PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

Similar documents
PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

Power Processor - Series 700F 10KVA to 150KVA

Power-Sure 700. Technical Data TD158001EN. Contents

ULTRA-K Series 600K - he

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

TOSHIBA International Corp

StatiVolt. Inverter UPS Systems. Features. Contents

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

MODEL 3810/2 Line Impedance Stabilization Network

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

SECTION PANELBOARDS

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Transformer Basics AN05-10ST. Application Note. innovation in wire wound magnetic technology. January 09 Rev 1

60K(i) - 260K(i) THREE PHASE. SureImage IMAGING & TREATMENT SERIES

PRODUCT FEATURES TYPICAL APPLICATIONS

Straight Isolation - Plug In (171 Series)

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

ASX SERIES PACIFIC OPERATION MANUAL AC POWER SOURCE POWER SOURCE

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

1 INTRODUCTION ORDER CODE / INFORMATION

B. Manufacturers: Square-D, G.E. or Westinghosue.

Power Conditioners product guide

USER S MANUAL. 1KSS60400/ ST Edition

LB115S 115W Single Output

S11 Adjustable Speed Drive Engineering Specification

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

Table of Contents. Facility EMI Filter Products

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

Amveco Toroidal Solutions. Acme Electric s class leading toroidal magnetics is the perfect solution for the most challenging applications.

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

Model 3725/2M. Line Impedance Stabilization Network (LISN) User Manual

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Power Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

USER S MANUAL. 3KSS6050/ nd Edition

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Military (Airborne, ground-fix, shipboard), Ruggedized, Telecom, Industrial Power Supply

Phoenix DX Clean Power (18 Pulse) AC Drive

VF-nC1 Adjustable Speed Drive Engineering Specification

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Product Specification sheet

SINGLE-PHASE VSV SWITCH

SECTION DISTRIBUTION SWITCHBOARDS

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

MAJORSINE Power Inverter

70 Watt Switching Medical Grade Switching Power Supply with Active PFC CONTENTS 1. GENERAL CIRCUIT TOPOLOGY...2

The MBC550 range is ideally suited to a wide variety of medical applications, and also where airflow is limited or not available.

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Multimode Video Fiber Optic Transmission Equipment

5 x 3 x 0.75 Inches form factor. 275 Watts with Forced Air Cooling. Efficiencies up to 92% Standby Power < 0.5 W

CLP0205 Open Frame Power Supply Vac input; 5Vdc output; 200W Output Power; 0.25A stdby

Dry-Type Transformers

MINI-PS AC/24DC/1.3

TPP 40 Series, 40 Watt. Order code Output voltage Output current max. Efficiency. max. screw terminal pin connector Vout 1 Vout 2 Vout 3

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

LINE CONDITIONERS Mi Mni nstat ista itc/steroguard

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

POWER QUALITY PRODUCTS FOR NON-LINEAR LOADS

Est Triplen Power Distribution Unit TPDU kVA

Isolated High Level Voltage Output 7B22 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H

TE60 60W Single Output External Power Test & Measurement/Industrial Series

These power supplies are ideal for medical, telecom, datacom, industrial equipment and other applications.

11SP 4247 LCD TV Power specification Rev 1.3 Specification

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors.

Asia-Pacific North America Europe, Middle East Bel Power Solutions, Inc. BCD.

Power Protection and Conditioning

SPECIAL SPECIFICATION 6609 Fiber Optic Color Video and Data Transmission Equipment

LED Driver. CertaDrive 18W 0.39A 46V V CI018C039V046FNN1M. Specifications. Enclosure. Wiring Diagram. Input and output use lead- wires.

These power supplies are ideal for telecom, datacom, industrial equipment and other applications.

VXR S SERIES 1.0 DESCRIPTION 1.1 FEATURES 1.2 COMPLIANCE 1.3 PACKAGING 1.4 SIMILAR PRODUCTS AND ACCESSORIES

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

SINGLE-PHASE VSV SWITCH

EMI Installation Guidelines

TECHNICAL DESCRIPTION

RoHS APPROVAL SHEET. ituner 12V/5A SERIES NO. (05) EA10523C-120 CUSTOMER CUSTOMER P/N DESCRIPTION EDAC MODEL DATE REVISION 0

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

B-2200/2300/3200 SERIES

K Factor Power Transformers

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT

WDG 12 - Technical Data Sheet

VXR D SERIES HIGH RELIABILITY COTS DC-DC CONVERTERS

Transcription:

PRODUCT SPECIFICATION FOR A 15 THRU 500 kva, THREE PHASE, MODULAR POWER REGULATOR AND CONDITIONER PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) 1.0 General This specification covers the electrical characteristics and general requirements for a modular power conditioner and voltage regulation. The PIRANHA shall include all components and systems required to install, operate and maintain the system. The PIRANHA shall utilize tap switching regulation technology. 2.0 Applicable Documents 2.1 The National Electrical Code NFPA (Latest Edition). 2.2 American National Standards Institute Corp. and its Applicable standards C39.1, C80.1, C89, C84.1. 2.3 FCC Part 15, Sub-Part J, Class A. 2.4 IEC 435 International Electro-technical Commission Recommendation "Safety of Data Processing Equipment". 2.5 VDE 0804/3.77 Verbauch Deulscher Elektotechniker standard. "Telecommunication and Electronic Data Processing Unit and Systems". 2.6 UL 1950 Underwriters Laboratories Inc. Standard for Safety. Electronic Data Processing and Office Equipment systems. 2.7 VDE 0806 Verbond Deutscher Electrotechniker Standard "Safety Design". 2.8 2.9 2.10 2.11 2.12 NEMA National Electrical Manufactures Association and its applicable standards. Local Inspection Authorities having jurisdiction over electrical equipment and its installation. MIL-T-27B Dry Transformer Insulation. UL 1561, K- Factor Transformer Ratings. NEMW TP-1, Energy Star, efficiency rated transformers 3.0 Major Components The basic components of the PIRANHA shall consist of: a three phase, copper wound, isolation transformer; input main circuit breaker; regulation electronics; internal wiring; manual bypass switch; input / output terminal blocks; input / output filters, over current and over temperature protection. 1

4.0 System Package and Construction 4.1 Agency approval. The PIRANHA shall be UL Listed. 4.2 Input Main Circuit Breaker (IMCB) The PIRANHA shall be equipped with an input main circuit breaker. The IMCB shall be rated for 125% of full load and be of thermal magnetic molded case construction. The IMCB shall have a minimum of 25,000 AIC rating. Provision for higher interrupting capacity shall be incorporated into the design to accommodate this type of breaker if required. The IMCB shall be UL Listed. 4.3 Cabinet The Cabinet shall consist of the following: 1. Frame The Frame shall be of tubular construction of heavy gage metal and welded for maximum strength. Each frame shall be treated before paint is applied and be of textured baked enamel. 2. Internal Sheet Metal Internal sheet metal not welded to the frame shall be galvanized, treated or Gold Zinc wash plated to ensure RFI, EMI susceptibility reduced to the absolute minimum. 3. Access Access to the IMCB shall be through two metal doors attached with a continuous hinge and held shut with two keyed locks. 4. Top Cover The top cover shall not contain any openings into the interior of the PIRANHA 5. Alternative Cabinet (kva dependent) NEMA 4, 4R and 12 cabinets are available. 4.4 Isolation Transformer A copper wound, 3-phase, isolation transformer shall be provided. Construction of the transformer should separate the Primary connections and the Secondary connections by placing them on opposite sides of the core (when possible). In addition, the output terminals of the secondary shall be at opposite ends of the coil (when possible) from the input terminals of the primary to minimize the possibility of transverse mode injection. A copper foil shield shall be provided to allow a large surface area for shunting RFI signals of the core to ground. The isolation transformer shall be mounted on rubber isolation pads to prevent 60 Hz hum of the core from being transmitted to the frame. The Transformer insulation system shall be 220 C. The transformer temperature rise shall be 150 C rise at full load. K-13 rating is standard with higher K Ratings transformers available. 4.5 Regulation Electronics A solid state electronic regulation system shall be provided. This technology shall use IGBT s high frequency technology in its construction and shall be rated at 100% above worst case current ratings without any adverse effects. The regulation system shall respond to a change in the input voltage within 1millisecond. 2

