Three-dimensional FEM model of an AC/DC hybrid high voltage transmission line to analyze the electrical field along composite insulators

Similar documents
Evaluation of coupling between dc and ac transmission lines on the same right-of-way: Parametric analysis and mitigation methods

Investigation of skin effect on coaxial cables

Identification of network models parameters for simulating transients

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Single-turn and multi-turn coil domains in 3D COMSOL. All rights reserved.

A6.6 9 th International Conference on Insulated Power Cables A6.6

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Transformers and power quality Part II. Modelling and researching generation of higher harmonics in small three-phase transformers

Analysis of Switching Transients of an EHV Transmission Line Consisting of Mixed Power Cable and Overhead Line Sections

Fatima Michael college of Engineering and Technology

Microwave Cancer Therapy

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

Numerical Simulation of PCB-Coil-Layouts for Inductive Energy Transfer

EE 740 Transmission Lines

Comparison of cable models for time domain simulations

EMERGING distributed generation technologies make it

Novel Simulation Method to Quantify Induced Voltage & Current between Parallel or Partially Parallel Proximity AC Transmission Circuits

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

HF Resonators for Damping of VFTs in GIS

Electric Field Analysis of High Voltage Condenser Bushing

FEM SIMULATION FOR DESIGN AND EVALUATION OF AN EDDY CURRENT MICROSENSOR

Accuracy of Lightning Surge Analysis of Tower Surge Response

EMT Model of the Sen Transformer for Fault Analysis Studies

Modeling and electromagnetic transients study of two 1800MVA phase shifting transformers in the Italian transmission network

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Testing 320 kv HVDC XLPE Cable System

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

HARMONIC ANALYSIS OF LEAKAGE CURRENT OF SILICON RUBBER INSULATORS IN CLEAN-FOG AND SALT-FOG

Critical Study of Open-ended Coaxial Sensor by Finite Element Method (FEM)

Analysis of lightning performance of 132KV transmission line by application of surge arresters

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

Overvoltages While Switching Off a HV- Transformer with Arc-Suppression Coil at No-Load

A Transmission Utility Approach to Electromagnetic Transient Analysis

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

Electromagnetic Wave Analysis of Waveguide and Shielded Microstripline 1 Srishti Singh 2 Anupma Marwaha

Dynamic Phasors for Small Signal Stability Analysis

Investigation of a Hybrid Winding Concept for Toroidal Inductors using 3D Finite Element Modeling

APPLICATION OF THE ELECTROMAGNETIC FIELD METHOD TO STUDY A COMMUNICATION SATELLITE SITE DAMAGED BY LIGHTNING

Electromagnetic Force Modification in Fault Current Limiters under Short-Circuit Condition Using Distributed Winding Configuration

Validation of the Experimental Setup for the Determination of Transmission Loss of Known Reactive Muffler Model by Using Finite Element Method

VARIATION OF LOW VOLTAGE POWER CABLES ELECTRICAL PARAMETERS DUE TO CURRENT FREQUENCY AND EARTH PRESENCE

Validation of power plant transformers re-energization schemes in case of black-out by comparison between studies and field tests measurements

Analysis and simulation of switching surge generation when disconnecting a combined 400 kv cable/overhead line with shunt reactor

How OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA

Power Transmission of AC-DC Supply in a Single Composite Conductor

ABSTRACTS of SESSION 6

Effect of Fault Resistance and Load Encroachment on Distance Relay- Modeling and Simulation PSCAD/EMTDC

About the High-Frequency Interferences produced in Systems including PWM and AC Motors

H. Arab 1, C. Akyel 2

1 Introduction General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Simultaneous AC-DC Transmission Scheme Under Unbalanced Load Condition

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Testing Firing Pulse Controls for a VSC Based HVDC Scheme with a Real Time Timestep < 3 µs

Mitigation Methods to Improve the Lightning Performance of Hybrid Transmission Line

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks

TRIGGERED by energy transition towards sustainability,

Compact Systems for HVDC Applications Dr. Denis Imamovic

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Nonlinear Shielded Multipair Railway Cable Modeling with COMSOL Multiphysics

DC current interruption tests with HV mechanical DC circuit breaker

CONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.

