A New Active Interphase Reactor for 12-Pulse Rectifiers Provides Clean Power Utility Interface

Similar documents
New 24-Pulse Diode Rectifier Systems for Utility Interface of High-Power AC Motor Drives

An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number

RECENTLY, the harmonics current in a power grid can

Third Harmonics Injection Applied To Three Phase/Three Level/Three Switch Unidirectional PWM Rectifier

A Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications

TO LIMIT degradation in power quality caused by nonlinear

Multilevel Inverters (Copyrighted Material) Prasad Enjeti, Ph.D.

Power Quality Improvement by Input Current Harmonic Reduction Using Three-Phase Multi-Pulse AC-DC Converter

Multi-Pulse Converters for High Voltage and High Power Applications. 2.1 Operating Principles

International Journal of Advance Engineering and Research Development. 18 Pulse Uncontrolled Rectifier

MODERN switching power converters require many features

A Novel Three-Phase to Nine-Phase Transformation using a Special Transformer Connection

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

IMPLEMENTATION OF PERFORMANCE ANALYSIS OF 18-PULSE AC-DC CONVERTER FED SWITCHED RELUCTANCE MOTOR DRIVES TO ROBOTICS

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

Improvement of Power Quality by Using 28-Pulse AC-DC Converter

Three-Phase Multi-Pulse Converter with Phase-Shifting Transformer

Power Quality Improvement using a 28-pulse AC-DC Converter for SMPS

CHAPTER 1 INTRODUCTION

Lecture 19 - Single-phase square-wave inverter

A Predictive Control Strategy for Power Factor Correction

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Dr.Arkan A.Hussein Power Electronics Fourth Class. Operation and Analysis of the Three Phase Fully Controlled Bridge Converter

A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Closed Loop Control of Multipulse Rectifier Using Novel Modulation Techniques

Hardware Implementation of SPWM Based Diode Clamped Multilevel Invertr

THE rapid development of power electronics in recent

Power Quality Improvement in Induction Motor Drive using 24-Pulse AC-DC Converter Employing Pulse Multiplication Technique

Understanding Input Harmonics and Techniques to Mitigate Them

THE third-harmonic current injection is a method to reduce

A THREE-PHASE HIGH POWER FACTOR TWO-SWITCH BUCK- TYPE CONVERTER

Harmonics White Paper

ECEN 613. Rectifier & Inverter Circuits

ECEN 613. Rectifier & Inverter Circuits

A NEW SOFT-SWITCHING ACTIVE CLAMP SCHEME FOR FULL-BRIDGE ISOLATED CURRENT FED DC-DC CONVERTER FED DRIVES

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

Bidirectional Ac/Dc Converter with Reduced Switching Losses using Feed Forward Control

Minimization Of Total Harmonic Distortion Using Pulse Width Modulation Technique

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Electrical Distribution System with High power quality Based on Power Electronic Transformer

COMPARATIVE ANALYSIS OF MULTIPULSE AC-DC CONVERTERS IN VCIMD

Harmonic Mitigation in AC DC Converters for Induction Motor Drives by Vector Controlled

International Journal of Advancements in Research & Technology, Volume 7, Issue 4, April-2018 ISSN

A Novel Power Factor Correction Rectifier for Enhancing Power Quality

Introduction to Rectifiers and their Performance Parameters

ISSN Vol.03,Issue.42 November-2014, Pages:

Effective Harmonic Mitigation with Active Filters

A BRUSHLESS DC MOTOR DRIVE WITH POWER FACTOR CORRECTION USING ISOLATED ZETA CONVERTER

International Journal of Scientific & Engineering Research, Volume 5, Issue 3, March-2014 ISSN

Simulation of H bridge Inverter used for Induction Melting Furnace

A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction

A New Three-phase Low THD Power Supply with High-Frequency Isolation and 60V/200A Regulated DC Output

v o v an i L v bn V d Load L v cn D 1 D 3 D 5 i a i b i c D 4 D 6 D 2 Lecture 7 - Uncontrolled Rectifier Circuits III

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Improving Passive Filter Compensation Performance With Active Techniques

ATYPICAL high-power gate-turn-off (GTO) currentsource

16B2011B1 EASY HARMONICS USER MANUAL

ISSN Vol.03,Issue.07, August-2015, Pages:

THE KURII CIRCUIT: A HIGH POWER FACTOR AND LOW COST THREE-PHASE RECTIFIER

I. INTRODUCTION. 10

A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation

HARMONIC contamination, due to the increment of nonlinear

Three phase six-switch PWM buck rectifier with power factor improvement

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Switching Angles and DC Link Voltages Optimization for. Multilevel Cascade Inverters

