Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Similar documents
PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

ABSTRACTS of SESSION 6

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Lightning performance of a HV/MV substation

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

University of Zagreb Faculty of Electrical Engineering and Computing

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Modeling insulation in high-voltage substations

The line-lightning performance and mitigation studies of shielded steelstructure

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

Lightning overvoltage and protection of power substations

Electric Stresses on Surge Arrester Insulation under Standard and

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May, Establishment of a new lightning location system in Croatia

The Many Uses of Transmission Line Arresters

High voltage engineering

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Software Development for Direct Lightning Stroke Shielding of Substations

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Mitigation of Back-Flashovers for 110-kV Lines at Multi-Circuit Overhead Line Towers

Lightning transient analysis in wind turbine blades

GIS Disconnector Switching Operation VFTO Study

X International Symposium on Lightning Protection

Analysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes

Utility System Lightning Protection

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

WORLD MEETING ON LIGHTNING Lightning Performance Research on Mexican High Voltage Transmission Lines

Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line

Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure

URL:

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Substation Insulation Coordination Study

Statistical Lightning Simulations for a HV "Mixed" Overhead-Cable Line: Preliminary Studies

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

Protection against unacceptable voltages in railway systems

Insulation Coordination Study of 275kV AIS Substation in Malaysia

TECHNICAL REPORT. Insulation co-ordination

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

The Influence of Atmospheric Overvoltages on High-Voltage SF 6. Substations

Insulation Co-ordination For HVDC Station

Mitigation Methods to Improve the Lightning Performance of Hybrid Transmission Line

Accuracy of Lightning Surge Analysis of Tower Surge Response

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

New Modeling of Metal Oxide Surge Arresters

TRIGGERED by energy transition towards sustainability,

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Lightning Performance of Transmission Lines with Tall Sections

Electrical Power and Energy Systems

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

INTERNATIONAL STANDARD

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

EE 1402 HIGH VOLTAGE ENGINEERING

ABSTRACT 1 INTRODUCTION

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

Lightning Overvoltage performance of 132kV GIS Substation in Malaysia

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

HIGH VOLTAGE Insulation Coordination

Metal-Oxide Surge Arresters Integrated in High-Voltage AIS Disconnectors An Economical Solution for Overvoltage Protection in Substations

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Energy Division. Bowthorpe LV/MV Surge Arresters

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

Tab 8 Surge Arresters

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

Transformers connected via a cable Overvoltage protection

EMTP Modeling of a Triggered-Lightning Strike to the Phase Conductor of an Overhead Distribution Line

Earthing of Electrical Devices and Safety

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS

Journal of Asian Scientific Research SUBSTATION PROTECTION AND THE CLIMATIC ENVIRONMENT OF NIGER DELTA. John Tarilanyo Afa

Electric Power Systems Research

Chapter 1. Overvoltage Surges and their Effects

Transcription:

Lightning Overvoltage Performance of 11 kv Air-Insulated Substation B. Filipović-Grčić, B. Franc, I. glešić, V. Milardić, A. Tokić Abstract--This paper presents the analysis of lightning overvoltage performance of 11 kv air-insulated substation connecting hydro power plant with the rest of the power system. The demonstrated procedure includes the application of a threedimensional electro-geometric model of transmission line entering the substation, description of modeling process and EMTP simulations. Different overvoltage protection schemes were discussed including station surge arresters with different rated voltages and energy classes. The installation of line surge arresters on the first towers of the transmission line entering the substation for the improvement of the lightning performance of substation was analyzed. Lightning parameters derived from lightning location system observations around 11 kv substation were analyzed and compared to ones used in literature and calculations. For this purpose an algorithm for the assessment of the lightning flash multiplicity was developed in order to determine the current amplitude probability distribution of the first and subsequent cloud to ground strokes. Energy absorbed by surge arresters due to multiple strokes was determined and an optimal overvoltage protection scheme was proposed. Keywords: lightning overvoltages, overvoltage protection, 11 kv air-insulated substation, EMTP simulations, surge arrester energy, insulation coordination, lightning location system. T I. INTRODCTION HE magnitude and rate of rise of overvoltages due to lightning strikes on transmission lines is an important consideration for substation insulation and the strategy adopted for limiting these overvoltages. The transmission line faults caused by lightning can be classified into backflashovers and flashovers due to shielding failures. Both events cause overvoltages which travel towards the substation from the struck point. Attenuation due to high frequency nature of lightning overvoltages is caused by corona loss and skin effect. Therefore, usually lightning strokes that are close to the This work has been supported in part by the Croatian Science Foundation under the project Development of advanced high voltage systems by application of new information and communication technologies (DAHVAT). B. Filipović-Grčić, B. Franc, I. glešić and V. Milardić are with the Faculty of Electrical Engineering and Computing, niversity of Zagreb, Croatia (e-mail: bozidar.filipovic-grcic@fer.hr). A. Tokić is with the Faculty of Electrical Engineering, niversity of Tuzla, Bosnia and Herzegovina (e-mail: amir.tokic@untz.ba). Paper submitted to the International Conference on Power Systems Transients (IPST215) in Cavtat, Croatia June 15-18, 215 substation are considered when assessing overvoltage protection requirements and the associated risk of failure of the substation equipment. Insulation faults on a transmission line in front of substation can provoke short circuit currents with high magnitudes. The consequence of insulator flashover is the forming of a surge with a very steep front that enters the substation and causes insulation stress especially on windings of power transformers [1]. The procedure presented in this paper includes the application of a three dimensional electrogeometrical model (EGM) of 11 kv transmission line entering the substation, transient simulations in EMTP/ATP software and the evaluation of the lightning performance substation equipment. II. ELECTRO-GEOMETRIC MODEL OF 11 KV TRANSMISSION LINE ENTERING THE SBSTATION The goal of the EGM simulation is to determine the distribution of lightning current amplitudes which strike shield wire or phase conductor of the transmission line. The basic parameter needed for EGM simulation is the statistical distribution of lightning current amplitude. The distribution for negative lightning current amplitudes of the first stroke, suggested by J. G. Anderson [2] and adopted by IEEE [3] is described by following expression: 1 P =, (1) 2.6 I 1+ 31 where P is a probability of occurrence of lightning current amplitude higher than I. The general expression for the striking distance R is represented by expression (2). b R = a I (2) The striking distance can vary significantly and therefore different s of constants and modifications of the above equation are proposed by various investigators [4]. The expression for the striking distance recommended by IEEE WG with constants a=8, b=.65 were used in simulations. A first few spans of a single-circuit 11 kv transmission line with single shield wire entering the substation were considered in EGM (Fig. 1). In order to collect enough data for the statistical calculation, the Monte Carlo simulations were conducted for a large number of generated lightning current amplitudes. The simulations were carried out until 1 lightning strokes ended at phase conductors and 7259 ended at towers and shield wire. The highest amplitude of lightning current impacting phase conductors was 14.2 ka. Fig. 2 shows probability distribution of lightning current amplitudes

V impacting phase conductors. Fig. 3 shows probability distribution of lightning current amplitudes impacting shield wire and towers. 4.33 m 25 21,65 2.61 m 2.61 m 3.16 m 2.61 m 3.73 m P (%) 2 15 1 9,64 15,23 17,31 11,1 7, 5 4,88 3,28 2,31 1,73 1,36 1,4,79,69,56,45,36,32,3 Fig. 1. 11 kv transmission line tower P (%) 2, 18, 16, 14, 12, 1, 8, 6, 4, 2,, 18, 16,7 16,2 11,6 12,3 1,8 5,6 3,6 2,7 1,3,5,4,3 1-2 2-3 3-4 4-5 5-6 6-7 7-8 8-9 9-1 1-11 11-12 12-13 13-14 I (ka) Fig. 2. Probability distribution of lightning current amplitudes impacting phase conductors 54.3 % of strokes impacting phase conductors finished in the upper phase which is most exposed to direct lightning strokes, while 36.1 % and 9.6 % strokes finished in the middle and lower phase, respectively. Fig. 3. Probability distribution of lightning current amplitudes impacting shield wire and towers I (ka) III. MODELING OF 11 KV TRANSMISSION LINE AND AIR- INSLATED SBSTATION Single-circuit 11 kv transmission line with one shield wire entering the air-insulated substation was modelled in EMTP/ATP software. The model shown in Fig. 4 represents the most unfavourable operating switching configuration of the substation with respect to lightning overvoltages: single transmission line bay, transformer bay and measuring bay in operation. Overvoltages were calculated on the substation equipment marked in Fig. 4: 1 - voltage transformers in line bay; 2 - current transformers in line bay; 3 - circuit breakers in line bay; 4 - circuit breakers in transformer bay; 5 - current transformers in transformer bay; 6 - power transformer; 7 - voltage transformers in measuring bay. The calculations of lightning overvoltages were carried out in case when lightning strikes upper phase conductor and shield wire at the first tower close to substation. MJERNO POLJE 1 SN-M VN-SN VN-M ENERGETSKI TRANSFORMATOR T1 I MOV r=96 kv zemljivac Strujni tr. Prekidac Naponski tr. Izolator TRANSFORMATORSKO POLJE GLAVNE SABIRNICE 1 Izolator Prekidac Strujni tr. Naponski tr. dar munje C I V V DALEKOVODNO POLJE I MOV r=144 kv Stup1 Stup2 Stup3 zemljivaè TRASA 11 kv DALEKOVODA Fig. 4. Model of 11 kv transmission line and substation in EMTP/ATP Stup 4