A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE

HVDC Transmission Using Artificial Neural Networks Based Constant Current and Extension Angle Control

Modelling of Voltage Regulation Issues in SWER Systems Using PSCAD/EMTDC

A Real-Time Platform for Teaching Power System Control Design

EE 340 Transmission Lines. Spring 2012

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Maximizing the Fatigue Crack Response in Surface Eddy Current Inspections of Aircraft Structures

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

Combined analytical and FEM method for prediction of synchronous generator no-load voltage waveform

Résumé.. Table of Contents List of Symbols and Abbreviations List of Tables List of Figures

Relevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines

Investigation of a Hybrid Winding Concept for Toroidal Inductors Using 3D Finite Element Modeling

Harnessing of wind power in the present era system

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

High Voltage DC Transmission 2

Simulation of line fault locator on HVDC Light electrode line

Bayesian Estimation of Tumours in Breasts Using Microwave Imaging

ABB September Slide 1

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Corona noise on the 400 kv overhead power line - measurements and computer modeling

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Effects of the Short-Circuit Faults in the Stator Winding of Induction Motors and Fault Detection through the Magnetic Field Harmonics

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION

Transient Finite Element Analysis of a SPICE-coupled Transformer with COMSOL Multiphysics

Analysis of Multiconductor Quasi-TEM Transmission Lines and Multimode waveguides

IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients

Transformer Engineering

Transcription:

Threedimensional FEM model of an AC/DC hybrid high voltage transmission line to analyze the electrical field along composite insulators D. Potkrajac, S. Papenheim, M. Kizilcay AbstractTo increase the power transfer capacity of existing lines, a transmission system operator in Germany plans to replace an existing 380kV threephase AC system into a bipolar HVDC system on the same tower that is called a hybrid line. Due to the proximity of AC transmission systems and the HVDC system electrical and magnetic coupling effects between those lines are present during system operation. The mutual influence of the electromagnetic fields between the AC and DC systems can cause changes in electrical components. The electrical performance of a composite insulator is affected by the electrical field distribution along its length and surface. The calculation of the electric field distribution is very important for the design of EHV transmission lines. The insulators are an important part of the transmission lines to prevent tripping of the transmission line by a flashover over the insulator. The electrical field distribution around the composite insulators and the heads of transmission towers is numerical calculated using finite element method. The calculations were executed in the time domain. A threedimensional (3D) model of a hybrid transmission line for a given tower configuration has been developed and the model is presented in this paper. The geometric dimensions and material properties of an insulator are taken into consideration. In this paper a field calculation program called COMSOL Multiphysics is used. COMSOL Multiphysics is a powerful simulation software that uses finite element method (FEM) to simulate multifield problems. COMSOL has the ability of spatial transient electromagnetic field calculation in time domain. The electrical field distribution around three 380kV AC System and one 400 kv bipolar DC system is analyzed. conversion of HVAC systems in existing lines to a HVDC system. This configuration is called a hybrid transmission line [1], [2] and [3]. A possible tower configuration is shown in Fig 1. 400kV DCSystem 380kV ACSystem (AC1) Fig. 1. AC/DC hybrid line + N 380kV ACSystem (AC2) Due to the proximity of HVDC and HVAC system electric and magnetic coupling effects are present. This paper focusses on the electrical field at the tower and the surrounding area. COMSOL, which makes use of the FEM method is used for the investigations. The software utilizes Maxwell s equations for steady state and transient calculations. II. AC/DCHYBRIDLINE IN 2DSPACE Keywords: FEM., Three dimensional, AC/DC hybrid, COMSOL Multiphysics I. INTRODUCTION The electrical power consumption in the world is growing and therefore there is a need for additional capacities in form of new transmission lines. Beside common HVAC technology HVDC technology is considered to be an attractive alternative, due to lower losses, better controllability and the lack of reactive power consumption. The erection of new transmission lines is often associated with demanding approval procedures and conflicts of interests. One possible solution is the D. Potkrajac, S. Papenheim and M. Kizilcay are with the Dept. of Electrical Eng. and Computer Science of the University of Siegen in Siegen, Germany. (email of corresponding author: dejan.potkrajac@unisiegen.de) Paper submitted to the International Conference on Power Systems Transients (IPST2017) in Seoul, Republic of Korea June 2629, 2017 A. Electrical field and potential formulation in COMSOL Multiphysics Finite element numerical model was used in COMSOL Multiphysics to calculate electrical field. The following Maxwell s equations were used for simulations [4]. E = Ñ V (1) Ñ J = Q (2) dd J = s E+ + Je dt (3) E is the electrical field intensity, J is the current density s is the conductivity, D is the electrical flux density and J is the externally generated current density [4]. Fig. 2 e illustrates the 2D arrangement of the simulation models with the associated boundary conditions. For the outer cut surface a

