Pulse Cable for TESLA Modulators Hans-Jörg Eckoldt DESY TESLA

Similar documents
Pulse cables for XFEL

XFEL/FLASH Meeting 30/07/07

CUSTOM DESIGN COAXIAL CABLES BY SICAB

TESLA RF POWER COUPLERS DEVELOPMENT AT DESY.

Grounding for EMC at the European XFEL

Field Instrument Cable. Electrical Noise

Data sheet MC GC1000 pro23 Cat.7 S/FTP 4P LSHF-FR 1640 ft

MarineLine YOZp 0,6/1 kv

Design and Construction of a150kv/300a/1µs Blumlein Pulser

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Data sheet MC GC1200 pro22 Cat.7A S/FTP 4P LSHF-FR, class Dca s2 d2

Data sheet MC GC1200 pro22 Cat.7A S/FTP 2x4P LSHF-FR 1640 ft

Tratos High Voltage cables

Addison. Profibus SK Indoor + Outdoor BUS CABLE. Application: Construction:

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation.

Armoured Power and Control Cables to BS7917

Armoured Power and Control Cables Fire Resistant

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s

High Power Couplers for TTF - FEL

EDS KV SINGLE CORE XLPE CABLES

Caledonian. Profibus L2 Indoor BUS CABLE. Application: Construction:

HIGH POWER INPUT COUPLERS FOR THE STF BASELINE CAVITY SYSTEM AT KEK

Armoured Power and Control Cables to BS6883

COPPER + LWL RAW CABLES

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

25 MW SMES-BASED LONG-PULSE KLYSTRON MODULATOR

Data sheet. Connection line M12 plug straight - M12 jack straight drag chain suitable, 8-pole, X-coded 2.0 m. Illustrations

EXCELLENT ELECTRICAL PERFORMANCES

High Voltage Engineering

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

EDS KV TRIPLEX CABLE RATING

SOLID-STATE SWITCHING MODULATOR R&D FOR KLYSTRON

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

CIR (Crush & Impact Resistant) VFD Power Cable

Market Survey. Technical Description. Supply of Medium Voltage Pulse Forming System for Klystron Modulators

K20 & L120 LSZH Armoured F/FTP Cat6 Cables

Armoured Instrumentation Cables to BS6883

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Coaxial Cables Coax Serie. HF Steckverbinder für Mobilfunk-Anwendungen. in Bulk Rings or on Cable Drums

CORFLEX VFD CORFLEX VFD Part Number: Drive Cable

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables

Couplers for Project X. S. Kazakov, T. Khabiboulline

SICK AG WHITEPAPER INFORMATION AND RECOMMENDATIONS FOR MOTOR APPLICATIONS AND INSTALLATIONS NOTE-1_06

Industrial Ethernet OPT cable manufactured for Petrol Forecourt Applications.

Corrosion Steel Inspection under Steel Plate Using Pulsed Eddy Current Testing

Mircea Stirbet. RF Conditioning: Systems and Procedures. Jefferson Laboratory

2.3 PF System. WU Weiyue PF5 PF PF1

Design Study. Reducing Core Volume in Matrix Transformers

Speedflex. Halogen free coaxial cables.

14 AWG 2 AWG: 600 Volt

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

Electrical Design Process

Tests on Extruded Cables

Coax element HF75-0,3/1,6 RG179 HF50-0,9/2,95 RG58 HF50-0,3/0,84 RG178 Part. No. CFKoax1 CFKoax2 CFKoax3

Validation of a measurement method for magnetic shielding effectiveness of a wire mesh enclosure with comparison to an analytical model

HO7RN-F 450/750V BS EN Highly Flexible Rubber Cable

Sensors for in-flight lightning detection on aircraft

Generation of Sub-nanosecond Pulses

TECHNICAL REPORT: CVEL Parasitic Inductance Cancellation for Filtering to Chassis Ground Using Surface Mount Capacitors

Cable Solutions for Servo and Variable Frequency Drives (VFD)

NETWORK CONNECTIVITY SYSTEMS

Fireproof Cables (Fire Resistant LSOH Sheathed Cables) КИФнг(A)-HF for RS485

5-46kV 3/C TRXLPE ARMORTEK Medium Voltage Commercial & Industrial Cables

Kerman & Kavian Cable Industries ( KCI )

Transformer Factory Testing

RECEIVER SECURYFILL IV

REVIEW OF HIGH POWER CW COUPLERS FOR SC CAVITIES. S. Belomestnykh

Medium Voltage Power Cables

The theory of partial inductance is a powerful tool

Fault location on power cables. Fault location on power cables

VSD cables in. Working with. industrial & automation applications

International Journal of Science and Engineering Investigations vol. 2, issue 15, April 2013

EE 340 Transmission Lines. Spring 2012

Coupler Electromagnetic Design

CX1140 Hydrogen Thyratron

MEASUREMENT OF THE INTERNAL INDUCTANCE OF IMPULSE VOLTAGE GENERATORS AND THE LIMITS OF LI FRONT TIMES

RGCoaxials RG, low noise and sub-miniature coaxials

Gain flexibility. Save weight. Specialty cables

High Votage Module AC/DC/Impulse Test System

HIGH POWER COUPLER FOR THE TESLA TEST FACILITY

Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking

Reactor and inductor are names used interchangeably for this circuit device.