COMPARISON OF POWER QUALITY SOLUTIONS USING ACTIVE AND PASSIVE RECTIFICATION FOR MORE ELECTRIC AIRCRAFT

REDUCTION OF THD IN POWER SYSTEMS USING STATCOM

A 24-Pulse AC DC Converter Employing a Pulse Doubling Technique for Vector-Controlled Induction Motor Drives

ELEC387 Power electronics

Power Quality Notes 2-1 (MT)

MULTICARRIER TRAPEZOIDAL PWM STRATEGIES FOR A SINGLE PHASE FIVE LEVEL CASCADED INVERTER

THE converter usually employed for single-phase power

Performance analysis of a Ĉuk regulator applying variable switching frequency

Simulation Study of PWM Techniques for Voltage Source Converters

A REVIEW ON THREE-PHASE TO SEVEN-PHASE POWER CONVERTER USING TRANSFORMER

Low Order Harmonic Reduction of Three Phase Multilevel Inverter

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

PULSE MULTIPLICATION IN FORCED- COMMUTATED CURRENT SOURCE CONVERTERS BY DC RIPPLE REINJECTION

22.0 Harmonics in Industrial Power Systems

A Novel Delta/Hexagon-Connected Transformer-Based 72-Pulse AC-DC Converter for Power Quality Improvement

Modular Grid Connected Photovoltaic System with New Multilevel Inverter

12 Three-phase Controlled Rectifiers

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

7/15/2002 PP.AFD.08 1 of 28

Multilevel Inverter Based Statcom For Power System Load Balancing System

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Study of Power Factor Correction in Single Phase AC-DC Converter

A New Three-Phase Interleaved Isolated Boost Converter With Solar Cell Application. K. Srinadh

Power quality improvement of self- excited induction generator using Multipulse AC-DC converters - A comparison

A Novel Single-Stage Push Pull Electronic Ballast With High Input Power Factor

COMMON mode current due to modulation in power

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Modeling and Simulation of STATCOM

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Transcription:

A New Active Interphase Reactor for 12-Pulse Rectifiers Provides Clean Power Utility Interface Sewan Choi* Prasad N Enjeti' Honghee Lee ** Ira J Pitel**' * * *Magna-Power Electronics *Power Electronics Laboratory Dept. of Electrical Engineering **Dept. of Control and Instru. University of Ulsan 85 Fulton st. Texas A M University Ulsan, Korea Boonton, NJ 07005 College Station, TX 77843-3128 Tel: (0522) 78-2 I87 Tel: (201) 263-0017 Tel: (409) 845-7466 Fa~:(O522) 77-3419 Fa: (201) 263-1928 Fa: (409) 845-6259 E-mail: enjeti@eesunl. tamu. edu Abstract - In this paper, a new active interphase reactor for twelve-pulse diode rectifiers is proposed. The proposed system draws near sinusoidal currents from the utility. In this scheme, a low kva ( 0.03 per unit ) active current source injects a triangular current into an interphase reactor of a twelve-pulse diode rectifier. The modification results in near sinusoidal input current with less than 1% THD. It is further shown that a low kva, 12-pulse system with an autotransformer arrangement ( kva rating of 0.18 per unit ) can be implemented with the proposed modification. The resulting system draws clean power from the utility and is suitable for powering larger kva ac motor drive systems. Detailed analysis of the proposed scheme along with design equations is illustrated. Simulation results verify the concept. L Introduction Large harmonics, poor power factor and high total harmonic distortion (THD) in the utility interface are common problems when nonlinear loads such as adjustable speed dnves, power supplies, induction heating systems, UPS systems and aircraft converter systems are connected to the electric utility. In several cases, the interface to the electric utility is processed with a three phase uncontrolled diode bridge recmer. Due to the nonlinear nature of the load, the input line currents have si@cant harmonics. For adjustable speed ac motor dnve systems with no dc-link smoothing inductor, the discontinuous conduction of the diode bridge rectifier results in a high THD and can lead to the malfunction of sensitive electronic equipment. The recommended practice, IEEE 519, has evolved to maintain utility power quality at acceptable levels [ 11. Rectifier U 1 I Lor kva 1 I I- I Rectifier I Fig. 1 Circuit diagram of the proposed clean power utility interface Scheme I. Current I, is near sinusoidal in shape with less than 1% THD. A number of methods have been proposed to overcome the presented problems 12-12]. One approach is to use a standard twelve-pulse converter which rqires two six-pulse converters connected via Y-A and Y-Y isolation transformers. An interphase reactor is required to ensure the independent operation of the two parallel-connected threephase diode bridge rectifiers. The operation of the standard twelve-pulse converter results in the cancellation of the 5th and 7th harmonics in the input utility line currents. To increase the pulse number further to 18 or 24, additional diode bridge rectifiers along with complicated multiphase transformer arrangements become necessary, which adds to the cost and complexity. This paper proposes a new three-phase diode rectifier system which draws near sinusoidal input currents from the three phase electric utility. Two possible ways for implementation are shown and are called Schemes I and 11. 0-7803-3008-0195 $4.00 0 1995 IEEE 2468

