Harmonic Analysis and Power Factor Correction For Food Processing Industry

Similar documents
A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Active Harmonic Filter (AF3)

Effects of Harmonic Distortion I

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Thyristorised Automatic Power Factor

Low Pass Harmonic Filters

Power Factor. Power Factor Correction.

Analysis of Harmonic Distortion in Non-linear Loads

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Understanding Input Harmonics and Techniques to Mitigate Them

Electromagnetic Harmonic Filters Technical Guide

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

UNBALANCED CURRENT BASED TARRIF

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Generator Advanced Concepts

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

CHAPTER 4 HARMONICS AND POWER FACTOR

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

Economical Solutions to Meet Harmonic Distortion Limits[4]

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Emicon Engineering Consultants L.L.C.

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Fundamentals of Power Quality

Power Quality Analysis in Power System with Non Linear Load

Influence of Switching Elements on Harmonics and Power Factor Improvement

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

22.0 Harmonics in Industrial Power Systems

Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost Regulator

1C.4.1 Harmonic Distortion

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Reduce harmonics in HVAC&R inverters through C-Less technology

Study of Power Factor Correction in Single Phase AC-DC Converter

Power Quality Study of Electrical Installation in Academic Institute Case Study

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

NJWA - Harmonics and Drives Proper System Design

Harmonic Filters for Single Phase Equipment

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Hybrid Islanding Detection Method for Distributed Generators

Load Isolation Transformers

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Power Factor and Power Factor Correction

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Harmonic Filters and Reactors

Harmonic Distortion and Variable Frequency Drives

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

General Description & Features Selection Charts Definition of Terms... 42

1. Introduction to Power Quality

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

PowerMonitor 5000 Family Advanced Metering Functionality

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Harmonics, its Mitigation & Result of Case study of Spinning Mill

Tuningintobetter power quality

Fluke 40/41 Power Harmonics Analysers

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

VARIABLE FREQUENCY DRIVE

EFFICIENT POWER QUALITY: AN APPROACH TO ENERGY CONSERVATION

Southern Company Power Quality Policy

McGill Power Sales & Engineering, INC.

Speed Control Of Transformer Cooler Control By Using PWM

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Improve Power Factor and Reduce the Harmonics Distortion of the System

Power Quality Monitoring and Power Metering Tutorial

Introduction to Harmonics and Power Quality

1) The diagrams in the section Assembly notes were provided by Rittal GmbH Co. KG, Herborn and by Invensys Systems GmbH EUROTHERM, Limburg/ Lahn.

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

POWER FACTOR CORRECTION AND ITS PITFALLS

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Power Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers

Advantages There are many diverse advantages of a portable analyzer for the user. The most important is information.

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants

LINEATOR. Advanced Universal Harmonic Filter

TOPOLOGICAL ISSUES IN SINGLE PHASE POWER FACTOR CORRECTION

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

An Introduction to Power Quality

II. RESEARCH METHODOLOGY

I J C T A, 10(9), 2017, pp International Science Press

Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

Buck-boost converter as power factor correction controller for plug-in electric vehicles and battery charging application

Comparative study on Bridge type Negative Luo converter fed BLDC motor drive.

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load Viralkumar A. Rana 1 Keyur Rana 2 Atul Talati 3

CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses

KRF EMC Filters Installation, Operation and Maintenance Manual

Harmonic Analysis and Its Mitigation Using Different Passive Filters

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

7/15/2002 PP.AFD.08 1 of 28

SINGLE PHASE BRIDGELESS PFC FOR PI CONTROLLED THREE PHASE INDUCTION MOTOR DRIVE

Effective Harmonic Mitigation with Active Filters

OBICON. Perfect Harmony. Short overview. ROBICON Perfect Harmony. System Overview. The Topology. The System. ProToPS. Motors.