The shield (screen) connecting system from WAGO offers high electrical and mechanical safety for very flexible applications.

Welding Cables Rubber Insulated

ALICE SRF SYSTEM COMMISSIONING EXPERIENCE A. Wheelhouse ASTeC, STFC Daresbury Laboratory

CABLES FOR MOTION CONTINUOUS-BENDING HI-FLEX ELECTRICAL CABLES TOTALTRAX TURN-KEY SYSTEMS PRE-ASSEMBLED CABLES STRAIN RELIEF DEVICES

5. The Different Types of Resistors

Performance Enhancement For Spiral Indcutors, Design And Modeling

RF power tests of LEP2 main couplers on a single cell superconducting cavity

The Power Supply System for CMS-ECAL APDs

Cores layed up around conductive filler with aramid rope in the center Rubber, special compound, mechanical properties acc.

IEC Standard Caledonian Offshore & Marine Cables

Wire and Cable. 99 Wire Dual Wall 120ºC rated, Modified Polyester Low fire hazard wire and cable. Features & Benefits

SAC-3P- 5,0-PUR/M12FR SH

TRAXLINE CABLES FOR MOTION

FLAME RETARDANT INSTRUMENTATION CABLE. Application Standard

Roll No. :... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/ POWER SYSTEM-I. Time Allotted : 3 Hours Full Marks : 70

Transcription:

Pulse Cable for TESLA Modulators Hans-Jörg Eckoldt DESY TESLA 2000-35

1 Introduction... 3 2 Demands for the cable... 3 3 Cable construction... 3 4 Simulation results... 4 5 Installation... 7 6 Cooling... 8 7 Specific losses in the tunnel... 8 8 Fire protection... 8 9 References... 8

1 Introduction Modulators are used to generate the pulsed power for the klystrons of the superconducting linear accelerator TESLA. The high voltage pulses have a rectangular shape with a voltage up to 120 kv. The electrical power during the pulse is typically 15 MW and can be up to 16.8 MW. The pulse length is 1.7 ms with a repetition rate of 5 Hz, for app. 10 % of the modulators it is 10 Hz. Inside the modulators the switched voltage is at the 10 kv level. Via a pulse transformer the HV is achieved. Due to the radiation inside the TESLA tunnel and the accessibility of the units the power part of the modulators shall be installed into the service halls. However the transformer tank and the klystrons have to be inside the tunnel near the cavities. The energy has to be transported from the modulator to the transformer via pulse cables. 2 Demands for the cable The pulse cables have to meet the following specifications: The cable shall not generate any stray fields in the tunnel The ohmic losses shall be app. 2.0 % in average The losses caused by the skin effects need to be low in order to keep the losses low There shall only be a low damping of the high frequencies 3 Cable construction The demand for the low stray fields gives the general design of the cable which is triaxial as shown in Fig. 1. The inner conductor is at the high voltage level (10 kv) of the modulator. The middle conductor carries the return current at the bouncer voltage level of +/- 1 kv. The cross section has to be 300 mm² copper. This is chosen for the inner and outer conductor. The shield is chosen as 16 mm² aluminum or copper foil. As insulator XPE (cross linked Polyethylen) is used. The rise time of the voltage pulse of the modulator is 10 µs. The current rise time is dependant of the transformer and cable inductance. It is between 140 and 240 µs. One solid cable having a 300 mm² cross section can not be taken. The occurring skin effect for such a cable does not allow the current to penetrate into the inner part of the conductor. During the pulse the current just flows at the outer rim of the conductor and enters about 2 mm into the material. Additionally the inner inductance of the such a cable leads to a to long rise time of the pulse. To compensate this effect two solutions are possible: The inner conductor of the cable can be built as a tube with a thickness of app. 2 mm. By this the diameter of the entire cable is increased There will be several smaller triaxial cables put in parallel. The sum of the cross sections equals to 300 mm².

