Assessment of Saturable Reactor Replacement Options

Similar documents
CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

ELEMENTS OF FACTS CONTROLLERS

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

Power Quality enhancement of a distribution line with DSTATCOM

Fundamental Concepts of Dynamic Reactive Compensation. Outline

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

Simulation Study of a Monopole HVDC Transmission System Feeding a Very Weak AC Network with Firefly Algorithm Based Optimal PI Controller

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Long lasting transients in power filter circuits

Voltage Source Converter Modelling

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Facilitating Bulk Wind Power Integration Using LCC HVDC

Control of Over-voltages on Hydro-Québec 735-kV Series-Compensated System During a Major Electro-mechanical Transient Disturbance.

SRI VIDYA COLLEGE OF ENGG AND TECH

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

U I. HVDC Control. LCC Reactive power characteristics

Power Quality Basics. Presented by. Scott Peele PE

ESB National Grid Transmission Planning Criteria

ABB Power Systems AB Sweden

Chapter 10: Compensation of Power Transmission Systems

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

EH2741 Communication and Control in Electric Power Systems Lecture 2

Voltage-Current and Harmonic Characteristic Analysis of Different FC-TCR Based SVC

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

High Voltage DC Transmission 2

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Modelling of the back-to-back converter between Uruguay and Brazil in A.T.P.

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System

II. RESEARCH METHODOLOGY

DYNAMIC PERFORMANCE OF THE EAGLE PASS BACK-TO-BACK HVDC LIGHT TIE. Å Petersson and A Edris ABB Power Systems AB, Sweden and EPRI,USA

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

Transients under energizing multiple power filter circuits

Analysis of a 405 km transmission line with series compensation

Reactive Power and AC Voltage Control of LCC HVDC System with Digitally Tunable Controllable Capacitors

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

ANALYSIS OF MULTI-TERMINAL HVDC TRANSMISSION SYSTEM FEEDING VERY WEAK AC NETWORKS

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Insulation Co-ordination For HVDC Station

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Investigation of D-Statcom Operation in Electric Distribution System

SERIES ACTIVE power filters have proved to be an interesting

Design and Simulation of Passive Filter

Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK

Implementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool

Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

DC current interruption tests with HV mechanical DC circuit breaker

Topics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

Analysis the Modeling and Control of Integrated STATCOM System to Improve Power System

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Great Northern Transmission Line: Behind the (Electrical) Design

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

INVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

Testing Firing Pulse Controls for a VSC Based HVDC Scheme with a Real Time Timestep < 3 µs

each time the Frequency is above 51Hz. Continuous operation is required

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

Solving Customer Power Quality Problems Due to Voltage Magnification

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne**

Transients impact on power filter circuit sizing

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Enhancing Power Quality in Transmission System Using Fc-Tcr

Dynamic Performance Evaluation of an HVDC Link following Inverter Side Disturbances

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Central East Voltage and Stability Analysis for Marcy FACTS Project Phase I

Power Quality and the Need for Compensation

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Volume I Issue VI 2012 September-2012 ISSN

Voltage Control and Power System Stability Enhancement using UPFC

Design and Control of Small Scale Laboratory Model of a Thyristor Controlled Series Capacitor (TCSC) to Improve System Stability

DESIGN CONSIDERATIONS OF ULTRA HIGH VOLTAGE DC SYSTEM

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Conventional Paper-II-2011 Part-1A

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

Transcription:

Assessment of Saturable Reactor Replacement Options D.T.A Kho, K.S. Smith Abstract-- The performance of the dynamic reactive power compensation provided by the existing variable static compensation (STC) on the UK side of the Cross-Channel HVDC link has been assessed. These uniquely designed STCs are now being considered for replacement. Alternatives to provide the same performance as delivered by the existing STCs have been proposed and their overvoltage suppression performances have been assessed against the existing STCs using a PSCAD-EMTDC model of the England-France HVDC link. The paper demonstrates how the PSCAD-EMTDC simulation has been used to make informed design decision concerning the STC replacement option. Keywords: Saturable reactor, Temporary overvoltage, HVDC link, Thyristor Controlled Reactor (TCR), PSCAD-EMTDC. T I. INTRODUCTION HE original Cross-Channel HVDC link was on the UK side, designed with three Saturable Reactors installed, two at Sellindge and one at Ninfield. These were installed with their primary function to manage the transient overvoltages (TOV) following HVDC converter blocking. The saturable reactors show signs of aging and there is a need to plan for their replacement. Five initial replacement options are being considered, (i) Like for like replacement 3 x 1 MVAr saturable reactors to be installed at the existing locations, (ii) Thyristor Controlled Reactors (TCR) units have been proposed at existing locations and potentially at additional locations, (iii) Shunt reactor solutions 5 x MVAr standard 400 kv shunt reactors with auto switching system, (iv) auto-tripped ac harmonic filters and (v) a hybrid combination of TCRs and auto-switched shunt reactors or auto-tripped ac harmonic filters. The technical risks involved in each of the above options need to be carefully considered. Although the existing saturable reactors resolve the transient overvoltage, their unique design means there is limited support. The alternative options of TCRs and auto-switched shunt reactors appears to be feasible, however the specification required to enable satisfactory operation across the period of the initial overvoltage is unclear. Given that the original TOV characteristics on which the design of the saturable reactor operation is based is not available, and that the actual requirement may have changed over time, it is difficult to design and specify the control systems for both the TCR and auto-switched shunt reactor options. This paper summarises the study undertaken to assess the voltage waveform during transient disturbances, particularly following ac side faults, leading to converter blocking, filter islanding and ultimately bipole connection trip. The PSCAD-EMTDC model of the recent IFA0 refurbishment project had been used throughout the study. The performance of the three replacement options have been compared in the context of TOV suppression due to faults. II. STC REPLACEMENT OPTIONS A. Like for Like Replacement - Variable Static Compensation (STC) The existing STC at the Sellindge side (one on each Bipole) consists of one saturable reactor, four filter banks (2x84 MVAr switched and 1x47 MVAr, 1x15.6 MVAr unswitched) and one earthing transformer as shown in Fig. 1. The saturable reactor provides the variable reactive element which has an automatic overload capability. To obtain the desired slope characteristics, a slope correcting capacitor is connected in series to increase the slope of the STC. The voltage-current characteristics of the PSCAD-EMTDC saturable reactor model with and without the slope-correcting capacitors are shown in Fig. 2. A bypass damping filter was provided for the overall series capacitor arrangement to inhibit sub-harmonic oscillations. More background information on the existing dynamic compensation is available in the technical literature. [1], [2], [3], [4]. D. T. A Kho is with Mott MacDonald Ltd, 1 Atlantic Quay, Broomielaw, Glasgow, Scotland, UK. (e-mail: denis.kho@mottmac.com). K. S. Smith is with Mott MacDonald Ltd, 1 Atlantic Quay, Broomielaw, Glasgow, Scotland, UK. (e-mail: Kenneth.Smith@Mottmac.com). Paper submitted to the International Conference on Power Systems Transients (IPST2013) in Vancouver, Canada July 18-20, 2013. Unswitched filters Saturable reactor with slope correction circuit Fig. 1. PSCAD representation of the STC Switched filters