4.6 Bypass Switch A manually operated bypass switch shall be provided. In the event that the electronic control circuit fails, the manual switch shall be available to select the bypass of the transformer to provide nominal voltage to the load. Access to the bypass shall not require removal of any panels. The bypass switch shall be accessible by the operator by opening the front doors. The bypass switch is a break-before-make" switch. 4.7 Internal Wiring All internal wiring shall be UL Listed appliance wire or power wiring of multi stranded construction. When in close proximity, Secondary and Primary wiring shall cross at a 90 angle to minimize the injection of transient electrical noise between the two circuits. 4.8 Single Point Ground (SPG) A single point ground shall be provided. The following shall be grounded to the SPG: 1. Equipment grounds. 2. Neutral (neutral to ground bond of the isolation transformer). 3. Core of the Transformer. 4. Frame. 5. Equipment grounding conductor from the branch circuit. 4.9 Input Transient Noise Filter The Input Transient, electrical noise filter consist of a resistor/capacitor network which acts as a large snubber circuit to eliminate high frequency impulses from entering the power conditioner. 4.10 Output Transient Noise Filter The Output Transient Noise Filter consists of a capacitor network installed on the secondary. This capacitor network, when coupled with the primary filter, virtually eliminates most electronic noise from reaching the applied load or being fed back to the unit from noise generating loads. 4.11 Surge Suppression A transient suppression network shall be located on the secondary side of the isolation/regulation transformer. The Surge Suppressor shall suppress common mode and transverse mode noise. The Surge Suppressor shall have the following characteristics: 1. Fault Current. 200 amp max / 10,000 amp max short circuit current. 3

2. Maximum Surge Current, Single Pulse, 8/20 µs 20 ka 3. Suppression Voltage / Current L-N, N-PE 500 A, 100 khz (6 kv) Using ANSI/IEEE C62-41 wave shapes 500 A, 8/20 µs (6 kv) 3 ka, 8/20 µs (6 kv) 10 ka, 8/20 µs (20 kv) 4. UL 1449 Suppression Voltage, L-N, N-PE 5. Surge Energy Capability, Total 3056 joules 6. Surge Life, VAC L-N applied 3 ka, 8/20 µs 3000 times 10/20 µs 75 times 7 Response Time <1ns 8. Visual service indicators (one for each phase) shall be provided to indicate that the Surge Suppressor is no longer providing protection. 5.0 Electrical Characteristics 5.1 60 Hz Frequency units 1. Output Rating kva: 10, 15, 30, 50, 75, 100,125, 150* 2. Input Voltage: 208 or 480 VAC* 3. Output Voltage: 208Y/120 or 480Y/277 VAC * 4. Input Frequency Tolerance: 60 Hz ± 3 HZ 5.2 50 Hz Frequency Units 1. Output Rating, kva: 15, 30, 50, 75, 100, 150* 2. Input Voltage: 380 or 415 VAC* 3. Output Voltage: 380Y/220 or 415Y/240* 4. Input Frequency Tolerance: 50 Hz ± 3 Hz *= consult factory for others 5.3 Transformer 1. Type: Dry, copper wound, isolation 2. Impedance: 3% to 5% maximum 3. Efficiency: 96 % @ 100% load 4. Load Power Factor: Unity to 0.3 lead or lagging 4

5. Noise rejection (typical): Common mode - 120 db (0.1 Hz to 10 MHz) Normal Mode - 60 db/decade (starting @ 2 KHz) 5.4 Audible Noise: Meets or exceeds NEMA standards 5.5 Input Voltage Regulation: +10 to -15 % of nominal 5.6 Output Voltage Regulation: ± 1% typical; ± 2% maximum for all load and line conditions 5.7 Response time: 1 millisecond typical 5.8 Output Rating: Continuous regardless of line / load conditions 5.9 Overload Inrush Rating: 200% of full load for 10 seconds 6.0 Physical Characteristics 6.1 Dimensions of Nema 1 cabinet: Height Width Depth 10 150 kva 71" 42.0" 25" Consult factory for other cabinet configurations. 6.2 Floor Loading Weight: Not to exceed 250 lbs. per sq./ft. 7.0 Operating Environment 7.1 Temperature: 32 F to 104 F (0 C to 40 C) 7.2 Humidity: 10% to 90% relative humidity, non-condensing 7.3 Altitude: 0 to 7000 ft. 8.0 Storage Environment 8.1 Temperature: 32 F to 140 F (0 C to 60 C) 8.2 Humidity: 10% to 90% relative humidity, non-condensing 9.0 Warranty The manufacturer shall warrant the PIRANHA to be free from defects in both material and workmanship for a period of 12 months from the time of installation or 18 months after shipment, which ever occurs first. 5

10.0 Manufacturer's Qualifications The PIRANHA shall be furnished by a manufacturer who specializes in the manufacturing of Power Quality Systems. The manufacture shall have at least 20 years experience in the design and manufacturing of such products. 11.0 Qualified Systems. The unit shall be a PIRANHA, Automatic Voltage Regulator as manufactured by DSPM 1921 S. Quaker Ridge Place Ontario, California 91761 (714) 970-2304 office (909) 930-3335 Fax 800? 6