Power quality report. A Manufacturing Plant

Transcription:

International Journal of Computational Engineering Research Vol, 03 Issue, 6 Harmonic Analysis and Power Factor Correction For Food Processing Industry Rupali Shinde 1, Amit Pathak 2, Bhakti Chaughule 3 1,2,3, M.Tech Pursuer (Power System), Bharati Vidyapeeth University s college of engg, Pune. ABSTRACT Harmonic analysis of the distribution system is essential to study the behavior of equipments connected in the non-sinusoidal system environment for designing and optimal location of filters. Harmonic distortion can have a significant impact on industrial customers such as additional losses and heating of certain network equipment, faulty operation of control equipment and interference in neighboring telecommunication system. In this case study harmonic analysis of food processing industry has done using harmonic analyzer YOKOGAVA. The aim of the study was to improve the power factor, maintain harmonic distortion within acceptable levels and reduce possible resonance problem at the plant. Analysis of voltage and current harmonics is performed at distribution side point of common coupling before and after connecting APFC panel. KEY WORDS: APFC Panel, Energy Audit, Harmonics, Nonlinear load, Total Harmonic Distortion, Under loaded motors, Yokogava. I. INTRODUCTION It is the objective of the electric utility to supply its customers with a sinusoidal voltage of fairly constant magnitude and frequency. To ensure compliance with the Grid Code [2] voltage and current distortion levels must satisfy limits set out by IEC 61000-3-6 [5]. In any industry, the three top operating expenses are often found to be on energy, labor and materials. If one were to find out the potential cost savings in each of the components, energy would invariably emerge at the top, and thus energy management function constitutes a strategic area for cost reduction.. Industries use a large amount of electrical energy, and that is why it is important to ensure a loss-free and energy-efficient system in industries [3]. In developing countries like India, where electrical energy resources are scarce and production of electricity is very costly, energy conservation studies are of great importance. Energy audit is the translation of conservation ideas into realities by blending technically feasible solutions with economic and other organizational considerations within a specified time frame [4]. An energy audit is a study of a plant or facility to determine how and where energy is used and to identify methods for energy savings. An energy audit was carried out under four major heads: (i) process section audit, (ii) Refrigeration section audit, (iii) power load audit (motors, compressor, etc.), and (iv) harmonic analysis. Readings were taken under these heads and analyzed to find the scope of energy conservation opportunities in the selected test case industrial unit. II. AUDITING PROCEDURE Energy audit cannot be successfully carried out without the commitment from the top management. Management must be firstly convinced of the necessity of implementing energy management and hence energy audit [7]. Energy audit consists of several tasks, which can be carried out depending on the type of the audit and the size and the function of the audited facility [8]. Therefore, an energy audit is not a linear process and is rather iterative. The audit described in this paper has been carried out based on the following functional activities: Walk-through survey Motor load survey used in various processes Harmonic analysis www.ijceronline.com June 2013 Page 53

III. FIELD VISITS AND MEASUREMENT WORK Katraj Dairy is one of the oldest milk processing industry in Pune, Maharashtra. Readings for harmonic distortion and and for power factor improvement are taken with the help of YOKOGAWA(Harmonic Analyser) before and after connecting APFC Pannal. 3.1 Plant Electrical Energy Consumption The energy consumption of the industry was identified in terms of the equipments and functional area wise. The results were obtained after measurements during the factory visits. Power analyzers, Harmonic Analyzer, clamp meters, etc. were used to measure the electrical energy consumption of the industry. The total load of the unit is approximately 1326.3 kw. Sr.no Sections Connected load in HP 1 Air compressor section 182 2 Process section 349.5 3 Refrigeration section 882 4 Boiler section 120 5 E.T.P. section 180 6 Raw water sector 30 7 Ice cream plant 10 8 Illumination 15 Total load in HP 1768.5 Total load in KW 1326.3 TABLE.1 Total load of Katraj Dairy 1 2 3 4 5 6 7 8 Fig.1Load division chart of Katraj Dairy www.ijceronline.com June 2013 Page 54

