Comparative Study of Single Phase PLL Algorithms for Grid Synchronization Applications

Similar documents
Synchronization Algorithms for Single Phase System

An Optimized Synchronous Techniques of Single Phase Enhanced Phase Locked Loop (EPLL)

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Grid disturbances

Phase-Locked Loops for Grid-Tied Inverters: Comparison and Testing

Phase-error correction by single-phase Phase-Locked Loops based on transfer delay

Integration of Phase-Locked Loop Based Real-time Oscillation Tracking in Grid Synchronized Systems

Control of grid connected inverter system for sinusoidal current injection with improved performance

Grid Synchronization by Estimation of Positive Sequence Component in Three Phase Signals

PHASE-LOCKED LOOP FOR AC SYSTEMS: ANALYSES AND COMPARISONS

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

Improved PLL for Power Generation Systems Operating under Real Grid Conditions

A Resonant Integrator Based PLL and AC Current Controller for Single Phase Grid Connected PWM-VSI

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Development of Phase Lock Loop System for Synchronisation of a Hybrid System with the Grid

PLL for Grid Synchronization of Single Phase Distributed Generation System

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

ABSTRACT I. INTRODUCTION

Conventional Synchronous Reference Frame Phase-Locked Loop Is An Adaptive Complex Filter Golestan, Saeed; Guerrero, Josep M.

Simulation And Hardware Analysis Of Three Phase PWM Rectifier With Power Factor Correction

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Fault detection in a three-phase system grid connected using SOGI structure to calculate vector components

Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop

Modular Grid Connected Photovoltaic System with New Multilevel Inverter

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

ISSN:

PLL based method for control of grid connected inverter for unbalanced grid frequency

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Impact Factor: Student, SV University, Tirupati, India.

Literature Review for Shunt Active Power Filters

A NEW POWER SIGNAL PROCESSOR FOR CONVERTER- INTERFACED DISTRIBUTED GENERATION SYSTEMS

Performance Analysis of DSOGI PLL under Balanced and Unbalanced Conditions

T.J.Moir AUT University Auckland. The Ph ase Lock ed Loop.

MATLAB/SIMULINK MODEL OF FIELD ORIENTED CONTROL OF PMSM DRIVE USING SPACE VECTORS

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) INDIRECT CURRENT CONTROLLED SINGLE PHASE SHUNT ACTIVE FILTER

Photovoltaic System Based Interconnection at Distribution Level With Different Loads

MODIFYING THE THREE-PHASE SYNCHRONOUS REFERENCE FRAME PHASE-LOCKED LOOP TO REMOVE UNBALANCE AND HARMONIC ERRORS

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

ACTIVE compensation of harmonics, reactive power and

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Modeling of PV Interconnected Distribution System using Simulink

A Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques A Comparison

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Power Quality Improvement in Wind Energy Conversion System of Grid Interfacing Inverter using Hysteresis Band Current Controller

CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

Simulation of Acquisition behavior of Second-order Analog Phase-locked Loop using Phase Error Process

THE CORRECT line phase-angle is a very important information

Indirect Current Control of LCL Based Shunt Active Power Filter

PLL simulation. Prepared by: Qian Wang Spinlab,Worcester Polytechnic Institute. Version 1.0

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Power Factor Improvement with Single Phase Diode Rectifier in Interior Permanent Magnet Motor

Microgrid Connection Management based on an Intelligent Connection Agent

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Simulation And Comparison Of Space Vector Pulse Width Modulation For Three Phase Voltage Source Inverter

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

ISSN Vol.07,Issue.11, August-2015, Pages:

Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

Pulse width modulated (PWM) inverters are mostly used power electronic circuits in

FFT Analysis of THD in Distribution System with Grid Connected RES

Design of an Efficient Phase Frequency Detector for a Digital Phase Locked Loop

Design Of An Integrated Dynamic Voltage Restorer-Ultracapacitor For Improving The Power Quality Of The Distribution Grid

Analysis of Phase Noise Profile of a 1.1 GHz Phase-locked Loop

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Performance of DVR under various Fault conditions in Electrical Distribution System

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

Synchronization of Photo-voltaic system with a Grid

2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media,

International Journal of Advance Engineering and Research Development CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

This is a repository copy of Voltage Synchronisation Techniques for Grid-Connected Power Converters.