Three different overvoltage protection schemes were analyzed: A) Surge arresters (SAs) with r=96 kv in transformer bay and SAs with r=144 kv in line bay. B) SAs with r=12 kv installed in line bay and in transformer bay. C) SAs with r=12 kv installed in line bay, transformer bay and in all phases of the first three towers entering the substation. The first protection scheme A) represents the situation where SAs in line bay and transformer bay have different rated voltages. This protection scheme was analyzed in order to determine the influence of SA s rated voltage on overvoltage protection and energy sharing between arresters. The second protection scheme B) represents the situation where SAs in line bay and transformer bay have the same rated voltage selected according to [5]. The third protection scheme C) represents the situation where SAs with the same rated voltage are installed in line bay, transformer bay and in all phases of the first three towers entering the substation. This protection scheme was analyzed in order to determine the influence of line surge arresters (LSAs) on overvoltage protection inside the substation. Energy sharing between LSAs and substation SAs was analyzed in case of multiple lightning strokes. The transmission line conductors and shield wire were represented by frequency-dependent model in EMTP and five spans close to substation were taken into account. To avoid reflections of travelling waves, the line was terminated with multiphase matching resistance on one end. Surge impedances of the transmission line towers [3] were determined by using expression (3): H Z = 6 ln 1, (3) R where H represents tower height and R equivalent radius of a tower base. Each tower was divided in four parts: the first part from tower top to upper arm, the second one from upper arm to middle arm, the third part from middle arm to lower arm and the last part from lower arm to the ground. This way it was possible to calculate transient voltages of tower arms. Tower footing resistances were modelled taking into account soil ionization [3] caused by lightning current. Tower grounding was represented as non-linear resistor using MODELS language and TACS-controlled time-dependent resistor. The important parameter for the behaviour of overhead line insulation subjected to lightning overvoltages is its corresponding flashover voltage, which depends on the voltage level and insulation clearances. The flashover mechanism of the transmission line insulators was represented with differential equation (4) of the leader progression model selected by the CIGRE WG 33-1[4]. u ( ) ( ) ( t) v t = kl u t E x (4) In the expression (4), u(t) is the voltage as a function of time, x is the distance of the unbridged gap, E is the gradient at which the breakdown process starts, and k L is a constant [6]. Insulator flashover was modelled using MODELS language in EMTP/ATP. The calculated volt-time characteristic of a 11 kv insulator string for a standard lightning impulse voltage waveform 1.2/5 µs is shown in Fig. 5. pr (MV) 4,5 4 3,5 3 2,5 2 1,5 1,5 8 9 1 11 12 13 14 15 t (µs) Fig. 5. Calculated volt-time curves of the 11 kv insulator strings (for 1.2/5 µs waveform) The equipment in high voltage substation was represented by surge capacitances obtained from manufacturer s data, whereas busbars and connecting leads were represented by a frequency-dependent transmission line model [7]. The model of gapless type SA includes non-linear and dynamic behaviour of the arrester. The non-linear behaviour was represented with the -I characteristics depicted in Fig. 6. A frequency-dependent arrester model [8] was used in simulations. The parameters of the SA model were identified using expressions that required only the data reported in manufacturers datasheets. The arrester leads were represented by inductance of 1 µh/m taking into account the effects of additional voltage rise across the lead inductance. (kv) 45 4 35 3 25 2 r =144 kv Series3 r =96 kv 15 1 1 1 I (ka) Fig. 6. Nonlinear -I characteristics of the SAs with r=144 kv and r=96 kv recorded with the current impulse 8/2 µs The lightning stroke hitting a tower or a phase conductor was represented by a CIGRE concave shape [3] shown in Fig. 7. The peak current magnitude and the tail time are important when observing the SA energy, while the influence of the rise time is hardly noticeable in such a case. In contrast, the current wave front is an important parameter with regard to insulator flashover. The CIGRE concave shape shown in Fig. 7 represents more accurately the concave front of a lightning stroke and usually gives more realistic results.

