FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2

Similar documents
ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

ET 51 - Electrician Theory Examination Marking Schedule

FINAL - EST Electrical Service Technician Answer Schedule

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

EASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE. SECTION 1 Marks Reference Marking notes Qu 1 A 10 MΩ (2 marks)

EAS Electrical Appliance Serviceperson Answer Schedule

ET 61 - Electrician Theory Examination Marking Schedule

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP)

, Power Industries and Communications Industry Training Board

Chapter 6. WIRING SYSTEMS Safe Electrical Design

ET 40 - Electrician Theory Examination Marking Schedule

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

ELECTRICIAN S THEORY EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

MinorWorks/Single Circuit Electrical Certificate

NZQA registered unit standard version 2 Page 1 of 8. Demonstrate knowledge of theory for registration of electrical installers

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

INSTALLATION WARNING: BEFORE COMMENCING INSTALLATION ISOLATE YOUR MAINS ELECTRIC SUPPLY

CURRENT FUTURE REGULATIONS PROPOSALS

Code for Design of Low Voltage Electrical Installations

TT W Wireless receiver Inline Switch

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

FAQ ON EARTHING STANDARDS 16/08/2018

Residual Current Operated Circuit-Breakers (RCCBs)

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL

17TH EDITION BS TH EDITION BS7671 HOW THIS AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.

Section 3. Test Procedures

Residual Current Operated Circuit-Breakers (RCCBs)

power Knowledge The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits.

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

Table of Contents. Introduction... 1

Wisconsin Contractors Institute Continuing Education

Module Title: Electrical Installation II Laboratory Sheet:

SERVICING & METERING SERVICING AND METERING SECTION 5 SEC5:

7. INSPECTION AND TEST PROCEDURES

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

Intermediate Physics PHYS102

VI 3 - i TABLE OF CONTENTS

ELECTRICAL INSTALLATIONS REGULATIONS FOR

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

Portable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No

APRIL 2017 Level 3 Advanced Technical Diploma in Electrical Installation (450) Level 3 Electrical Installation Theory Exam

Chapter F Protection against electric shocks

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3

Chapter F Protection against electric shocks

1. general. 1.1 electric shock. 1.2 direct and indirect contact. electric shock. indirect contact. direct contact

Alternating Current Power

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

PPS MFS series - Installation Guide. Power Protector Stabilizer V 3.8 1

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

Residual Current-operated Circuit Breakers (RCCBs) F 360 and F 370 Range

Residual current circuit breakers (RCCBs)

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

MV network design & devices selection EXERCISE BOOK

Electrical Protection System Design and Operation

G SAFETY WARNINGS. LT300 High current loop tester. User guide

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

Automatic disconnection of lighting circuits from dimming equipment

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Choice of earth leakage protection devices

Earthing, HV Switching and Associated Operational Equipment. Approval: Chief Operating Officer

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv

V1.3. TBLC08 50mH AC-LISN TBLC08

3B SCIENTIFIC PHYSICS

USER'S MANUAL DMR-6700

Field Instruction Switching Activities. Purpose. Scope. Objective. Safety

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Instruction Manual for Digital Grounding Resistance Meter

TECHNICAL NEWS CABLE CONSIDERATIONS [ISSUE 46] DECEMBER 05 FEATURES:

Article 225: Outside Branch Circuits And Feeders

AC/DC CLAMP METER USER S MANUAL

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

IEC ED.1 Safety secondary circuits in series circuits General safety requirements. a new draft

PSSI 27 Work or Testing On or Near to High Voltage Direct Current (HVDC) Plant and Apparatus

User's Guide. AC Circuit Load Tester. Model CT70

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

ELECTRICAL INSTALLATIONS

Customer Connection Guide Updates Effective May 2017

General Requirements. Technical Specification LVAC Systems

CURRENT, POTENTIAL DIFFERENCE AND RESISTANCE PART I

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS

79/26 Series III Multimeter

Controls Contactors and Contactor Assemblies Special Applications

ECET Fall 2017 Name: _ Lab Assignment #01

Utility Interconnection and System Protection

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

Transcription:

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker can exercise their discretion and decide on the overall accuracy of any answer that is presented in the candidate s own words. 3. Symbols and terms - alternatives Power W or P Voltage V or E or U Phase Active Question 1 Marks Reference Marking notes (a) The work is undertaken under such control and direction of a person authorised under the Act to do the work and is sufficient to ensure: That the work is performed competently. That while the work is being undertaken, appropriate safety measures are adopted. That the competed work complies with the requirements of the regulations. (2 marks) EA 2 (b) Use the associated equipment and person protective equipment that is necessary to ensure his or her safety and the safety of other person within the vicinity of the work. (2 marks) ESR 103(2) (c) Any TWO of: The use of a key or tool is required. An interlocking device is fitted. An intermediate barrier is provided. (2 marks) AS/NZS 3000: 1.5.4.4(b) Exception (d) Any TWO of: Where the electrical equipment operates under conditions of fluctuating or intermittent loading, or a definite duty cycle Where the electrical installation is large and complex Where special types of occupancy exist. (2 marks) AS/NZS 3000: 2.2.2(b) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 1