homogeneous Neumann boundary condition is applied. The bottom surface (ground) is set to Dirichlet boundary condition of 0 V. Table 1 documents the specific parameters of the simulation model. Neumann V = 0 V V DC + V DC N V V AC 2 L 3 V AC 2 L 1 n conversion to a hybrid tower. 2 x 380kV AC 400kV DC + N VDC V AC 1 L 2 V AC 2 L 2 y x V AC 1 L 3 V AC 1 L 1 Ground V = 0 Dirichlet Fig. 2. 2DSpace Model of AC/DC hybrid line including the boundary condition TABLE I PARAMETERS OF THE SIMULATION MODEL HVDCSystem 380kVACSystem (AC1) 380kVACSystem (AC2) Ground Wire V DC+ =400 kv V DC N =0 V V DC =400 kv V =380 kv sin(ωt) V =380 kv sin(ωt +2π/3) V =380 kv sin(ωt 4π/3) V =380 kv sin(ωt) V =380 kv sin(ωt +2π/3) V =380 kv sin(ωt 4π/3) V =0 V Fig. 4a. 3 x 380kV AC systems Fig.4b. 1 x bipolar HVDC system and 2x380kV AC systems A detailed view of the electrical field at 2 m above the ground is shown in Fig. 5 for the transmission tower with three AC systems. The meshed surface is a result of the superposition of discrete time points. The electrical field of the AC/DC hybrid transmission line is shown in Fig. 6. The electrical field of the hybrid line is more unsymmetrical and has a higher amplitude under the HVDC system compared with the pure AC transmission line. B. Influence of the DC systems on the ACsystem To study the basic phenomena in the time domain only the conductors, including the ground wires, are modelled in COMSOL. The tower is neglected. Fig. 3 shows the 2D model and visualizes the electrical potential in kv. Fig. 5. Electrical field 2 m above the ground level 3x 380kV AC systems Fig. 3. Electrical potential of the simulated AC/DC hybrid line To investigate the influence of the hybrid transmission line, two simulations are carried out. Fig. 4 shows the transmission tower before (see Fig. 4.a) and after (see Fig. 4.b) the Fig. 6. Electrical field 2 m above the ground level 1x bipolar HVDC system 2x 380kV AC systems