Fig. 7. CIGRE concave shape (If is the crest current, Sm is the maximum front steepness, tf is the equivalent front duration) The majority of lightning flashes comprise multiple strokes which occur a few milliseconds of each other. These lightning strokes can be especially dangerous for SAs because they require dissipation of a large amount of energy which results in heating of metal-oxide blocks. However, SAs must be capable of dissipating multiple lightning strokes without deterioration and therefore it is important to select the appropriate energy class. Two negative lightning flashes were simulated comprising the first and following stroke: - strokes to tower: first stroke 1 ka, 9.9/2 µs and following stroke 4 ka, 4.5/14 µs; - strokes to phase conductor: first stroke 14.2 ka, 2.3/2 µs and following stroke 5.68 ka, 1.3/14 µs. Amplitude and duration of the strokes, i.e. time to half have the greatest impact on the SA energy [9]. The amplitudes of the first strokes were selected based on the results of EGM, while the amplitudes of the subsequent strokes were assumed to have 4 % of the first stroke amplitude. Time to half s for the first and following strokes were selected according to [4], with only 5 % probability of being exceeded. The lightning parameters are essential input variables for estimating the effectiveness of overvoltage protection. More recent direct lightning current measurements were obtained from instrumented towers in Austria, Germany, Canada and Brazil, as well as from rocket-triggered lightning [1]. Further, modern lightning location systems (LLSs) report peak currents estimated from measured electromagnetic field peaks. The available technology for detecting and locating cloud to ground (CG) lightning has significantly improved over the last decades. LLS data have the advantage of covering extended areas on a continuous basis and can therefore observe the related exposure of objects to the lightning threat. Therefore, the analysis of lightning activity around 11 kv substation obtained from LLS was performed. The lightning activity was observed for a 6 year period within a radius of 1 km from 11 kv substation. This area covers the most exposed part of 11 kv transmission line corridor extending over a mountain area. Data were obtained from LLS [11], which is capable of detecting multiple-stroke flashes where every stroke is represented by individual set of data (current amplitude, discharge time, location, etc.). CG flashes consist of one or several strokes coming in very short temporal intervals and close spatial proximity. The common method for grouping stroke data into flashes is using the thresholds for maximum temporal separation and maximum lateral distance between successive strokes. For this purpose an algorithm for grouping of lightning strokes into flashes (assessment of the lightning stroke multiplicity) was developed in order to determine the current probability distribution of the first and subsequent CG strokes. The multiplicity was calculated for a maximum temporal separation of 2 ms and a maximum lateral distance of 2 km between successive strokes [12]. A total of 7762 negative CG strokes were detected, consisting of 4999 first strokes and 2763 subsequent strokes, with an average stroke multiplicity of 1.55 strokes per flash. Fig. 8 shows the comparison between cumulative frequency distributions of negative CG lightning current amplitudes obtained from LLS and IEEE. Cumulative frequency (%) 1% 9% 8% 7% 6% 5% 4% 3% 2% 1% IEEE - first strokes LLS - first strokes LLS - subsequent strokes % 1 1 1 Current (ka) Fig. 8. Comparison between cumulative frequency distributions of negative CG lightning current amplitudes obtained from LLS and IEEE Fig. 8 shows that according to data from LLS, there is a significantly higher probability of lightning strokes occurrence with lower current amplitudes, compared to IEEE data. This difference is caused by sensitivity of LLS which is capable of detecting multiple CG strokes with low current amplitudes. Table I shows average and median s of all first and all subsequent strokes detected by LLS and according to IEEE. TABLE I PARAMETERS OF NEGATIVE FIRST AND SBSEQENT STROKES Average LLS Median LLS Median IEEE First strokes 13.6 ka 8.8 ka 31.1 ka Subsequent strokes 12.4 ka 9.5 ka 12.3 ka LLS data gives lower median s of current amplitudes both for first and subsequent strokes. Table II shows the average and median s of first and subsequent strokes in shielding failure domain (I<13 ka) and backflash domain (I 13 ka) detected by LLS. In backflash domain first strokes have higher median, while in shielding failure domain subsequent strokes have higher median. The analysis of LLS data showed that the lightning current parameters of the first and subsequent strokes used in the simulations were conservative and on the safe side.