Each STC is fed from a 1 MVA 400/56.6 kv star-delta step-down transformer. During normal operating condition, the STC will be expected to operate in an approximately floating condition, i.e. zero reactive absorption. This is achieved by appropriately setting the tap on the step-down transformer. A simple control scheme has been implemented to control the switched filter banks based on a typical STC operating characteristic shown in Fig. 3. The control scheme will switch the filter banks based on current in the saturable reactor, i.e. when the reactor current is maximum, a bank is deenergised; when the reactor current falls to a minimum, a bank is energised. The bank switching is time delayed by 1 s, which is not expected to operate during the transient time frame considered in the study. 71 69 67 with a reference signal V ref, and an error signal is input into the controller transfer function. The output of the controller is a per-unit susceptance signal B ref, which is generated to reduce the error signal to zero in the steady state. The susceptance signal is subsequently transmitted to the gate-pulse-generation circuit, which produces appropriate firing pulses for the thyristor-controlled reactor and the thyristor switched capacitors in the case of SVC. A typical PSCAD-EMTDC phase locked loop based firing angle control has been used to generate the firing pulses for the thyristors. The TCR model and its control circuit have been tested in a simple PSCAD-EMTDC model with MVAr reactive load rejection and acceptance. The calculated firing angle, the reactive power and the per unit RMS voltage at the TCR terminal are shown in Fig 6 to Fig. 8. The response of the TCR control circuit to the transient voltage disturbances is acceptable. Voltage (kv) 65 63 61 59 57 55 0 0.2 0.4 0.6 0.8 1 1.2 1.4 Current (ka) Fig. 4. Three phase delta connected TCR Slope-corrected Saturable Reactor Saturable Reactor without slope-correction capacitor Fig. 2. VI characteristics of Saturable Reactor 20 Saturated reactor current (A) 0 10 0 0 0 - -1 - - 0 1 Reactive power (MVAr) No switched filters One Switched filters Two switched filters Fig. 3. STC operating characteristics B. TCR Option One of the potential replacement options is the use of Thyristor controlled reactors (TCR). It is assumed that the saturable reactor and the associated 56 kv switched capacitor banks on each bipole will be replaced by a TCR. A three-phase delta connected TCR as shown in Fig. 4 has been implemented in PSCAD-EMTDC using a typical standard thyristor model with typical snubber circuit of resistance and capacitance values. Different reactor sizes have been considered. A typical voltage regulator used in a Static VAr Compensator (SVC) [5] as shown in Fig. 5 has been adapted for the TCR control. The measured control variables V meas are compared Fig. 5. Three phase delta connected TCR C. Auto-switched Shunt Reactor Option The overvoltage suppression performance utilizing autoswitched shunt reactors at the Sellindge converter station has also been assessed. With this option, two 400 kv shunt reactors will be connected on each bipole at Sellindge. The study has assumed a star-grounded connection for each shunt reactor. The automatic switching scheme is implemented based on the rate of change of the 400 kv RMS voltage at Sellindge converter station calculated without the dynamic compensation. D. Auto-tripped AC filters The tripping logic will compare the ac RMS voltage at Sellindge and send the switching signals to the respective filters at Sellindge converter station. The time delays were originally set to ms, 2 ms and ms for the filter no. 2, filter no.3 and filter no.4 respectively for each bipole. Shorter time delays have been considered to examine the benefit and effectiveness of tripping the filter to control the dynamic ac overvoltage at Sellindge. E. Combined Solutions The combined 56 kv 2x2 MVAr TCR and the 400 kv 2x MVAr auto-switched shunt reactor configuration has