For verification purposes the position of the HVDC system is changed (see Fig. 7). The simulation results are shown in Fig. 8 to Fig. 10. At all configurations the electrical field under the HVDC system has a higher amplitude compared to the pure HVAC systems (see Fig. 5). 400kV DC + N 400kV DC + N 400kV DC N + Fig. 10. Electrical field 2 m above the ground level for the third configuration AC/DC hybrid line first configuration AC/DC hybrid line second configuration Fig. 7. Three different configurations of the AC/DC hybrid line AC/DC hybrid line third configuration Furthermore, the influence of transposed phase conductors of a ACSystem on the electrical field will be investigated. For this investigation, the phase arrangement of the AC/DC hybrid line corresponds to the first configuration (see Fig.7). The following configuration is used for the transposition. L 1 L 2 L 2 L 1 L 3 Fig. 11. Transposition scheme L 3 Fig. 8. Electrical field 2 m above the ground level for the first configuration In this investigative series two different scenarios exist. In the first scenario only the conductors of the 380kV AC system AC1 will be transposed. In the second scenario only the conductors of the 380kV AC system with the identifier AC2 will be transposed. Table 2 documents clearly the individual scenarios. Fig. 12 and the Fig. 13 illustrate the electrical field for both scenarios. Fig. 9. Electrical field 2 m above the ground level for the second configuration Scenario 1 (AC/DC hybrid line first configuration) Scenario 2 (AC/DC hybrid line first configuration) TABLE II TWO DIFFERENT SCENARIOS AC1 AC2 AC1 AC2

Fig. 12. Electrical field 2 m above the ground level for the first scenario (AC/DC hybrid first configuration) Fig. 14. The coupled fundamental frequency voltage on the conductors of DC poles using COMSOL Multiphysics To verify the computations by COMSOL Multiphysics the simulation program PSCAD/EMTDC [7] is used. The same tower geometry that was used in COMSOL is now used in PSCAD/EMTDC to model the transmission lines. Fig. 15 illustrates the simplified simulation model. The transmission lines are energized through two 380kV AC systems, and the 50Hz components are measured on the HVDC lines. 50Hz Energization of AC/DC hybrid line DC Fig. 13. Electrical field 2 m above the ground level for the second scenario (AC/DC hybrid first configuration) As it can be seen from the figures, the electric field is additionally influenced by the arrangement of the individual phases. A homogenization of the electrical field in scenario 1 is recognizable. In scenario 2 it can be seen that this transposing configuration has a major influence on the electrical field. C. Influence of ACsystems on DCsystem The HVAC systems work with a base frequency of 50Hz in the considered case. Due to the proximity, the HVDC system is stressed with a permanent 50Hz signal, resulting from capacitive coupling as in this simulations only the electrical filed is considered. The 2D simulation model is used again for the computations (see Fig. 3). Fig 14 shows the simulation results in the time domain for the 50Hz coupled voltages in the three conductors of the HVDC system. The voltages are unsymmetrical and in the range of 40 kv. U50 Hz 380 kv AC1 Open End 380 kv AC2 Open End Fig. 15. Simplified simulation model in PSCAD/EMTDC Comparing the results from the Fig. 14 and the Fig. 16, it can be seen that they are nearly identical. Completely different computation program produces in this case the same 50Hz coupled voltages in the three conductors of the HVDC system. Fig. 16. The coupled fundamental frequency voltage on the conductors of DC poles using PSCAD/EMTDC

III. AC/DCHYBRIDLINE IN 3DSPACE As the HVDC system is stressed with a DCfield and a superimposed fundamental frequency field the influence of the insulators plays an important role. For this purpose the 2D model was expanded to a 3D model. The boundary condition that were used for 2D model are also used for the 3D model. The 3D model represents a 500 m section of a hybrid line and is shown in Fig 17. Besides the conductors the tower, ground wires and insulators are considered (see detailed view in Fig. 18). TABLE III INSULATOR PARAMETER SIR relative permittivity 4.3 FRP relative permittivity 7.2 The amplitude of the electrical field along the insulator of the HVAC system for three different time steps is shown in Fig. 20. As it can be seen the electrical field changes along the insulator and is time dependent ranging from MIN to MAX. A 2D representation of the array of curves of the electrical potential at different time points is shown in Fig 21. The electrical potential has the highest amplitude near the conductor and reaches zero at the grounded tower. Fig. 17. 3D model of the hybrid transmission line in COMSOL Fig. 20. Electrical field along an ACinsulator t start=0 t mid=0.03s t end=0.06 s Fig. 18. 3D model of the hybrid transmission line (detailed view) The core of the composite insulator consists of Fiber Reinforced Plastic (FRP). For the electrical insulation of the core and to protect the core from weather sheds a Silicon Rubber (SIR) is used. Fig. 19 shows the 3D model and the cross section view of the composite insulator. The simulation parameters of the insulator are given in Table 3 [5]. 3Dstructure of the composite insulator Fig. 19. Structure of a composite insulator FRP core 2DCross section view of composite insulator Fig. 21. Electrical potential along an ACinsulator for different time steps The results for the composite insulator of the HVDC system are shown in Fig. 22 for the same three different time points. A constant DCcomponent can be observed. ACcomponents are not visible at the first point of view. The 2D representation of the array of curves of the electrical potential for different time points is show in Fig. 23. In the detailed view (see Fig.24) the influence of the fundamental frequency coupling is visible as the different curves form an area. With a pure HVDC system only a solid line would be visible.