In discussion with the cable manufacturer the solution with several small cables is preferred for production reasons. A standard cross section of cables is 70 mm². Therefore only minor changes have to be done to fabricate a cable with 75 mm². This results in a lower price. For TESLA four cables in parallel with a cross section of 75 mm² each are chosen. The impedance of the four cables in parallel is 6.45 Ω. Solutions for the constructions of cable end pieces and cable sleeves are available. The diameters of the cable are: Inner conductor Cu bare fine strand Semiconductor layer Insulation VPE Semiconductor layer Outer conductor Cu bare fine strand Semiconductor layer Insulation Semiconductor layer Aluminum foil Outer sheath 10 mm 10.2 mm 19.2 mm 19.4 mm 21.8 mm 22.0 mm 27.2 mm 27.4 mm 27.8 mm 33.8 mm semicond. layer insulation semicond. layer Aluminum foil outer sheath cond. 75mm², Cu tinned, fine-strand semicond. layer insulation semicond. layer cond. 75mm², Cu bare fine-strand Fig.1: Cross section of the cable 4 Simulation results The behavior of the cable is simulated in a pspice model and analytically in [1] in good agreement. Since the cable impedance is not matched when a transformer is connected to the cable a matching network as shown in Fig. 6 is used. Fig. 6: Impedance matching network

The values for the components are: R1 = 6 Ω, corresponding to the klystron resistance transformed to the primary side of the transformer. The nonlinear behavior of the klystron is not simulated. Ls = 200 µ H, transformer leakage inductance Lh = 2 H, main inductance of the transformer C1 = 1 µ F, matching network R2 = 100 kω, matching network R3 = 10 Ω, matching network The simulation results from [1] are shown for a set of four parallel cables of 100 m length (Fig. 7), 1 km length (Fig. 8), 2.5 km length (Fig. 9) and 3 km length(fig. 10). The occurring over shoot of voltage u 2 is at the primary side of the transformer and does not affect the klystron. The klystron voltage corresponds to the current i k. The rise time delay of the klystron voltage due to the cable is in the order of 90 to 100 µs. The rise time for a 3 km long cable is < 250 µs. Fig. 7: Simulation result of 4 cables 75 mm² in parallel 100 m

Fig. 8: Simulation result of 4 cables 75 mm² in parallel 1000 m Fig.9: Simulation result of 4 cables 75 mm² in parallel 2500 m

Fig.10: Simulation result of 4 cables 75 mm² in parallel 3000 m 5 Installation The cables will be installed in a special area inside the tunnel shown in Fig. 11. They will be laid on cable trays that are connected to steel plates which are integrated into the concrete of the tunnel wall. Air flow Signal lines Mains cable Mains distribution system 400 Pulse cable App. 40 mm Max 208 in parallel Mains cable 20 kv Cooling water Cooling water Fig.11. Principle of tunnel installation

6 Cooling The cable will have a specific loss of 2.8 W/m at 5 Hz respecting 5.5 W/m at 10 Hz repetition rate. Since this value is low the cable shall be natural air cooled. With a proper installation a free air flow is possible as shown in Fig. 11. 7 Specific losses in the tunnel The cables are a heat load for the tunnel with a maximum of the power near the service halls. At this point all cables are coming in parallel from the service halls. Every 48 m this number is decreased by a set of cables for a modulator. The maximum occurring specific losses are 264 W/m in tunnel near the DESY site where the modulators are operating in 10 Hz repetition rate. In the halls having modulators operating at 5 Hz repetition rate these values are less than 150 W/m. 8 Fire protection The pulse cables are a fire load in the tunnel. To minimize the risk of a fire for these cables precautions in the construction are made. The outer sheath of the cable will be of halogen free flame retardant material. The outer shield will be constructed of a foil. Therefore in case of a fire the insulation material is kept inside the cable. An outer flame will not have contact with this material. Additionally a fire protective coating will be painted onto the cable. In case a flame heats this coating it will increase in volume avoiding the flame from getting contact to the cable. A short circuit inside the cable will be detected with the modulator interlock. The main capacitor bank will be short circuited and the modulator will be turned off. By this no further energy will be supplied to heat material. A slow heating of the cable can occur due to a bad contact in the cable sleeves or cable end piece. In this case smoke will be produced in the hot spot. This has to be detected by smoke detectors which then turn the modulators off. 9 References [1] M.Filtz, Analytische Berechnungen zu einem Hochspannungskabel, Technische Universität Berlin, Fachgebiet Theoretische Elektrotechnik, Okt. 2000 [2] H. Kaden, Impulse und Schaltvorgänge in der Nachrichtentechnik, R. Oldenburg Verlag, München, 1957 [3] H. Kaden, Wirbelströme und Schirmung in der Nachrichtentechnik, Springer Verlag, 1959