been considered as an alternative option to replace the existing STC. Fig. 6. TCR control test firing angle Fig. 7. TCR control test reactive power absorption Fig. 8. TCR control test RMS voltage at the TCR terminal III. SIMULATION AND RESULTS A. Short Circuit Ratio (SCR) Consideration The short circuit level of 4800 MVA was used to represent the Sellindge 400 kv ac equivalent in the PSCAD-EMTDC model, which corresponds to the extreme minimum short circuit level. This gives a short circuit ratio (SCR) of less than 3 which corresponds to the worst case scenario in the context of dynamic overvoltage. For example, when there is an interruption to the dc power transfer, the reactive power absorption of the HVDC converters drops to zero; with a low SCR system, the resulting increase in the alternating voltage due to shunt capacitors and harmonic filters could be excessive. This worst case scenario has been considered in the study so that the performance of the existing STCs can be determined to provide the base criteria for the STC replacement option. The drawback in terms of the study is that it is necessary to increase the ac terminal voltage of the equivalent source at Sellindge and Les Mandarins to a high value in order to obtain the required ac system voltage level of 1.03 pu and the desired power transfer of 0 MW across the HVDC link. In cases where a sustained fault has been considered, the converter will block the power transfer in ms and the 400 kv circuit breakers will open to isolate HVDC link from the ac equivalent source. Consequently, the calculated 400 kv ac system voltage level returns to the high initial set point. B. PSCAD-EMTDC HVDC Link Model The PSCAD-EMTDC model of the HVDC link created during the recent refurbishment exercise has been used for the study. The HVDC transmission scheme consists of two bidirectional bipole HVDC links between England and France, each of 0MW capacity; thus, each 12 pulse bridge converter has a power capability of 0 MW giving the two bipoles a rating of 0MW. The nominal HVDC voltage per 12 pulse monopole is 270 kv, and so the nominal maximum current is 1.852 ka. The DC current is carried by undersea cables, the land sections of these being buried underground. The transmission scheme connects to the Hz 400 kv AC network on either side of the link. The England side converters are located at Sellindge and the France side converters are located at Les Mandarins. The PSCAD HVDC link model, with a modified short circuit ratio has been verified against recorded data during a recent fault incident. The PSCAD- EMTDC calculated Sellindge RMS voltage profiles for the single phase to ground fault at Les Mandarins for the first ms after the fault occurrence plotted against the recorded RMS voltage waveforms from the fault incident are shown in Fig.9 to Fig.11. The results show that the PSCAD-EMTDC model used for the study is accurate reproducing the measured fault response. In addition, a transient three phase fault (1 ms) at the Les Mandarins side of the converter station has been simulated, with power transfer from France to UK at the worst case shortcircuit ratio. Assuming all the filter banks at the STCs are switched on, the RMS voltage profiles calculated at Sellindge with and without the existing STCs are shown in Fig. 12. The results show that the initial voltage transients contain damped oscillatory component at subsynchronous frequency (30 Hz 40 Hz). It is observed that the combined series capacitor and the damping filters are tuned at round about 35 Hz. The inductance of the saturable reactor reduces to 0.029 H during the fault period, wtih reactive power absorption of approximately 600 MVAr on each saturable reactor. Note that the inductance (0.029 H) when connected in series with the slope correcting capacitance of 451 µf has a natural frequency of 44 Hz, which is close to the frequency of the initial voltage oscillation. Furthermore, this voltage oscillation can be replicated using a simple test network model consisting of the Sellindge voltage source and the saturable reactor model and some capacitive and inductive loads to represent the reactive power absorption of the HVDC link. These results are consistent with the transient overvoltage results documented in [1] and [4].

Recorded RMS voltage (kv) 2 1 PSCAD simulation Time (s) 0 0.05 0.1 0.15 0.2 23.08 23.13 23.18 23.23 23.28 Recorded Time (s) Vr rms recorded PSCAD_Vrms_A Fig. 9. Comparison of the PSCAD simulated RMS voltage plots and the recorded data from the single phase to ground fault incident (Phase A voltage) Recorded RMS voltage (kv) 2 1 PSCAD simulation Time (s) 0 0.05 0.1 0.15 0.2 23.08 23.13 23.18 23.23 23.28 Recorded Time (s) Vy rms recorded PSCAD_Vrms_B Fig. 10. Comparison of the PSCAD simulated RMS voltage plot and the recorded data from the single phase to ground fault incident (Phase B voltage) Recorded RMS voltage (kv) 2 1 PSCAD simulation Time (s) 0 0.05 0.1 0.15 0.2 23.08 23.13 23.18 23.23 23.28 Recorded Time (s) Vb rms recorded PSCAD_Vrms_C Fig. 11. Comparison of the PSCAD simulated RMS voltage plot and the recorded data from the single phase to ground fault incident (Phase C voltage) 2 1 2 1 2 1 PSCAD simulated RMS voltage (kv) PSCAD simulated RMS voltage (kv) PSCAD simulated RMS voltage (kv) directions. The results of the overvoltage suppression performance during a transient three phase to ground fault, with and without the saturable reactors for different power transfer directions are shown in Fig. 13 and Fig. 14. The results indicate that the existing saturable reactors do not have a significant influence on the initial RMS voltage dip at Sellindge when the fault occurs. The influence of the saturable reactors on the transient overvoltage can be observed during the transient/sustained fault period before the fault is cleared. The results also show that the saturable reactor has little impact on the rate and the percentage of RMS voltage rise during the fault clearing period, which is apparent for the case with pre-fault power transfer from UK to France (Fig. 13). D. Dynamic Overvoltage Suppression with the TCR Option When a three phase fault occurs close to the rectifier (Les Mandarins), the ac voltage collapses to zero and the dc system shuts down. The converter reactive power absorption reduces to zero, while the TCR control reduces the firing angle to increase the reactive power absorption, offsetting the surplus of reactive power at Sellindge during the transient fault duration. This is shown in Fig. 15. The overvoltage suppression performances of different TCR sizes have been compared with that of the existing STCs and are shown in Fig. 16. The study results show that replacing the existing STCs with 3 MVAr TCRs at the Sellindge converter station (one at each bipole) can match the performance of the existing STCs under both power transfer directions between UK and France. 1.5 1.4 1.3 1.2 Without STCs With STCs RMS voltage (pu) 1.1 1 0.9 0.8 0.7 0.6 0.5 0.40 0.45 0. 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 1.00 1.05 1.10 1.15 1.20 Time (s) Case1A-STC in service Case1B-STC out of service Fig. 12. Simulated RMS voltage profile at the Sellindge converter station obtained from the initial model validation exercise for the HVDC link with and without the existing STCs. Fig. 13. Comparison of the average RMS voltages at Sellindge converter station with and without saturable reactor, when a transient three phase to ground fault occurred at Les Mandarin, pre-fault power transfer from UK to France C. Dynamic Overvoltage Suppression with the Existing STC (Saturable Reactor) The overvoltage suppression performance of the existing STCs have been assessed using the PSCAD-EMTDC model of the HVDC link. The study has focused on transient and sustained three phase to ground faults at the Les Mandarins converter station with different pre-fault power transfer