In Scheme I ( Fig. l), a A - Y isolation transformer of 0.52 per-unit capacity is employed. The interphase reactor and the line impedances LsI, Ls2 are designed such that stable twelve-pulse operation is obtained with equal current sharing. A low kva( 0.03 per unit ) PWM-controlled active current source, I, is now injected into the secondary winding of the interphase reactor. It is shown via rigorous mathematical modeling as well as computer simulations that the exact shape of I, (Fig. 3 (a)) can be computed to alter the utility line current I, to a perfect sinewave. It is further shown that an approximation to the exact waveshape of I, is a triangular wave (Fig. 4 (a)). Therefore by injecting a triangular shaped current I, into the secondary winding of the interphase reactor, near sinusoidal input line currents flow in the utility line with less than 1% THD. Fig. 6 shows the active interphase reactor implementation in Scheme 11. In this scheme, an autotransformer is employed to obtain 30 degree phase shift between the two diode rectifiers. Two interphase reactors now become necessary due to the absence of electrical isolation [12]. The kva rating of the proposed autotransformer is 0.18 per unit. The resulting input current with thls approach is also near sinusoidal providing clean power utility interface. Both of the topologies shown in Schemes I and I1 result in hgh performance with reduced kva components and offer clean power utility interface suitable for powering larger kva ac motor drives. Detailed analysis of the proposed schemes is discussed. IL Proposed clean power utility interface - Scheme I Fig. 1 shows the circuit diagram of the proposed scheme to shape input line currents. The main transformer has delta-wye winding ( kva rating of 0.52 per unit ) with a,/? to 1 turns ratio to maintain an equal per unit voltage. They are connected in such a way that the two diode bridge rectifiers have balanced sets of three-phase voltages with 30 degrees phase shift. The proposed system is identical to a standard 12-pulse system except that the interphase reactor has an additional winding. The additional winding is used to inject a low kva PWM current source to shape input line current. With the PWM current source, I,, disabled (i.e. I, = 0) the system operates as a standard 12-pulse rectser providing cancellation of the 5th and 7th harmonics in the input line currents, I,, Ib and I,. The active current source I,, when injected into the interphase reactor (Fig. l), results in near sinusoidal input current with unity input power factor. The following selctions illustrate the proposed concept in more detail. 1.5 i -1-0.5-1,5... -.- 0 7T Fig. 2. Switching function Sal for Rectifier I A. Analysis of the proposed active interphase reactor - Scheme I Fig. 1 shows the proposed active interphase reactor scheme I for a 12-pulse diode rectifier. In this section, waveforms are analyzed to determine the relationship between current I, and input currents I,, Ib and L. With I, = 0, input current I, can be shown to be [2,5], Equation (1:) describes a 12-pulse input line current with 5th and 7th harmonics absent and 1 Id, :=I --I, "-2 An active current I, is now injected into the secondary winding of the interphase reactor as shown in Fig. 1. Fig. 8 shows the circuit topology for implementing this scheme. Analyzing lhe MMF relationship of the interphase reactor, we have, where Np and N, are the numbers of turns of the primary and the secondaq windings of the interphase reactor. The load current Id is,, I, :=I,, +Id2 From (3) and (4) we have, (3) (4) 2469