The following points can be observed from this survey: The major load in the plant is that of refrigeration, which constitutes approximately 66 % of the total load. Motor load constitutes approximately 38% of the total load. Total number of units consumed per month is 188380 after taking the average of 12 months. 3.3 Motor Survey For most of the applications, three-phase, 4-pole, 1470- rpm induction motors of Kirloskar make have been used for various production processes in the plant. During survey and measurement process, it was observed that some of the motors are underloaded. And most of the motors used are energy efficient motors. Load on compressor where 45 KW,1460 rpm, 415V,80 amp,3ph,50 Hz motor is used is continuously varying between 40amp to 80 amp. Other motors have almost constant load on them. 3.4 Problems with Underloaded Motor An underloaded motor always runs at a low lagging power factor. If the motor is loaded around 50% of the rated load, power factor can be as low as 0.5 lagging. This means industry is utilizing only 50% of the power from the supply mains and paying for 100% if the billing is kva based. Extra expenditure on installation of power factor improvement equipment to maintain the power factor within permissible limits set by the state electricity board needs to be done. Otherwise, penalty has to be paid. Efficiency of a standard induction motor is about 87-90% at the rated load and it reduces drastically at half of the rated load depending upon the size of the motor and loading (about 70-75% for 60 hp motor). This means motor will draw more current for the same mechanical output IV. ENERGY-EFFICIENT MOTORS More and more industries are switching to energy-efficient motors (EEMs) because EEMs lower the production costs. Just a small increase in motor efficiency can significantly lower the production costs. A motor can cost thousands of rupees a year to operate, so savings of even a few percent add up quickly. An EEM generates savings whenever it is running and as long as it lasts, which may be 20 years or more. EEMs cost more than the standard motors, but purchase price can be paled in comparison to a motor's operating costs. Since the annual operating cost of a motor is often 5-10 times its initial cost, the typical 3-5% higher efficiency of an EEM can more than offset its 15-20% higher initial cost over its life. In addition to costing less to operate, EEMs generally last longer, require less maintenance, and reduce system amperage draw. The efficiency curves of two EEMs are shown Figure 2: Efficiency of EEMs as per IS-12615 (Eff1 = 2-pole motor, Eff2 = 4-pole motor) EEMs also offer other advantages, such as longer insulation life, longer lubrication interval, greater inertial acceleration, and higher service factors. In addition, they may be better equipped to handle heavy starting loads, large sustained loads, phase imbalances, voltage excursions, high ambient temperatures, and impaired ventilation. EEMs also do not add as much to air-conditioning loads as standard motors, since they do not give off as much heat. www.ijceronline.com June 2013 Page 55

4.1 Energy-efficient Motor's Performance The efficiency of a motor is the ratio of the mechanical power output to the electrical power input. Design changes, better materials, and manufacturing improvements reduce motor losses, making premium or EEMs more efficient than the standard motors [Figure 2]. Reduced losses mean that an EEM produces a given amount of work with less energy input than a standard motor. In 1989, the National Electrical Manufacturers Association (NEMA) developed a standard definition for EEMs [10]. The definition was designed to help users identify and compare electric motor efficiencies on an equal basis. Figure 3: Losses comparison among standard and high efficiency motors [14] V. Harmonic Analysis Harmonics are one of the major concerns in a power system. Harmonics cause distortion in current and voltage waveforms resulting into deterioration of the power system. The first step for harmonic analysis is the harmonics from non-linear loads. The results of such analysis are complex. Over many years, much importance is given to the methods of analysis and control of harmonics. Harmonics present in power system also has noninteger multiples of the fundamental frequency and have aperiodic waveform. The harmonics are generated in a power system from two distinct types of loads. First category of loads are described as linear loads. The linear time-invariant loads are characterized such that application of sinusoidal voltage results in sinusoidal flow of current. A constant steadyimpedance is displayed from these loads during the applied sinusoidal voltage. As the voltage and current are directly proportional to each other, if voltage is increased it will also result into increase in the current. An example of such a load is incandescent lighting. Even if the flux wave in air gap of rotating machine is not sinusoidal, under normal loading conditions transformers and rotation machines pretty much meet this definition. Also, in a transformer the current contains odd and even harmonics including a dc component. More and more use of magnetic circuits over a period of time may get saturated and result into generation of harmonics. In power systems, synchronous generators produce sinusoidal voltages and the loads draw sinusoidal currents. In this case, the harmonic distortion is produced because of the linear load types for sinusoidal voltage is small. Non-linear loads are considered as the second category of loads. The application of sinusoidal voltage does not result in a sinusoidal flow applied sinusoidal voltage for a non-linear devices. The non-linear loads draw a current that may be discontinuous. Harmonic current is isolated by using harmonic filters in order to protect the electrical equipment from getting damaged due to harmonic voltage distortion. They can also be used to improve the power factor. The harmful and damaging effects of harmonic distortion can be evident in many different ways such as electronics miss-timings, increased heating effect in electrical equipments, capacitor overloads, etc. There can be two types of filters that are used in order to reduce the harmonic distortion i.e. the active filters and the passive filters. Active harmonic filters are electronic devices that eliminate the undesirable harmonics on the network by inserting negative harmonics into the network. The goal of harmonic studies is to quantify the distortion in voltage and current waveforms in the power system of industrial units. The results are useful for evaluating corrective measures and troubleshooting harmonic related problems. www.ijceronline.com June 2013 Page 56

