Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Similar documents
and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SECTION TRANSFORMERS

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

Steps for Selecting the Proper Transformer

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

Dry-Type Transformers

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

SECTION PANELBOARDS

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

What is a Transformer?

Technical Data and Specifications. Core and Coil Assemblies

T S 15KVA 1PH 240/480 Transformer

INTERNATIONAL TRANSFORMERS. Acme Electric s broad selection of CSA energy efficient transformers

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R

Power Processor - Series 700F 10KVA to 150KVA

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

500 kva Isolation Transformer - 480V Delta Primary - 400Y/231 Wye Secondary - NEMA 3R

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

ULTRA-K Series 600K - he

2.1. Product Description

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

B. Manufacturers: Square-D, G.E. or Westinghosue.

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

75 kva Isolation Transformer - 480V Delta Primary - 208V Delta Secondary - NEMA 3R

K Factor Power Transformers

S10N06P02P 2KVA 1PH 120/240V 16/32V Buck Boost Transformer. Descriptions

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

DTS ISOLATION TRANSFORMER SPECIFICATIONS

Transformer Questions & Answers

Energy Efficient Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

CITY OF TACOMA Transmission & Distribution

2.5. Contents Description Motor Drive Isolation Transformers... Mini Power Centers... Totally Enclosed Non-Ventilated Transformers

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Transformer Questions & Answers

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Load Isolation Transformers

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

General Description & Features Selection Charts Definition of Terms... 42

2.5. Transformers. Mini Power Centers. Distribution Transformers. Product Description

SECTION DISTRIBUTION SWITCHBOARDS

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

5 kva Isolation Transformer - 115V Primary Voltage - 230V Secondary Voltage - Single Phase - NEMA 3R

SECTION DISTRIBUTION SWITCHBOARDS

80 kva Isolation Transformer - 480V AC Primary - 20V AC Secondary - NEMA 3R - Single Phase

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

225 kva Autotransformer - 240V Delta Primary Voltage - 220V Delta Secondary Voltage - NEMA 3R

HPS Universal BUCK-BOOST TRANSFORMERS

7.5 kva Isolation Transformer - 460V Primary - 230V Secondary - NEMA 3R - Single Phase - 50/60 Hz

Full Line Product Catalog

Howard Smart Transformer Specification Guide

Liquid-Filled Transformers

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

7. INSPECTION AND TEST PROCEDURES

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

1.5 kva Single Phase Transformer - 120V Primary Voltage - 277V Secondary Voltage - NEMA 3R

10 kva Transformer - 480V Primary Voltage - 208V Secondary Voltage - Single Phase - NEMA 3R

Section 2 Outdoor Voltage Transformers

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

Your Presenters. > Thomas Patzner Product Manager, Low Voltage Transformers. > Marquette University Electrical Engineering. > Apprentice Electrician

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Warehouse Stock Transformers

Low Voltage Transformers. Selection Guide

LVGP. Advanced transformers built for the industrial environment. Catalog: LVGP-16C-English. By Micron Power Delivery. Supersedes: LVGP-16B-English

15 kva Isolation Transformer - Single Phase - 208V Primary - 120/240V Secondary - NEMA 3R

Description. Features and Benefits

Power-Sure 700. Technical Data TD158001EN. Contents

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

SECTION CABLE TRAYS

50-SDMS-01 SPECIFICATIONS FOR

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SPECIAL SPECIFICATION Inch LED Traffic Signal Lamp Unit

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

VIRGINIA TRANSFORMER CORP. Drive & Rectifier. Transformersrs

Component Requirement Specification for SGI 500XT Isolation Transformer

Variable Transformers Product Design & Engineering Data

Isolation Transformer Series

Transcription:

SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600 VAC and below, with system primary voltages of 4.16 KV and below. 1.2 REFERENCE STANDARDS 1.2.1 Dry-type transformers shall be designed, manufactured, tested and installed in accordance with the latest industry standards, including the following: 1.3 QUALITY ASSURANCE A. ANSI/IEEE C57.12.01 Test Code for Dry-Type Distribution and Power Transformers B. ANSI/IEEE C57.110 Recommended Practice for Establishing Transformer Capability When Supplying Non-Sinusoidal Load Currents C. NECA 409 Recommended Practice for installing and Maintaining Dry- Type Transformers D. NEMA ST1 Specialty Transformers E. NEMA ST20 Dry-Type Transformers for General Applications F. NEMA TP-1 Guide for Determining Energy Efficiency for Dry-Type Transformers G. NFPA-70 National Electrical Code H. UL Standard 506 - Transformers I. UL Standard 1561 K-rated Transformers 1.3.1 All transformers shall be designed, manufactured and tested in accordance with the latest applicable ANSI, NEMA and UL standards. 1.3.2 All transformers shall bear the Underwriters' Laboratories (UL) Label and shall be suitable for the intended use on the Project. 1.4 SUBMITTALS: 1.4.1 Submit product literature detailing the electrical and physical characteristics of the equipment, including: Dimensions, weights, lifting and installing provisions 16461-1 Dry Type Transformers

Voltage (primary and secondary) kva rating Percent impedance Tap configurations Insulation system type and rated temperature rise Sound Level Design Impedance K-Factor Rating (where applicable) Manufacturer s installation and maintenance manuals Energy Star Label compliance Basic Impulse Level (BIL) for transformers over 600 Volts. 1.4.2 Submit manufacturer s standard connection diagrams and installation instructions. 1.5 DELIVERY, STORAGE AND HANDLING 1.5.1 Provide for delivery, storage and handling of transformers per the manufacturer s guidelines. 1.5.2 Transformers delivered to the job site shall be inspected for damage caused in transit. 1.5.3 Store transformers per manufacturer s requirements in a clean, dry and protected space until moved to final installation. PART 2 - PRODUCTS 2.1 DRY-TYPE TRANSFORMERS GENERAL REQUIREMENTS 2.1.1 Transformer ratings and types shall be selected to match the requirements of the primary service and the types of load served. In most cases, a general purpose type of transformer shall be adequate for the load. For applications requiring isolation transformers, such as for motor variable speed drives, utilize a rated Drive Isolationtype transformer. For applications where large harmonic loads are anticipated, utilize a non-linear load-type transformer. 2.1.2 Transformers shall be designed and manufactured in compliance with NEMA ST-20 and UL 1561. 2.1.3 Transformers shall be capable of operating at 100% of nameplate rating continuously while in an ambient temperature of 40 O C (104 O F). 2.1.4 Transformer insulation materials shall be fire retardant and shall not support combustion. 2.1.5 Transformer windings and terminations shall be copper. 16461-2 Dry Type Transformers

2.1.6 Transformer sound levels shall not exceed the levels indicated below: Transformer KVA Maximum Sound Level (db) 15-50 45 51-150 50 151-300 55 301-500 60 2.1.7 Three phase transformers shall be wound in a Delta-Wye configuration unless otherwise required for the application. 2.1.8 Transformer core and coil assembly shall be grounded to the transformer enclosure by means of a visible, flexible copper grounding strap. 2.1.9 Enclosures for transformers shall be fabricated of minimum 12-gauge steel, properly cleaned, degreased and painted per the manufacturer s standard practice. Enclosures for indoor applications shall be NEMA 2 drip-proof rated, with ventilation openings protected against falling dirt. Enclosures for exterior applications shall be rated NEMA 3R minimum. 2.1.10 Maximum temperature at the top of the enclosure shall be 90 degrees C. 2.2. TRANSFORMERS GENERAL PURPOSE TYPE 2.2.1 Transformer insulation type shall be as follows: a. Less than 15 KVA: 185 degrees C insulation system with maximum 115 b. 15 KVA and above: 220 degrees C insulation system with maximum 115 2.2.2 Transformers shall conform to NEMA TP-1 requirements for energy efficiency and be Energy-Star listed. 2.2.3 Taps: a. 3 through 12 KVA: two 5% taps below rated primary voltage b. 15 KVA and above: six 2.5% taps, 2 above and 4 below rated primary voltage. 2.2.4 Core and Coil Assemblies: a. For transformers rated 9KVA and below, completely encapsulate the core and coil windings in a resin and aggregate to provide a moisture-proof and shock resistant seal, and to provide reduced sound levels. b. For transformers rated 15 KVA and above, core and coil assemblies shall be 16461-3 Dry Type Transformers