1 N I,, =-(Id ->Ix) 2 NP I N I --(I, +>Ix), -2 Np Fig. 2 shows switching function Sal for phase a of Rectifier-I shown in Fig. 1. The Fourier series expansion for Sa, is given by, 1. 1. - -sln7ot + -smllot+ 7 11 and for phase b and c, the switching functions can be written as, s,, = S,,L - 120 sc, = S,,L + 120 Similarly, the switching functions for Rectifier-I1 in Fig. 1 with a 30 degree phase shift are, (7) Note I, is replaced by I,],where I,1 is the fundamental rms component of I,. Therefore, equation (12) describes the exact shape of I, for a given load current Id. Since input power is equal to output power, we have &VJ,, = V,Id (13) where v, = 1.35vuand VL, is the line to line rms voltage. Hence, from (13) we have, I a,, = 0.7794 I, (14) Now, for input current I, to be sinusoidal, i.e., I, = &I1,,sinot (1 Fig. 3 (a) shows the shape of I, for sinusoidal input current. B. Simulation results of the proposed approach Sa, = S,,L - 30 Sb2 = S,,L - 30 S,, = S,,L-30 The input currents for Rectifier I and I1 can now be expressed in terms of switching functions as, (9) -! -1.5 i...... 0 7T (a) 27c and Equation (1) can now be modified using (5) and the switching functions described in (6)-( 10) as, Ia 0.4 / -1 4-1. 1 0 7c 27c Equation (11) illustrates the relationship between I, and input current I,. For input current I, to be sinusoidal, (b) Fig. 3 (a) Injected current I, calculated from (12) (b) Input line current I,(pure sinusoidal) The proposed active interphase reactor approach shown in Fig. 1 is simulated on SABER and the results are presented in this section. From Fig. 3 (a), it is apparent that I, is near triangular in shape. Simpllfylng the injected current I, to a triangular wave shape( Fig. 4(a) ) yelds a near sinusoidal input current I, ( Fig. 4 (e)). Furthermore, 2470

generating a triangular injection current I, into the secondary of the interphase reactor can be accomplished by means of a PWM-controlled current source (Fig. 9). Fig. 4 (b) and (c) show the respective input currents of the rectifier blocks I and I1 (Fig. 1) as a.result of the injected current I,. Fig. 5 (a) and (b) show the dc output voltages Vdl and V,. Fig. 5 (c) shows the voltage across the interphase reactor. It should be noted that injecting active current I, ( Fig. 4 (a) ) which is triangular in shape yields near sinusoidal input currents (Fig. 4 (e) ) of less than 1% THD. The kva rating of the injected current is small and is computed in the next section..------- _---,,I..(.,., U...,.,.r,,.m I (I, ii Fig. 4 Simulation results for the proposed Scheme I ( Fig. 1) (a) Injected current I, (b) Rectifier I input current I,, (c) RecWier I1 input current Id (d) Input line current I, (e) Frequency spectrum of I, 247 1

I,,,, = E= 0.2887 per unit J5 The rms value of I, can be reduced by adjusting turns ratio @I@&) between the primary and the secondary windings of the interphase reactor. From (21) and (22), the kva rating of the injected current source, kvar, can be computed as, Fig. 5 Simulation Results of Scheme I ( Fig. 1 ) (a) Rectifier I output voltage vdl (b) Rectifier I1 output voltage V, (c) Voltage across the interphase reactor V, = vd2-vdl C. kva rating of the injected current source, I, The line to line rms input voltage Vu and dc output current Id is assumed to be 1 per unit. The voltage across the interphase reactor V, ( see Fig. 1 ) can be expressed as, v, = v,, - v,,. Fig. 5 (a) and (b) show the waveshape of vdl and V,. Furthermore, vdl can be expressed in Fourier series as [3], From (13) the output power for the 12 pulse system in Fir is, Po = V,.Id = 135 perunit (24) Therefore, the percentage kva rating of the injected current source with respect to the output power becomes, kva,, = * 100 (25) Po = 332(%) Equation (25) shows that the kva rating of the injected current source I, is a small percentage of the output power. This demonstrates the superior features of the proposed scheme to realize a clean power utility interface. Output voltage V, is phase shifted by 30 degree. substituting (17) into (16), V, can be expressed as, nx. nx. x (18) V, =-5.4018V, cos-sin-sm n(wt - -1 1-6J2.18.. n' -1 l2 12 From (18), the rms value of V, can be computed as, Vm,ms = 0.1553V, By (19) The voltage across the interphase reactor secondary winding V, is given by, N V ' v = NP Then, from (19) and (20) the rms value of V, is, N V,,,, = 0.1553VLL 2. NP From the results in the previous section, the peak value of the current I, of Fig. 4 (a) is 0.5 Id for N, / Np = 1. Therefore, the rms value of I, for a triangular waveshape is, DI. Proposed active interphase reactor-scheme II In this section, Scheme I1 of the active interphase reactor implementation is discussed. Fig. 6 shows the propos':t.. clean power utility interface implementation wth an autotransformer connection. Fig. 7 (a) shows the vector diagram of the delta type autotransformer. The proposed autotransformer generates two three-phase sets of voltages displaced +15 degrees from the input supply ( Fig. 7 (a) ). Fig. 7 @) shows the resulting autotransformer winding arrangement on a three-limb core. It has been shown [12] that the kva rating of the delta type autotransformer is 0.18 per unit. Fig. 6 shows the resulting active interphase reactor implementation with the autotransformer arrangement. A current source I, can now be injected such that the utility line current ( I,, Ib and I, ) are near sinusoidal in shape. The switching function analysis discussed in section 1I.A can be repeated for Scheme I1 shown in Fig. 6. Input current I, can be expressed as, 2472