Question 1 Marks Reference Marking notes (e) Any TWO of: The neutral pole of a multi-pole switch or circuit breaker having an appropriate short-circuit breaking and making capacity is linked and arranged to switch substantially together with all active poles. The switch or circuit breaker is linked with corresponding switches so that the neutral contact cannot remain open when the active contacts are closed. A switched neutral pole shall not open before and shall not close after the active pole(s). Where an item of switchgear is required to disconnect all live conductor of a circuit, it shall be of a type such that the neutral conductor cannot be disconnected or reconnected without respective active conductors also being connected or reconnected. (2 marks) AS/NZS 3000 2.3.2.1.1 (b)(ii)(a) AS/NZS 3000 2.3.2.1.1 (b)(ii)(b) AS/NZS 3000 2.3.2.1.1(b)(ii) AS/NZS 3000 2.3.2.1.1(b)(iii) (f) Any ONE of: (2 marks) The minimum size of the main earthing conductor may be determined in relation to the crosssectional area of the minimum cable size required to carry the maximum demand The minimum cross-sectional area determined by calculation shall not be less than the value determined by the following equation. AS/NZS 3000 5.3.3.2 Exception (b) AS/NZS 3000 5.3.3.1.3 (g) An electricity generation system shall be arranged so that it cannot supply energy upstream of the point of connection to the installation either directly or indirectly. (2 marks) AS/NZS 3000: 7.3.3 (h) Any TWO of: Shall not accept plugs of other voltage systems. Shall not have a contact for a protective earthing conductor. Shall have their voltage conspicuously marked. Shall be of a form that will prevent insertion of an extra-low voltage (2 marks) AS/NZS 3000: 7.5.10(b) AS/NZS 3000: 7.5.10(c) AS/NZS 3000: 4.4.1.2(a) AS/NZS 3000: 4.4.1.2(b) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 2

Question 1 Marks Reference Marking notes plug into a socket-outlet connected to a circuit of greater than extralow voltage. The nominal voltage shall not be capable of exceeding the limits for extra-low voltage (50V a.c. or 120V ripple-free d.c.) and the source of supply is arranged so it cannot exceed those values. Circuits shall be electrically segregated from each other and from circuits of higher voltages. Live parts of SELV circuits shall not be connected to earth or to protective earthing conductors that are part of other circuits or to other live parts. Live parts of PELV circuits shall be protected from direct contact by barriers or insulation unless the voltage does not exceed 25Va a.c. or 60V ripple-free d.c. in dry areas where a large contact area with the human body is not expected or 6V a.c. or 15V d.c. in all other areas.. (i) (i) It has a fusing factor between 1.25 and 1.5 AS/NZS 3000: 1.5.7(a) AS/NZS 3000: 1.5.7(b) AS/NZS 3000: 1.5.7(c) AS/NZS 3000: 1.5.7(d) (1 mark) GK (ii) A gg type fuse (1 mark) GK (j) This is the maximum current that can be safely interrupted under short circuit conditions. (2 marks) GK FINAL - IT30 ANSWERS 15 NOVEMBER 2014 3

Question 2 Marks Reference Marking notes (a) (i) The owners and operators of the caravan park. (1 mark) ESR 75(1)(a) (ii) 5 years (1 mark) ESR 75(1)(a) (iii) A periodic assessment may be undertaken only by a person who is authorised to assess prescribed electrical work in a caravan park. (1 mark) ESR 75(2) (iv) (A) The person supplying electricity to the caravan. (1 mark) ESR 76(1) (B) A current warrant of electrical fitness. (1 mark) ESR 76(1) (b) (i) A/NZS 3001 Appendix C4 and C5 (1 mark) AS/NZS 3001 (iii) IEC 60309 AS/NZS 3001 Appendix C4.5 A rating not less than 16A AS/NZS 3001 2.2.7.2(c) AS/NZS 3112 AS/NZS 3001 Appendix C4.5 A rating not less than 15A AS/NZS 3001 Appendix C4.5 (c) The use of 0.4s disconnection times for protective devices fitted to caravan park socket-outlets is to ensure adequate touch voltage control is provided for all transportable structures or vehicles installations connected to those socket-outlets. (2 marks) AS/NZS 3001 2.2.4.2.2 Note FINAL - IT30 ANSWERS 15 NOVEMBER 2014 4

