BACnet Protocol Implementation Conformance Statement Date: 2012-06-27 Vendor Name: Trane Product Name: Trane TR150 Product Model Number: TR150 Applications Software Version: 3.0 Firmware Revision: 3.0 BACnet Protocol Revision: 5 Product Description: The TR150 is dedicated to basic control of fans and pumps in HVAC applications. Lowest investment, high reliability & efficient, compact design, Built-in EMC and harmonics filters is the main features for this product. Tranes' unequalled experience in advanced drive technologies for HVAC application provides optimized features in the TR 150 and makes it the perfect match for pumps, fans in buildings fitted with sophisticated HVAC solutions. BACnet Standardized Device Profile (Annex L): o BACnet Operator Workstation (B-OWS) o BACnet Building Controller (B-BC) o BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) o BACnet Smart Sensor (B-SS) o BACnet Smart Actuator (B-SA) List all BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B DS-WP-B DM-DDB-B DM-DOB-B DM-DCC-B DM-RD-B Segmentation Capability: o Segmented requests supported o Segmented responses supported Window Size Window Size Standard Types Supported: Input Output Binary Input Binary Output Binary Device Multi-state-value instantiation is static. Refer to tables at end of this document for object details.
Data Link Layer Options: o BACnet IP, (Annex J) o BACnet IP, (Annex J), Foreign Device o ISO 8802-3, Ethernet (Clause 7) o ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) o ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) MS/TP master (Clause 9), baud rate(s): 9.600; 19.200; 38.400; 76.800 o MS/TP slave (Clause 9), baud rate(s): o Point-To-Point, EIA 232 (Clause 10), baud rate(s): o Point-To-Point, modem, (Clause 10), baud rate(s): o LonTalk, (Clause 11), medium: o Other: Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) o Yes o No Networking Options: o Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. o Annex H, BACnet Tunneling Router over IP o BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? o Yes o No Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously. ANSI 3.4 o IBM /Microsoft DBCS ISO 8859-1 o ISO 10646 (UCS-2) o ISO 10646 (UCS-4) o JIS C 6226 If this product is a communication gateway, describe the types of non-bacnet equipment/networks(s) that the gateway supports:
Device Binary Input Binary Output Binary Input Output Multistate entifier x Name x Type x x System Status Vendor Name Vendor entifier Model Name Firmware Revision Appl Software Revision Location Description Protocol Version Protocol Revision Services Supported List Max APDU Length Segmentation Support Local Time Local Date APDU Timeout Number APDU Retries Max Masters Max Info Frames Device Address Binding Database Revision Present Status Flags Event State Reliability Out-of-Service Number of States State text Units Priority Array * * * Relinquish Default x* * * Polarity Active Text Inactive Text *For commandable values only
ue Inputs Name / AI:1 Input 53 R AI:2 Input 54 R ue Outputs Name / AO:1 Terminal 42 Output Bus Control ue s Name / AV:1 Input Reference 1 AV:2 Input Reference 2 AV:3 Output Speed AV:4 P Feedback AV:5 Motor Current AV:6 Power [kw] AV:15 Motor Thermal AV:21 Operating Hours AV:22 Running Hours AV:23 kwh Counter AV:24 Motor Voltage AV:25 Frequency AV:27 DC Link Voltage AV:28 Heatsink Temp. AV:29 Inverter Thermal AV:31 Bus Feedback 1 AV:50 Last Alarm AV:51 Fault Code AV:52 P Start Speed AV:53 On Reference Bandwidth AV:54 P Proportional Gain AV:55 P Integral Time Binary Inputs Name / BI:2 Digital input Term 29 BI:3 Digital input Term 27 BI:4 Digital input Term 19 BI:5 Digital input Term 18 Bacnet embedded objectlist for Trane TR150 Page 4 of 5
Binary Outputs Name / BO:4 Relay 1 BO:5 Relay 2 Binary s Name / BV:1 RUN/STOP Command BV:2 REF1 / REF2 Select BV:3 Fault Reset Command BV:4 RUN / STOP Monitor BV:5 OK / FAULT Monitor BV:6 HAND / AUTO Reference BV:21 Warning BV:22 Trip BV:23 Triplock BV:24 Coasting BV:25 CW/CCW BV:26 Jog BV:27 Reset BV:28 Reset KWh Counter BV:29 Reset Running Hours Counter BV:31 Speed = reference BV:32 Bus Control BV:33 Running BV:34 Ramp 1/Ramp 2 Multistate Name MSV:0 Smart Logic Controller State MSV:1 Active Setup / Bacnet embedded objectlist for Trane TR150 Page 5 of 5