TABLE II PARAMETERS OF NEGATIVE FIRST AND SBSEQENT STROKES IN SHIELDING FAILRE AND BACKFLASH DOMAIN I<13 ka I 13 ka Average Median Average Median First strokes 7.3 ka 6.9 ka 28. ka 2.9 ka Subsequent strokes 7.8 ka 7.5 ka 22.6 ka 18.6 ka IV. SIMLATION RESLTS A. Lightning overvoltages The rated lightning impulse withstand voltage of substation equipment is 55 kv, while the coordination lightning impulse withstand voltage cw=478 kv was determined for safety factor K s=1.15 [13]. Overvoltages were calculated on the substation equipment marked with red colour at Fig. 4: 1 - voltage transformers in line bay; 2 - current transformers in line bay; 3 - circuit breakers in line bay; 4 - circuit breakers in transformer bay; 5 - current transformers in transformer bay; 6 - power transformer; 7 - voltage transformers in measuring bay. Figs. 9-11 show overvoltage amplitudes on substation equipment in case of lightning strokes to tower 1 with current amplitudes 5 ka, 75 ka and 1 ka. (kv) 8 7 6 5 4 3 2 1 cw =478 kv Fig. 9. Overvoltages on substation equipment in case of lightning stroke 5 ka (5.9/77.5 µs) to tower 1 (kv) 8 7 6 5 4 3 2 1 cw =478 kv Fig. 1. Overvoltages on substation equipment in case of lightning stroke 75 ka (7.9/77.5 µs) to tower 1 7 6 5 cw =478 kv In case of overvoltage protection scheme A) lightning overvoltages on substation equipment (2, 4, 5 and 7) exceeded critical of cw=478 kv. Overvoltages were highest in this case due to relatively high rated voltage of SAs in line bay. In case B) overvoltages were reduced with regard to case A), due to lower rated voltage of SAs in line bay. However, overvoltages on voltage transformers in measuring bay still exceeded cw. The calculation results showed that in all cases lightning overvoltages were highest on voltage transformers in measuring bay since they are furthest away from the SAs with respect to other equipment. Also, reflections of travelling waves occurred at the end of 11 kv busbars where voltage transformers were installed. In case C) overvoltages were further reduced compared to case B). In this case with LSAs installed in all phases of the first three towers entering the substation, overvoltages on all substation equipment were lower than cw. Fig. 12 shows percentage reduction of overvoltages on substation equipment in case of lightning stroke 5 ka to tower 1. Overvoltage reduction (%) 6 5 4 3 2 1 compared to A) compared to B) Fig. 12. Percentage reduction of overvoltages on substation equipment in case of lightning stroke 5 ka to tower 1 A significant overvoltage reduction on all substation equipment was obtained with application of LSAs, especially on voltage transformers in measuring bay. Figs. 13 and 14 show calculated overvoltages on insulators of the first tower and on voltage transformers in measuring bay in case A) and 1 ka lightning stroke to first tower. Backflashover occurred in all phases and overvoltages in measuring bay exceeded cw. Fig. 15 shows overvoltage amplitudes on substation equipment in case of lightning stroke 14.2 ka (2.3/77.5 µs) to upper phase conductor at tower 1. 5 4 3 (kv) 4 3 2 1 2 1 Fig. 11. Overvoltages on substation equipment in case of lightning stroke 1 ka (9.8/77.5 µs) to tower 1-1 4 8 12 16 [us] 2 Fig. 13. Overvoltages on insulators of the first tower