5.1 Effects of Harmonics on Networks [10] Overloading of neutral conductor Reduced efficiency of motors Malfunctioning of control equipment Poor power factor of the total system due to introduction of distortion power factor Overloading of power factor capacitors Increase in kva demand of the plant due to increase in rms current drawn Harmonic Analysis And Power VI. RESULTS: Following results are obtained before after connecting APFC panel. Total consumption for FEB- 2013 is 139300. KVA demand is 419. MSEB charges 190Rs. Per KVA for industrial load. Total electricity bill including (TOD tariff, Electricity Duty and other charges) is 10,36,033.06 Rs. They are getting power factor incentive 67,848.40Rs. Total current bill is 9,68,184.66 Rs. Figure (4) Without APFC panel connected THD = 9.1 % Figure (5) With APFC panel with the system THD = 2.3 % www.ijceronline.com June 2013 Page 57

VII. CONCLUSION On the basis of Harmonic analysis study & electrical energy audit conducted, the following recommendations have been suggested to the consumer: In due course of time, if any motor gets damaged or some new motor is to be purchased, EEMs should be purchased. Harmonic components at PCC are greater than the permissible limits. Therefore, the consumer must install harmonic filter to improve the power quality and save the penalty on harmonic emission. Harmonic component across individual loads is much higher where variable frequency drives are used, which reflects at the PCC, so a more in-depth analysis is required and a harmonic filter can be designed. It is also shown in this paper that the proposed PFC capacitor banks can be tuned to act as harmonic filters and operate to reduce the harmonic distortion to acceptable levels. It is recommended that the PFC capacitor banks be tuned to act as harmonic filters and also that upon completion of the plant expansion harmonic measurement are taken to meet the grid code requirement. Proper size of motor should be used, as per the rated load. If possible, motor should be replaced with a proper size motor in a phased manner. REFERENCE [1] Modeling And Harmonic Analysis Of Domestic/Industrial Loads Purushothama Rao Nasini, Narender Reddy Narra and Santosh AEirgrid Grid Code, V.3.1 [2] P. Z. Yaacoh, and A. A. Mohd. Zin, "Electical energy management in small and medium size industries", IEEE TENCON, Beijing, 1993. [3] Thumann, and W. J. Yonger, "Hand Book of Energy Audits", 7 th ed, Lilburn: Fairmont Press Inc.; 2007. [4] IEC 61000-3-6 - Electromagnetic compatibility (EMC) -Part 3-6: Limits - Assessment of harmonic emission limits for the connection of distorting installations to MV, HV and EHV power systems. [5] Huyck, and J. Cappelle, "Electrical energy management for low-voltage clients", International Conference on Clean Electrical Power, IEEE, 2007. [6] X. W. Chen, "Energy Audit of Building: A Case Study of A Commercial Building in Shanghai", Power and Energy Engineering Conference, Asia-Pacific, 2010. [7] Tyagi, "Hand Book of Energy Audit & Management" India: TERI Press; 2000. [8] Catalouge Surelink Technologies" Shenzhen, China, 2008 [9] "IEEE recommended practice for electric power systems in commercial buildings", Recognized as an American National Standard (ANSI) IEEE Standard, pp. 241, 1990. Rupali shinde-m.tech Electrical Power System (Pursuing), Department of Electrical Engineering, Bharati Vidhyapeeth University s College of Engineering, Pune, India. Amit pathak - M.Tech Electrical Power System (Pursuing), Department of Electrical Engineering, Bharati Vidhyapeeth University s College of Engineering, Pune, India. Bhakti Chaughule- M.Tech Electrical Power System (Pursuing), Department of Electrical Engineering, Bharati Vidhyapeeth University s College of Engineering, Pune, India. www.ijceronline.com June 2013 Page 58