Fig. 22. Electrical field along a HVDCinsulator (positive pole) t start =0 t mid =0.03s t end =0.06 s Fig. 23. Electrical potential along HVDCinsulator (positive pole) for different time steps Fig. 24. Electrical potential along HVDCinsulator (positive pole) for different time steps (detailed view) When the electrical potential along the insulator at the negative pole of the HVDC system is considered, the influence of the fundamental frequency coupling is visible. t start =0 IV. CONCLUSIONS Hybrid transmission lines with AC and DC systems on the same tower is a new technology and a lot research is currently done. Due to the proximity of the AC and DC systems magnetic and capacitive coupling are present. For the calculation of these effects several simulation tools are available like circuit based EMTP or FEM software. COMSOL Multiphysics was primarily used for the investigations in this paper, focusing on the electrical field for pure ACtransmission lines and hybrid AC/DC lines. 2D and 3D models were developed. The 2D model was used for the calculation of the electrical field under the transmission line. With a DCsystem the amplitude of the field is amplified due to the constant potential of the HVDC conductors and the alternating potential of the AC systems. The second investigation in 2D space focused on the coupling from the AC line to the DC line. A fundamental frequency component appears in the DC line which is superimposed on the DC quantities. The 3D model, containing detailed representation of conductors, towers and composite insulators, was used to study the stress on the composite insulators of AC and DCsystems. The insulators of the DC system, that are assumed as the same as for ACsystems, are exposed to a constant and a superimposed AC electrical field. V. REFERENCES [1] J. Knauel, A. Wagner, R. Puffer, J.M. Seifert, S. Liu, M. Brückner, B. Rusek, S. Steevens, A. Gravelmann, K. Kleinkorte, Behaviour of insulators under hybrid electrical AC/DC field stress, Cigre2014 [2] B. Rusek, K. Vennemann, J. Velasquez, K. Kleinekorte, C. Heising, and V. Staudt, Special requirements regarding VSC converters for operation of hybrid AC / DC overhead lines, in CIGRE Symp. 2014 [3] M. Kizilcay, A. Agdemir, and M. Losing, Interaction of a HVDC System with 400kV AC systems on the same tower, in Int. Conf. Power.Syst. Transients, Kyoto, 2009, pp. 3 6 [4] COMSOL Multiphysics User s Guide, Version 4.3, May 2012 [5] Arshad, A. Nekahi, S. G. McMeekin and M. Farzaneh, Effect of Pollution Layer Conductivity and Thickness on Electric Field Distribution along a Polymeric Insulator, 2015 Comsol conference Grenoble [6] A. Majzoobi, I. A. Joneidi, S. Mohajer, H.Mohseni, A. A. Shayegani 3D modeling of Electrical Field and Electrical Potential in different contamination condition in Polymeric Insulator, International Symposium on High Voltage Engineering, Hannover, Germany, August 2226, 2011 [7] User s Guide PSCAD Power Systems Computer Aided Design, Ver. 4.2.1, Manitoba HVDC Research Center, Winnipeg, Canada, 2010 t mid =0.03s t end =0.06 s Fig. 25. Electrical potential along HVDCinsulator (negative pole) for different time steps