7 6 5 4 3 2 1 25 2 15 1 5-5 -1 1 2 3 4 5 [us] 6 Fig. 14. Overvoltages on voltage transformers in measuring bay -1 1 2 3 4 [us] 5 Fig. 17. Overvoltages on power transformer (kv) 6 5 4 3 2 1 cw =478 kv Fig. 15. Overvoltages on substation equipment in case of lightning stroke 14.2 ka (2.3/77.5 µs) to upper phase conductor at tower 1 In this case amplitudes were below cw for all overvoltage protection schemes. Figs. 16 and 17 show calculated overvoltages on insulators of the first tower and on power transformer in case A) and 14.2 ka lightning stroke to upper phase conductor. Flashover occurred in upper phase (marked red on Fig. 16) and overvoltages on power transformer were lower than cw. B. Surge arrester energy SA energy was calculated in case of lightning stroke to tower 1 with current amplitudes 3 ka 1 ka and in case of lightning stroke to upper phase with current amplitudes 1 ka and 14.2 ka. SA energies in case of overvoltage protection schemes A) and B) are shown in Figs. 18 and 19. In case A) (Fig. 18), energy of SAs in transformer bay was higher than in line bay, due to their lower rated voltage. In case B) (Fig. 19), SAs in line bay absorbed more energy because their rated voltage was equal to SAs in transformer bay and they were closer to lightning stroke position. 4 18-4 -26-48 -7 [us] 8 Fig. 16. Overvoltages on insulators of the first tower w (kj/kv) 2, 1,8 1,6 1,4 1,2 1,,8,6,4,2, SAs in line bay SAs in transformer bay 3, ka 4,/77,5 µs 5,52 ka 5,9/77,5 µs 75, ka 1, ka 7,8/77,5 µs 9,9/77,5 µs Lightning current waveforms 14,2 ka 2,3/77,5 µs Fig. 18. SA energies in case of overvoltage protection scheme A) E (kj) 3 25 2 15 1 5 SAs in line bay SAs in transformer bay 3, ka 4,/77,5 µs 5,52 ka 5,9/77,5 µs 75, ka 7,8/77,5 µs 1, ka 9,9/77,5 µs Lightning current waveforms 14,2 ka 2,3/77,5 µs 1, ka 1,8/77,5 µs Fig. 19. SA energies in case of overvoltage protection scheme B) 1, ka 1,8/77,5 µs Therefore, energy sharing between SAs in line and transformer bay was strongly affected by the of their rated voltages. SA energy was calculated in case of two negative lightning flashes comprising the first and following stroke: - strokes to tower: first stroke 1 ka, 9.9/2 µs and following stroke 4 ka, 4.5/14 µs; - strokes to phase conductor: first stroke 14.2 ka, 2.3/2 µs and following stroke 5.68 ka, 1.3/14 µs. Calculation results in cases A) and B) show that energy class 4 (w r=7 kj/kv) of station SAs should be selected in order to withstand the energy due to multiple lightning strokes. Fig. 2 shows energies of SAs in case C). SAs in transformer and line bay and LSAs at first three towers with energy class 2 (w r=2.8 kj/kv r) withstood the energy caused by lightning except in case of multiple lightning stroke to phase conductor with relatively high amplitude and long duration. According to the results of EGM, this event has a low probability of 2,94 2,45 1,96 1,47,98,49 w (kj/kv)