section employs low kva magnetics and is currently undergoing, active evaluation in the Power Electronics Laboratory of Texas A&M University. IV. Implementation of the active current source I. Fig. 8 shows the circuit topology of the PWM-controlled active current source for I, in Scheme I. A six pulse injection ciurrent I, of triangular in shape ( Fig. 4 (a) ) is generated with a PWM-controlled current source. Fig. 9 shows the block diagram of the PWM current loop. ReeWiisr II Rectifier I Fig. 6 Circuit diagram of the proposed clean power utility interface Scheme I1 Rectifier If 1 1 '- p--- Rectifier I Fig. 8 Circuit diagram for implementation of the proposed schemes. I I Amullfier ComDarntor (b) Fig. 7 (a) Vector diagram of the delta-type autotransformer connection (b) Autotransformer windings on a three limb core Fig. 9 Block diagram of the current controlled PWM gating signal generator. VL Conclusion For the triangular-shaped injected current I, of Fig. 4 (a), the input line current I,,expressed as (26), becomes near sinusoidal in shape and approximates that shown in Fig. 4 (e). The clean power rectifier Scheme I1 discussed in this In this paper a new active interphase reactor for a twelve-pulse rectifier system has been proposed. It has been shown that by injecting a low kva ( 0.03 per unit ) active current source I, into the interphase reactor near sinusoidal input currents with less than 1% THD can be obtained. It is further shown that a low kva twelve-pulse system with the proposed active interphase reactor can be implemented with 2473

autotransformers. The resultant system is a high performance clean power utility interface suitable for powering larger kva ac motor drive systems. Detailed analysis of the proposed scheme along with design equations has been illustrated. Simulation results have been shown to venfy the proposed concepts. References [I] IEEE Recommended Practices and Requirements for Harmonic Control in Electric Power Systems, IEEE PES and Static Converter Committee of IAS, Jan. 1993 [Ill I. Pitel and S. N. Talukdar, A Review of the Effects and Suppression of Power Converter Harmonics, IEEE IAS Conference, May 1977. [12] S. Choi, A. Jouanne, P. Enjeti, I. Pitel, New Polyphase Transformer Arrangements with Reduced kva Capacities for Harmonic Current Reduction in Rectifier Type Utility Interface, IEEE PESC conf.,1995 [ 131 P. Enjeti and I. Pitel, An Active Interphase Reactor for 12-pulse rectifiers, U. S. Patent disclosure [2] J. Schaefer, Rectifier Circuits: Theory and Design, John Wiley & Sons, Inc., 1965 [3] B. R. Pelly, Thynstor Phase-Controlled Converters and Cycloconverters, John Wiley & Sons, 197 1, [4] R. W. Lye, etc. al, Power Converter Handbook, Power Delivery Department, Canadian General Electric Company Ltd.. 1976 [5] G. Seguier, Power Electronic Converters ACDC conversions, McGraw-Hill, New York, NY, 1986. [6] G. Oliver, etc. al, Novel Transformer Connection to Improve Current Sharing on High Current DC Rectifiers, pp. 986-992, IEEE IAS cod.., 1993. [7] S. Miyairi, etc. al, New Method for Reducing Harmonics Involved in Input and Output of Rectifier with Interphase Transformer, IEEE Trans. on Industry Applications, pp. 790-797, Vol. IA-22, No. 5, Sep./Oct. 1986 [8] A. R. Prasad, P. D. Ziogas, S. Manias, An Active Power Factor Correction Technique for Three-phase Diode Rectifiers, pp. 83-92, IEEE Trans. on Power Electronics, Vol. 6, No. 1, Jan. 1991 [9] Ned Mohan, A Novel Approach to Minimize Line- Current Harmonics in Interfacing Renewable Energy Sources with 3-Phase Utility Systems, IEEE AF EC Annual meeting, 1992, pp.852-858. [IO] S. Kim, P. Enjeti, P. Packebush and I. Pitel, A New Approach to Improve Power Factor and Reduce Harmonics in a Three-phase Diode Rectifier Type Utility Interface, pp. 1557-1564, IEEE Trans. on Industry Applications, Vol. 30, No. 6, Nov./Dec. 1994. 2474