ANALYSIS OF GRID SYNCHRONISATION UNDER BALANCED AND UNBALANCED FAULTS USING PLL TECHNIQUES

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Modeling and simulation of a single phase photovoltaic inverter and investigation of switching strategies for harmonic minimization

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

IJOSTHE ISSN: Volume 5 Issue 3 April

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Performance of DVR & Distribution STATCOM in Power Systems

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

Speed Control of Induction Motor using Space Vector Modulation

Performance Analysis of Matrix Converter Fed Induction Motor with Different Switching Algorithms

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Power Quality Improvement using Shunt Passive Filter

Power Quality improvement of a three phase four wire system using UPQC

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers

Harmonic Reduction of Arc Furnaces Using D-Statcom

Transcription:

IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) Comparative Study of Single Phase PLL Algorithms for Grid Synchronization Applications 1 Atul Gupta, 2 Anurag Porippireddi, 3 Venu Uppuluri Srinivasa, 4 Akash Sharma, 5 Mangesh Kadam 1,2,3,4,5 Santerno India Design Center, India Abstract Phase Locked Loop is a control system technique that is used extensively for synchronization purposes in diverse fields, most importantly in communication systems and in power electronics. Owing to its significance, the PLL has been a subject of great interest and various schemes and their improvements have been proposed for its implementation. This paper serves to elaborate on and compare the performance of four prevalent PLL schemes, the Zero Crossing Detector based PLL, Inverse Park based PLL, Second Order Generalized Integrator based PLL and the Enhanced Phase Locked Loop. The Zero Crossing Detector based PLL detects the phase error between its output and the reference at every zero crossing and corrects for it. The Inverse Park PLL and the SOGI PLL differ only in the way they generate the orthogonal signals that are fed to the phase detector. The Enhanced PLL is based on the Adaptive Filter theory. Keywords Single Phase PLL, Inverse Park PLL, SOGI PLL, Enhanced PLL Fig. 1: Typical Grid Connected Inverter with a PLL Based Synchronization Method The generic synchronization solution to a time-varying signal is described by the basic structure of a Phase Locked Loop shown in fig. 2, where the difference between the phase angle of the input and that of the output signal is measured by the Phase Detector (PD) and passed through the Loop Filter (LF), which acts as the control system in the loop. The LF output signal drives the Voltage-Controlled Oscillator (VCO), which generates the output signal, which would follow the input signal. I. Introduction Automatic synchronization of electronic oscillators was first described by Appleton in 1923. The concept of the Phase Locked Loop was proposed by H. de Bellescise in 1932 based on which British researchers developed a simpler alternative to the Superheterodyne Receiver. It was immediately put to use in radio communication systems and analog television receivers. The Phase Locked Loop however, was put to widespread use after the advent of Signetics monolithic IC based Phase Locked Loop systems. Today PLLs are extensively used in various industrial fields such as communication systems, motor control systems, induction heating power supplies and contactless power supplies. Recently, PLL techniques are being used in grid-interfaced converters. For efficient power transmission to the grid, it is essential that the inverter is synchronized with the utility grid for a power factor that is close to unity. The Phase Locked Loop is being extensively used as the synchronization algorithm in these inverters. II. PLL Basics The phase locked loop structure [1-2] is a feedback control system that automatically adjusts the phase of a locally generated signal to match the phase of an input signal. In grid connected systems, the purpose of a PLL is to synchronize the instantaneous phase angle of the inverter voltage θinv with the phase angle of the grid voltage θgrid in order to obtain a power factor as close to unity as possible. A PLL alters the inverter voltage frequency ωinv if the inverter output and the grid voltage are out of phase due to a sudden change in the loading condition at the utility grid so that they are in phase. Figure 1 shows the block diagram of a typical grid connected inverter that employs a PLL as a synchronization method. Fig. 2: Generic Closed Loop PLL Structure III. PLL Techniques A. Zero Crossing Detector A simple method of obtaining the phase information of a wave is to detect the zero crossing point of the signal. Figure 3 shows the block diagram of a zero crossing detector based PLL. The method is based on counting the number of fixed frequency pulses between the adjacent zero crossings of a signal to determine its time period and thus its frequency. The phase angle is estimated by integrating the angular frequency obtained and no control block is involved. The major drawback of the method is that it needs a signal that is devoid of any harmonic distortion and noise, to which it is highly susceptible. Moreover, since phase tracking action occurs only at the zero crossings, a fast dynamic response is not possible. Fig. 3: Block Diagram of a Zero Crossing Detector PLL www.iject.org International Journal of Electronics & Communication Technology 237

IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) B. Single Phase Inverse Park PLL The Inverse Park PLL resembles the Synchronized frame PLL design [3] which is used for three phase systems. In a Synchronized Frame PLL, the three phase signal is converted to the (α-β) stationary reference frame by using the Clarke transformation. The Park transformation is then used to convert the stationary reference frame to a rotating reference frame. The Direct or the Quadrature (q) axis component is then fed to a PI controller having a reference of zero. The PI controller output is integrated to get the estimated instantaneous phase angle for the PLL output signal. The estimated instantaneous phase angle is fed back to the Clarke and Park transforms. The estimated phase angle gets synchronized with the instantaneous phase angle of the utility grid once the d or q axis output is driven to zero. It is explained in the following derivation. Denoting the Clarke transformation outputs as, The Grid reference signal is fed as Vα while Vβ is internally generated. The outputs of the park transform block are passed through single order filters which act as lag blocks, before being fed to the Inverse Park Transform block. The β-axis block is fed back to the Park transform block mentioned earlier. The Vα and Vβ signals are passed to the Park transform block which acts as the Phase Detector(PD) in the PLL. The output of the PD is then passed to the PI controller, whose output is integrated to get the estimated phase angle. The overall structure of the Inverse Park PLL is shown in fig. 5. (1) The Park transformation outputs can be denoted as, Substitutuing equations (1), (2) in (3),(4), we get, (2) (3) (4) (5) Fig. 5: Overall Structure of Inverse Park based PLL The Inverse Park based orthogonal signal generation system filters the signal without delay, is resilient to harmonic noise and makes the orthogonal signal generation frequency adaptive but is susceptible to distortion due to a DC voltage offset in the input signal. Equation (4) can be rewritten as, (7) Therefore, solving for V q =0, we get θ=θ +2nπ, which for practical purposes, can be written as θ=θ. Hence, the estimated instantaneous phase angle, θ, is equal to the grid phase angle, θ, when the q-axis output of the Park transform block, which acts as the phase detector, is zero. For a single phase system, the PLL structure is modified as mentioned in [4]. The Clarke transformation block is replaced by an Orthogonal Signal Generator, whose block diagram is shown in fig. 4. (6) C. Second Order Generalized Integrator based PLL The structure of the SOGI based PLL [5] differs from the Inverse Park based PLL in the way the orthogonal signals are produced. The structure of the SOGI is shown in fig. 6. As output signals, two sine waves V and qv, with a phase shift of π/2 are generated. The component V has the same phase and amplitude as the fundamental of the input voltage signal (v). Fig. 6: SOGI based Orthogonal Signal Generator The closed loop transfer functions H d (V /v) and H q (qv /v) are defined as follows: (8) Fig. 4: Orthogonal Signal Generation Using Inverse Park Transform 238 International Journal of Electronics & Communication Technology (9) where ω n is the angular frequency of the signal and k is a constant that determines the bandwidth of the filters. www.iject.org

ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) As can be seen, the transfer function for Hd resembles that of a Band Pass Filter, that filters out harmonic and random noise and whose output is in phase with that of the input signal. The transfer function for Hq is the same as that of a second order Low Pass Filter, that not only filters out harmonics and random noise, but also introduces a phase shift of π/2 radians. Figure 7 shows the block diagram of the overall PLL structure. IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 From fig. 10, one can see that assuming V in =Asin(ωt + θ), V out =0 when θ =ωt + θ. Hence, the above ANF can be used as the Phase Detector for a PLL. Fig. 10 shows the block diagram of an EPLL segregated into the parts of a generic PLL. Fig. 10: Block Diagram of Enhanced PLL Fig. 7: Structure of SOGI based PLL The performance of the SOGI orthogonal signal generator is dependent on the term ωn which is the angular frequency of the signal. Thus, it is calculated and adjusted in the SOGI by the PLL in order to make it frequency adaptive. Like the Inverse Park PLL, the SOGI PLL can filter out noise and harmonics but is susceptible to a DC bias in the voltage signal. D. Enhanced PLL The enhanced phase locked loop [6-7] is frequency-adaptive and has a non-linear phase detector. Figure 8 shows the block diagram of the Enhanced PLL. Its major improvement over conventional PLLs is the PD mechanism which provides information about the frequency, phase angle and amplitude. The constant K controls the speed of amplitude convergence while kp and ki control the rates of frequency and phase convergence. An EPLL can provide higher degree of immunity and insensitivity to noise and harmonics in the input signal. It is an effective method for synchronization of the grid-interfaced converters in polluted and variable-frequency environments. IV. System Modeling and Simulation The aforementioned PLLs were modeled using SIMULINK. Fig. 8: Block Diagram of Enhanced PLL Fig. 11: Zero Crossing Detector based PLL The EPLL is based on adaptive filter theory. An adaptive filter is a filter that self adjusts its transfer function according to an optimization algorithm driven by an error signal. The error signal in this case is the difference between the estimated and the reference signal and the optimization algorithm is the steepest descent method. Figure 9 shows the block diagram of a typical Adaptive Notch Filter. Fig. 9: Block Diagram of an Adaptive Notch Filter www.iject.org International Journal of Electronics & Communication Technology 239

IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) Fig. 13, show the SOGI based PLL and the SOGI OSG subsystem, respectively. Fig. 14 shows the model of the Enhanced PLL. V. Experiments and Results A. Susceptibility to Random Noise Uniform noise, having a maximum magnitude of 10% and 33% of the input voltage is added to the input signal. Fig. 15 shows the input signal without any noise added. Fig. 12: Inverse Park PLL. Orthogonal Signal Generation System Fig. 15: Input Signal Without Noise Fig. 13: SOGI based PLL Model. SOGI-OSG Fig. 14: Enhanced PLL Model Fig. 11 shows the SIMULINK model of a Zero Crossing Detector based PLL. Fig. 12 shows the model of the Inverse Park PLL. Fig. 12 shows the Orthogonal System Generator subsystem. 240 International Journal of Electronics & Communication Technology www.iject.org

ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 Fig. 16: Input signal with 10% noise. Zero Crossing Detector Inverse Park PLL response. SOGI PLL response. Enhanced PLL response Fig. 16 shows the response of the PLL models to 10% noise. The distortion in the outputs of each of the PLL models other than the ZCD is negligible and is slightly visible only in the case of the Inverse Park PLL. The noise in the signal leads to multiple unwanted zero crossings, disrupting the functioning of the ZCD. Fig. 17: Input signal with 33% noise. Zero Crossing Detector. Inverse Park PLL response. SOGI PLL response. Enhanced PLL response. Fig. 17 shows the response of the PLL models to 30% noise. Other than the ZCD PLL, the Inverse Park PLL is most susceptible to noise distortions among the three, whereas the Enhanced PLL shows little distortions in its output. Distortion in the SOGI PLL output is visible but is relatively less than that of the Inverse park PLL. The Zero Crossing Detector gives a completely disrupted output as expected. B. Response to Change in Frequency The PLL models are then subjected to a frequency jump of 6 Hz from 47 Hz to 53 Hz. The Kp and Ki constants of their control loops are given the same values. www.iject.org International Journal of Electronics & Communication Technology 241

IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) Fig. 18: Zero Crossing Detector. Inverse Park PLL response. SOGI PLL response. Enhanced PLL response. Response Frequency of the PLL models. Fig. 18,, and show the output signals of the PLL models along with the input signal. Figure 18 shows the response frequency of the PLL models. The settling time of the PLLs, other than the ZCD, is almost the same, owing to the fact that their control loops are identical. However, it can be observed that the EPLL has the lowest overshoot of the three PLLs. The change in frequency of the ZCD is almost instantaneous, owing to the absence of a control loop. C. Response to Voltage Sag The input signal is subjected to voltage sag of 33% and the response of the PLL models is plotted. 242 International Journal of Electronics & Communication Technology www.iject.org

ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 Fig. 19: ZCD based PLL,. Inverse Park PLL. SOGI PLL. EPLL with K=10. EPLL with K=30. As can be seen in Figure 19 and, the change in the amplitude of Inverse Park PLL and the SOGI PLL is almost instantaneous. This can be slowed down by adding a low-pass filter. Figure 19, show how the value of K in an EPLL affects the amplitude convergence time. The RMS method of determining amplitude of the ZCD is too slow when the RMS is taken over the whole wave. This can be rectified by taking the RMS of the amplitude over an individual cycle. D. Harmonic Distortion Fig. 20 shows the time response of the PLLs to a 40% 2nd harmonic injected in the input signal. Fig. 20: Input signal with 30% 3rd harmonic injected in. ZCD Inverse Park PLL. SOGI PLL. EPLL. The Inverse Park PLL shows the maximum distortion whereas the Enhanced PLL is practically immune and has the lowest sensitivity. The ZCD s measured frequency is twice that of the signal owing to the additional zero crossing in a cycle. E. Distortion Due to DC Voltage Offset in Input A DC bias of 33% is added to the input. Fig. 21. shows the response of the PLL models. www.iject.org International Journal of Electronics & Communication Technology 243

IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) Fig. 21: ZCD response Inverse Park PLL response. SOGI PLL response. EPLL response As can be seen, the Inverse Park PLL and the SOGI PLL show significant distortion in their output, with that of the Inverse Park PLL being the most visible. The output of the Enhanced PLL is practically immune to the DC voltage offset. A DC bias disrupts the fundamental principle of a ZCD because the zero crossings no longer occur at the end of each half cycle. VI. Conclusion In this work, four existing algorithms for single phase PLLs have been briefly reviewed. They have been modeled using MATLAB- SIMULINK and their response to aforementioned disturbances have been simulated and presented. It has been observed that despite its complexity relative to the ZCD PLL, SOGI PLL and the Inverse Park PLL, the Enhanced Phase Locked Loop is the least sensitive to distortion due to DC bias and harmonic and random noise in the input and is thus suited for use in practical applications in noisy conditions. Although the implementation of the ZCD is quite simple, one has to devise methods to filter out bias, noise and any harmonic distortions in the input in order to get it to work in real, noisy conditions. VII. Appendix Abbreviations and symbols used: PLL: Phase Locked Loop 244 International Journal of Electronics & Communication Technology PD: Phase Detector VCO: Voltage Controlled Oscillator ZCD: Zero Crossing Detector SOGI: Second Order Generalized Integrator OSG: Orthogonal System Generator EPLL: Enhanced Phase Locked Loop θ: Measured Phase Angle/ Phase Angle of the Input Signal θ : Phase Angle of the PLL output ω: Angular Frequency V: Voltage References [1] Guan-Chyun Hsieh, James C. Hung, Phase Locked Loop Techniques-A Survey, in IEEE Transactions on Industrial Electronics, Vol. 43, No. 6, December 1996. [2] Pota, H. R, Phase Locked Loop, University of New South Wales (UNSW), Australia, (Technical Brief Lecture Notes) (2005). [3] A. Timbus, M. Liserre, R. Teodorescu, F. Blaabjerg, Synchronization Methods for Three Phase Distributed Power Generation Systems. An Overview and Evaluation, in Power Electronics Specialists Conference, 2005. PESC 05. IEEE 36th, 2005, pp. 2474-2481. [4] Mihai Ciobotaru, Remus Teodorescu, Frede Blaajberg, Improved PLL structures for single phase grid inverters, in Proceedings of PELINCEC 05. [5] Mihai Ciobotaru, Remus Teodorescu, Frede Blaajberg, A New Single-Phase PLL Structure Based on Second Order Generalised Integrator, in Power Electronics Specialists Conference, 2006. PESC 06. 37th IEEE, 2006. [6] S. Eren, M. Karimi-Ghartemani, A. Bakhshai, Enhanced Frequency-Adaptive Phase-Locked Loop for Distributed Power Generation System Applications, in World Wind Energy Conf., Kingston, Canada. 2008. [7] Wang, Zhibing, Yuhong Wang, Shouyuan Wu, Enhanced Single Phase Locked Loop for Grid-Connected Converter in Distribution Network, in Electrical and Control Engineering (ICECE), 2010 International Conference on Electrical and Control Engineering. IEEE, 2010. Atul Gupta received the B.E. degree in electronics and telecom engineering from Army Institute of Technology, affiliated to Pune University, MH, India, in 2002, and the M..Tech. degree in instrumentation from School Of Instrumentation, affiliated to DAVV University, Indore, MP, India. From 2004 to 2007, he was with the Research Division, TVS Electronics, Bangalore, India, where he worked on development of On- Line uninterruptible power system, sine wave inverters, and lowpower dc dc converters. He also worked at Emerson Network Power as Champion R&D at head office at thane, India. Since Sept 2007, he has been with the Santerno India Design Center, Pune, India, working on grid connected advance solar inverter design. His research interest includes power conditioning, Solar Energy, Hybrid Energy; Grid Interconnection of Renewable Energy sources. www.iject.org