RMS voltage (pu) 1.5 1.4 1.3 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1 1.15 1.2 Time (s) Case3A-STC in service Case3B-STC out of service Fig. 14. Comparison of the average RMS voltages at Sellindge converter station with and without saturable reactor, when a transient three phase to ground fault occurred at Les Mandarin, pre-fault power transfer from France to UK. Fig. 15. TCR option - reactive power absorbed by the TCR (upper plot), TCR firing angle (lower plot) RMS voltage (pu) 1.4 1.3 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 Time (s) Case3A-Sat Reactor Case3C-2x4 MVAr TCR Case3D-2x3 MVAr TCR Case3E-2x2 MVAr TCR Fig. 16. TCR options - comparison of the average RMS voltages at Sellindge converter station for a transient three phase to ground fault at Les Mandarin, pre-fault power transfer from France to UK. breaker operation. The overvoltage suppression effect by the auto-tripped ac harmonic filters can be observed in Fig. 17 for a sustained three phase fault. However, this cannot match the fast response of the existing STCs (saturable reactors and the switchable capacitor banks) during the first 1 ms / ms of the fault depending on the time delay settings. F. Dynamic Overvoltage Suppression with the Autoswitched Shunt Reactors The 1x MVAr, 1x1 MVAr auto-switched shunt reactors configuration (per bipole) has been considered for the transient three phase fault scenario. The simulations show that the response of the auto-switched shunt reactors cannot match the response of the saturable reactors in terms of transient overvoltage suppression. The results also show that the system may experience an undesirable voltage dip when the fault is cleared and subsequently the shunt reactors switch off. These voltage depressions are more severe as the size of the shunt reactors increases. Sustained three phase fault conditions have been considered with different sizes of shunt reactors. In the case with the pre-fault power transfer from the UK to France and a three phase fault occurring close to Les Mandarins converter station, the study has shown that 1x MVAr autoswitched shunt reactors can be used to match the existing STCs performance, if the initial average transient overvoltage of 1.26 pu with a duration of 1 ms is acceptable as shown in Fig. 18. In the case with the pre-fault power transfer from France to UK and a three phase fault occurs close to Les Mandarins converter station, 1x MVAr, 1x MVAr autoswitched shunt reactors can be used to match the existing STCs performance, if the initial average transient overvoltage of 1.33 pu for a duration of 1 ms is tolerable. This is shown in Fig. 19. G. Dynamic Overvoltage Suppression with the Combined TCR and Auto-switched Shunt Reactors The study shows that a combination of TCR and autoswitched shunt reactor can be used to match the existing STCs response for both transient and sustained three phase fault close to Les Mandarins, if the initial transient overvoltage of slightly above 1.2 pu within the first ms after fault occurrence is acceptable. This is shown in Fig. 20. Alternatively, a combined TCRs and auto-tripped ac harmonic filters may also be used, which will be more economically favorable. E. Dynamic overvoltage suppression with the autotripped harmonic filters The dynamic response of the existing saturable reactor cannot be matched using auto-tripped harmonic filters. The auto-tripped ac harmonic filters option does not contribute towards the overvoltage suppression during short duration transient three phase fault conditions. This is due to the time delay required for the overvoltage detection and circuit

