolated conductors also serve as the equipment (Safety) ground for the technical equipment housings as required by the electrical code. As a minimum requirement, these conductors must satisfy the electrical code. The minimum equipment ground conductor sizes

required by the National Electrical Code in the United States and the Canadian Electrical Code in Canada are given in the following table. Other countries have similar wiring regulations. Minimum Equipment Ground Conductor Sizes ( based on National Electrical Code table 250-95 "Minimum Size Equipment Ground Conductors for Grounding Raceway and Equipment") Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Not Exceeding (A) Copper Wire AWG (square millimeters) 15 14 (2.081) 12 (3.309) 20 12 (3.309) 10 (5.261) 30 10 (5.261) 8 (8.366) 40 10 (5.261) 8 (8.366) 60 10 (5.261) 8 (8.366) 100 8 (8.366) 6 (13.30) 200 6 (13.30) 4 (21.18) 4.2. Technical Consideration Aluminum or Copperclad Aluminum Wire AWG (square millimeters) The sizing of the conductor with regard to the requirements for Electro-Magnetic Interference (EMI) control is more difficult to determine. The appropriate wire gauge for EMI reasons is influenced by the sensitivity of the system and the anticipated level of electromagnetic interference. Obviously systems of low dynamic range such as paging and background music systems do not have stringent requirements for technical grounding whereas broadcast and post- production complexes are more critical. Wire gauges typical of a broadcast installation, are shown in the figures. The following table gives suggested values [1]. Technical Ground Conductor Sizes in AWG (square millimeters) (Suggested Only) Conductor Out From Medium Dynamic High Dynamic Low Dynamic Range (60 to 80 db) Range (>80 db) Range (< 60 db) Lo EMI Hi EMI Lo EMI Hi EMI Ground electrode to main 00 0000 6 (13.30) 2 (33.63) 00 (67.45) bus (67.45) (107.2) Main bus to Local bus 10 (5.261) 8 (8.366) 6 (13.30) 4 (21.18) 0 (53.48) Local bus to single 12 14 (2.081) 12 (3.309) 12 (3.309) unit/rack or receptacles (3.309) 10 (5.261) Local bus to multiple units/racks or major equipment 14 (2.081) 12 (3.309) 10 (5.261) 8 (8.366) 4 (21.18)

Maximum resistance (ohms) for any cable 0.5 0.1 0.001 0.001 0.0001 In all cases the ground conductor must be suitably rated for the overcurrent device of its associated power conductors. 5. Conductor Separation and Routing The electrical code requires that the ground conductor must be routed with its associated power conductors. Exceptions have been made in some cases, but special approvals may be required. The authors have not been able to determine whether there is any benefit from running ground conductors separately. Further work will follow in this regard. As the ground conductor is sensitive to EMI the routing of the technical power and ground conductors should be done with some care and should be routed away from other major high voltage feeders, transformers, large motors and other EMI sources in the building. 6. Conclusion The most widely accepted approach to the implementation of a isolated star ground system has been presented. It is suggested that from a value engineering stand point, this approach represents an appropriate level of system design and installation practice. If EMI problems exist in technical systems so implemented it is suggested that designers and trouble shooters look for solutions in areas other than grounding. These areas include interconnection schemes, internal ground of electronic equipment ("the pin 1 problem") and overall systems design. 7. References [1] Giddings, P. 1990. Audio Systems Design and Installation, Indianapolis: Howard W. Sams. 8. Bibliography [2] Muncy, N. A. 1994. "Noise Susceptibility in Analog + Digital Signal Processing Systems". Presented at the 97th AES Convention, San Francisco. [3] Macatee, S. R. 1994. "Considerations In Grounding and Shielding Audio Devices". Presented at the 97th AES Convention, San Francisco. [4] Whitlock, B. 1994. "Balanced Lines in Audio Systems - Fact, Fiction, and Transformers". Presented at the 97th AES Convention, San Francisco. [5] Windt, J. 1994. "An Easily Implemented Procedure for Identifying Potential

ElectroMagnetic Compatibility Problems in New Equipment and Existing Systems - The Hummer Test". Presented at the 97th AES Convention, San Francisco. [6] Perkins, C. 1994. "Automated Test & Measurement of Common Impedance Coupling In Audio System Shield Terminations". Presented at the 97th AES Convention, San Francisco. [7] Morrison, R. and Lewis, W. H. 1990. Grounding and Shielding in Facilities, New York: Wiley Interscience. [8] Giddings, P. 1989. "An Introduction to Electromagnetic Compatibility (EMC) and Electromagnetic Interference (EMI) for Audio System Designers", J. Audio Eng. Soc., Vol. 37, No. 7/8. [9] Burdick, A. H. 1986. A Clean Audio Installation Guide, North Syracuse, N.Y.: Benchmark Media Systems, Inc. [10] Davis, C., and Davis, D. 1985. "Grounding and Shielding Workshop", Tech Topics, Vol. 12, No. 10. San Juan Capistrano: Syn Aud Con. [11] Morrison, R. 1977. Grounding and Shielding Techniques in Instrumentation, 2nd ed., New York: Wiley Interscience. Contains interesting information. [12] Violette, N., and White, D. 1987. Electromagnetic Compatibility Handbook, New York: Van Nostrand Reinhold. Philip Giddings 1995 Rev: Feb. 15/96