impregnated with non-hygroscopic, thermosetting varnish to reduce hot spots and seal out moisture. Mount assemblies to the transformer case with vibration-resistant pads. 2.3. TRANSFORMERS DRIVE ISOLATION TYPE 2.3.1 Isolation-type transformers shall generally be utilized when more than 20% of the load will be comprised of variable frequency motor drives or similar three-phase rectifier type loads. 2.3.2 Transformer windings shall be specially braced to withstand the thermal and mechanical stresses of DC drive current spikes. 2.3.3 Transformer windings shall incorporate an isolated and shielded secondary winding to provide greater isolation of drive noise coupling back to the primary windings. 2.3.4 Isolation transformer insulation type shall be as follows: a. 7.5 KVA and above: 220 degrees C insulation system with maximum 115 2.3.5 Taps: a. 5 KVA and above: two 5% taps, 1 above and 1 below rated primary voltage. 2.3.6 Core and Coil Assemblies: shall be impregnated with non-hygroscopic, thermosetting varnish to reduce hot spots and seal out moisture. Mount assemblies to the transformer case with vibration-resistant pads. 2.4. TRANSFORMERS NON-LINEAR LOAD TYPE 2.4.1 Non-linear load type (K-rated) transformers shall generally be utilized when more than 50% of the load will be comprised of single-phase computers or similar electronic power supply loads. K-factor shall be specified as required for the project. In general, K ratings of 4 or 13 shall be specified. 2.4.2 Transformer windings shall be specially braced to withstand the thermal and mechanical stresses of harmonic currents and voltages. 2.4.3 Transformer windings shall incorporate an isolated and shielded secondary winding to provide greater isolation of harmonic noise coupling back to the primary windings. 2.4.4 Transformer windings shall incorporate a 200% rated neutral winding and doublecapacity neutral terminations. 2.4.5 Isolation transformer insulation type shall be as follows: a. 15 KVA and above: 220 degrees C insulation system with maximum 115 16461-4 Dry Type Transformers

2.4.5 Taps: a. 500 KVA and below: six 2.5% taps, 2 above and 4 below rated primary voltage. b. 750 KVA and above: six 3.5% taps, 2 above and 4 below rated primary voltage. 2.4.6 Core and Coil Assemblies: shall be impregnated with non-hygroscopic, thermosetting varnish to reduce hot spots and seal out moisture. Mount assemblies to the transformer case with vibration-resistant pads. PART 3 - EXECUTION 3.1 INSTALLATION: 3.1.1 Transformers shall be installed in accordance with Article 450 of the National Electric Code (NEC) and the manufacturer's instructions 3.1.2 Provide proper spacing from walls in accordance with Articles 450-21 and 450-22 of the NEC to insure fire ratings of adjacent surfaces, for proper transformer ventilation and cooling.. 3.1.3 Mounting Considerations: 1-15 kva: Suitable for wall mounting. 30-75 kva: Suitable for floor or trapeze mounting. Larger than 75 kva: Suitable for floor mounting. 3.1.4 Provide vibration isolating pads suitable for isolating transformer noise and vibration from the building structure and use a minimum 2 foot length of flexible metal conduit to minimize noise transmission. 3.1.5 Provide concrete housekeeping pad for floor-mounted transformers. 3.1.6 Transformer grounding shall be in accordance with Article 250 of the NEC. 3.1.7 Verify final connections for proper application and workmanship prior to energizing. 3.1.8 Verify that all internal shipping braces and brackets are removed. 3.1.9 Check primary and secondary voltages and make appropriate tap adjustments after transformer energization to provide optimum voltage conditions to the utilization equipment. 3.1.9 Transformer installation shall be left neat and clean with all foreign material removed from inside and around enclosures. 16461-5 Dry Type Transformers

3.2 IDENTIFICATION 3.2.1 Label each transformer with laminated plastic nameplate, secured to the case with corrosion-resistant screws. END OF SECTION 16461 16461-6 Dry Type Transformers