Fig. 17. Auto-tripped AC filters - comparison of the overvoltage suppression performance at Sellindge between saturable reactor and the auto-tripped filters option for a transient three phase to ground fault at Les Mandarin, prefault power transfer from France to UK Fig. 18. Auto-switched shunt reactors - comparison of the overvoltage suppression performance at Sellindge between saturable reactor and the autoswitched shunt reactors option for a transient three phase to ground fault at Les Mandarin, pre-fault power transfer from UK to France IV. CONCLUSIONS This paper has described the basic operation of the existing variable static compensation implemented at the English terminal of the Cross Chanel HVDC link. The STCs utilise three 56 kv 1 MVAr saturable reactors, two at Sellindge and one at nearby Ninfield 400 kv substation. Several replacement options for the existing STC have been described. The dynamic overvoltage suppression performance of the replacement options have been benchmarked against that of the existing STC units using PSCAD-EMTDC simulation studies. The paper demonstrates how such computer simulations are used in practice as an engineering tool to assess the viability of the proposed replacement options for the existing life expired STCs. The PSCAD-EMTDC study shows that it is possible to match the existing overvoltage suppression performance with appropriately sized TCRs. The auto-tripped filters and autoswitched shunt reactors options only show marginal benefit if they are implemented as a standalone replacement option to the existing STCs. The study has shown that due to the time delay settings and the circuit breaker operating time, these two options are unable to match the overvoltage suppression performance of the existing STCs during a transient three phase fault. The possibility of a hybrid auto-switched shunt reactor and TCR solution may be a favourable option in terms of cost effectiveness and further work has been carried out to examine the appropriate balance of static and dynamic equipment that would be required. Fig. 19. Auto-switched shunt reactors - comparison of the overvoltage suppression performance at Sellindge between saturable reactor and the autoswitched shunt reactors option for a transient three phase to ground fault at Les Mandarin, pre-fault power transfer from France to UK V. REFERENCES [1] H. Allon, G.E. Gardner, L.A. Harris, I.M. Welch, H.L. Thanawala, D. J. Young, "Dynamic Compensation for the England France 0 MW HVDC Link," Cigre International Conference on Large High Voltage Electric Systems 1982 Session 14-04-1982. [2] A. R. Wells and M. Dang, Reactive Power Compensation Requirements for the 0 MW D. C. Link with E.de.F. Under Light Load and Peak Load Condition, System Technical Branch Report TPR- ST/3/82, Central Electricity Generating Board, 25 February 1982. [3] H. Allon, G.E. Gardner, Voltage Disturbance Control For 0 MW HVDC Link, System Technical Branch Report PL-ST/8/80, Central Electricity Generating Board, June 1980 [4] G.L Brewer, I.M. Welch, C. Horwill, H.L. Thanawala, D.J. Young, The Application of Static VAR Compensators to the English Terminal of the 0 MW HVDC Cross Channel Link, Cigre International Conference on Large High Voltage Electric Systems 1986 Session 14-07. [5] R. Mohan Mathur, Rajiv K. Varma, Thyristor-based Facts Controllers for Electrical Transmission Systems, IEEE Press, Wiley-Interscience, 2, p.114. Fig. 20. Comparison of the overvoltage suppression performance at Sellindge between saturable reactor and the combined TCR (2x2 MVAr) and autoswitched shunt reactors (2x MVAr) option for a transient three phase to ground fault at Les Mandarin, pre-fault power transfer from France to UK