ISSN : 2230-7109 (Online) ISSN : 2230-9543 (Print) IJECT Vo l. 3, Is s u e 4, Oc t - De c 2012 Mangesh Kadam received the B.E. degree in Electronics and Telecom engineering from Pune University, MH, India, in 2008. From 2009 to 2011, he was with the Research Center, Electronet Equipment, Pune, India, where he was working on development of Automation & Automotive products like process control & measurement equipments, Data Logger, Throttle Paddle controller. Since July 2011, he has been with the Santerno India Design Center, Pune, India, working on grid connected advance solar inverter design & Electrical Drives Design. His research interest includes Embedded System Design, Control system Design, Linux & Embedded Linux, RTOS, Device Driver & Communication protocols development. Akash Sharma is pursuing his B.E (Hons) degree in Electrical and Electronics Engineering from BITS Pilani, currently in his final year and will be graduating in 2013. He was with Bokaro Steel Plant (SAIL India) in 2011 for a period of 2 months as a Summer Intern. Since July 2012, he has been associated with Santerno India Engineering Design Center, Pune, India, working on Precision Time Protocol based synchronization applications. His research interests include Control System Design, VLSI Design and Embedded System Design. Anurag Poripireddi is pursuing his B.E.(Hons) degree in Electrical and Electronics Engineering from the BITS Pilani, and is currently in his final year, graduating in August(2013). He was with L&T Integrated Engineering Services for a period of 2 months in 2011. Since July 2012, he has been associated with Santerno India Engineering Design Center, Pune, India, working on Phase Locked Loop based synchronization applications. His research interests include Embedded System Design and Digital Signal Processing. Venu Uppuluri Srinivasa holds Master s degree in Mechanical from Osmania University, Hyderabad, A.P, India. He also holds Master s degree in management & Post graduate diploma in Financial Management discipline. Has over 20 years of experience as an IT / ITes Technologist with both established public companies and Venture funded startups. Held senior executive roles in product marketing, strategy, product development and business development. Currently working as General Manager and Head for Carraro Technologies India Limited (an Italian Company) since 6 years representing Board as an authorized signatory. Also signed as board of director for Santerno India Private Limited. Served in the capacity of Engineering Director for Emerson Electric Co. (USA), Group Manager for Tecumseh Products India Limited etc. www.iject.org International Journal of Electronics & Communication Technology 245