occurrence. Finally, station SAs with energy class 3 (w r=4 kj/kv r) and LSAs with energy class 2 were selected. E (kj) 4 35 3 25 2 15 1 5 SAs in line bay SAs in transformer bay LSAs at tower no. 1 LSAs at tower no. 2 LSAs at tower no. 3 5,52 ka 5,9/77,5 µs 75, ka 7,9/77,5 µs Energy class 2, w r =2,8 kj/kv ( r ) 1, ka 9,9/77,5 µs 1, ka 9,9/2 µs 4, ka 4,5/14 µs Lightning current waveforms 14,2 ka 2,3/77,5 µs Fig. 2. SA energy in case of overvoltage protection scheme C) 14,2 ka 2,3/2 µs 5,68 ka 1,3/14 µs Fig. 21 shows energies of LSAs at first tower in case of multiple lightning stroke to tower. 25 [kj] 2 15 1 5,,216,432,648,864 [ms] 1,8 Fig. 21. Case C) - energies of LSAs at first tower in case of first lightning stroke 1 ka, 9.9/2 µs and following stroke 4 ka, 4.5/14 µs V. CONCLSIONS This paper presents the analysis of lightning overvoltage performance of 11 kv air-insulated substation. Different overvoltage protection schemes were discussed including station SAs with different rated voltages and energy classes, as well as the application of LSAs on the first three towers of the transmission line entering the substation, with relatively high grounding resistance. For this purpose, the model of 11 kv transmission line and substation was developed in EMTP/ATP. The conducted simulations showed that SA s rated voltage have significant influence on overvoltage distribution inside the substation and on energy sharing between arresters in line and transformer bay. An optimal protection scheme was proposed considering overvoltage distribution on substation equipment and SA energy due to multiple lightning strokes. This protection scheme includes station SAs with energy class 3 and LSAs with energy class 2, both having the same rated voltage r=12 kv. 3,92 3,43 2,94 2,45 1,96 1,47,98,49 w (kj/kv) Furthermore, the analysis of the lightning activity around 11 kv substation obtained by LLS was performed, which showed that there is a significantly higher probability of lightning stroke occurrence with lower current amplitudes, compared to IEEE data. Therefore, the lightning current parameters of the first and subsequent strokes used in the simulations were conservative and on the safe side. VI. REFERENCES [1] I. glešić, V. Milardić, B. Filipović-Grčić, A. Tokić, Preventing Flashover near a Substation by Installing Surge Arresters, 29 th International Conference on Lightning Protection, ppsala, Sweden, 28. [2] J. G. Anderson, Lightning performance of transmission lines, chapter 12, Transmission Line Reference Book, Electric Power Research Institute, Palo Alto, CA. [3] IEC/TR 671-4, Insulation co-ordination - Part 4: Computational guide to insulation co-ordination and modelling of electrical networks, 1 st edition, 24. [4] CIGRE Working Group 1 (Lightning) of Study Committee 33 (Overvoltages and Insulation Coordination), Guide to Procedures for Estimating the Lightning Performance of Transmission Lines, brochure 63, October 1991. [5] IEC 699-5, Surge arresters - Part 5: Selection and application recommendations, 2 nd edition, 213. [6] D. Filipović-Grčić, B. Filipović-Grčić, I. glešić, Lightning Critical Flashover Voltage of High Voltage Insulators: Laboratory Measurements and Calculations, International Review of Electrical Engineering, vol. 7, no. 2 - part B, pp. 4321-4328, 212. [7] A. F. Imece, D. W. Durbak, H. Elahi, S. Kolluri, A. Lux, D. Mader, T. E. McDemott, A. Morched, A. M. Mousa, R. Natarajan, L. Rugeles, E. Tarasiewicz, Modeling Guidelines for Fast Front Transients, Report prepared by the Fast Front Transients Task Force of the IEEE Modeling and Analysis of System Transients Working Group, IEEE Transactions on Power Delivery, Vol. 11, No. 1, January 1996. [8] P. Pinceti and M. Giannettoni, A simplified model for zinc oxide surge arrester, IEEE Transactions on Power Delivery, vol. 14, no. 2, pp. 545 55, April 1999. [9] I, glešić, V. Milardić, B. Filipović-Grčić, A. Tokić, Evaluation of Energy Stress on Line Arresters, CIGRE International Colloquium: Application of Line Surge Arresters in Power Distribution and Transmission Systems, Cavtat, Croatia, 28. [1] F. Heidler, Z. Flisowski, W. Zischank, Ch. Bouquegneau, C. Mazzetti, Parameters of lightning current given in IEC 6235 background, experience and outlook, 29 th International Conference on Lightning Protection, ppsala, Sweden, 28. [11] I. glešić, V. Milardić, B. Franc, B. Filipović-Grčić, J. Horvat, Establishment of a new lightning location system in Croatia, CIGRE C4 International Colloquium on Lightning and Power Systems, Kuala Lumpur, Malaysia, 21. [12] B. Franc, I. glešić, B. Filipović-Grčić, Application of Lightning Location System Data for Designing the External Lightning Protection System, CIGRE International Colloquium on Lightning and Power Systems, Lyon, France, 214. [13] IEC 671-2, Insulation co-ordination Part 2: Application Guide, 3 rd edition, December 1996.