Question 3 Marks Reference Marking notes (a) (i) Final subcircuits supplying one or more socket outlets. Final subcircuits supplying lighting points Final subcircuits supplying directly connected hand-held electrical equipment AS/NZS 3000 2.6.3.1(a) AS/NZS 3000 2.6.3.1(b) AS/NZS 3000 2.6.3.1(c) (ii) 30 ma. AS/NZS 3000 2.6.3.1 (iii) At the switchboard where the final subcircuit originates (1 mark) AS/NZS 3000 2.6.3.1 (b) (i) Type AC AS/NZS 3000 2.6.2.2 Note 1(a) (ii) Tripping is ensured for residual AS/NZS 3000 sinusoidal alternating currents. 2.6.2.2 Note 1(a) (iii) Because tripping is not ensured for residual pulsating direct currents. (2 marks) GK (c) (i) Type A. AS/NZS 3000 2.6.2.2 Note 1(b) (ii) Tripping is ensured for residual sinusoidal alternating currents. Tripping is ensured for residual pulsating direct currents. AS/NZS 3000 2.6.2.2 Note 1(b)(i) (1 mark) AS/NZS 3000 2.6.2.2 Note 1(b)(ii) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 5

Question 3 Marks Reference Marking notes (d) Tripping is ensured for residual sinusoidal alternating currents. Tripping is ensured for residual pulsating direct currents. With rated residual current not exceeding 10 ma with an interrupting time not exceeding 40 ms at rated residual current. AS/NZS 3000 2.6.2.2 Note 1(c)(i) AS/NZS 3000 2.6.2.2 Note 1(c)(i) (1 mark) AS/NZS 3000 2.6.2.2 Note 1(c)(i) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 6

Question 4 Marks Reference Marking notes (a) Living Unit Calculations 5 units = 116A (given) 6 units Load Group Calculation Load (A) Group A Lighting and track 5 + (6 x 0.25) = 6.5 (1 mark) Group B Socket outlets 15 + (3.75 x 6) 37.50 (1 mark) Group C Range 6 x 2.8 16.80 Group E Instantaneous hot water 6 x 6 36.00 Group F Storage water heaters 6 x 6 36.00 Total 132.8 (1 mark) Unit load allocated across the three phases: Red White Blue 132.8 132.8 116 FINAL - IT30 ANSWERS 15 NOVEMBER 2014 7

Question 4 Marks Reference Marking notes (b) Communal Areas Three-phase Allocation of three-phase loads Load Group Calculation Load (A) Group J(i) Hot water cylinders /phase (2000 230)x 0.5 4.35 Group L Water pump /phase Name plate rating 10.8 Red White Blue 15.15 15.15 15.15 (c) Communal areas single phase loads Load Group Calculation Load (A) Group A(ii) Tennis court lighting 0 0 Group H Lighting (30 x 56) 230 7.3 Group I 9 Socket outlets 15.00 Group J(i) Clothes dryers (6000 230)x 0.5 13.05 FINAL - IT30 ANSWERS 15 NOVEMBER 2014 8

Question 4 Marks Reference Marking notes (d) Balancing the loads across the three-phases Red White Blue Living units 132.8 132.8 116 Three-phase loads Tennis court lighting Communal lighting Communal socket outlets Communal clothes driers 15.15 15.15 15.15 0 0 0 7.3 5 5 5 4.35 4.35 4.35 Totals 157.3 157.3 147.8 (1 mark) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 9

Question 5 Marks Reference Marking notes (a) (i) 25 x 1.5 = 37.5A (ii) The fuse would operate in 10,000 second or 2.78 hours (1 mark) (b) (i) The minimum current that needs to flow to enable the fuse to operate within 0.4s is 150A (1 mark) Values between 135 and 160A acceptable. (ii) Z = V I = 230 150 = 1.53Ω (1 mark) (c) To ensure the protective devices operate with 0.4s To ensure that touch voltages do not rise to dangerous levels. (d) The 20A HRC fuse operated within 0.019s with 200A flowing. It would take the 32A fuse 0.4s to operate with 200A flowing. Correct discrimination occurred because the 20A HRC fuse operated 21 times quicker than the 32A would have. (1 mark) (1 mark) (1 mark) (1 mark) (1 mark) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 10

Question 6 Marks Reference Marking notes (a) Load 1 kva = kw pf x 1000 = 9200 1 x 1000 = 9.2 kva Load 2 kva = kw pf x 1000 = 3450 0.75 x 1000 = 4.6 kva Load 3 kva = kw pf x 1000 = 2300 0.92 x 1000 = 2.5 kva kva = 9.2 + 4.6 + 2.5 = 16.3 kva (1 mark) (b) Load 1 Q = 0 (1 mark) Load 2 Q = S 2 - P 2 = 4600 2 -- 3450 = 3042.61 VAr Load 3 Q = S 2 - P 2 = 2500 2 -- 2300 2 = 979.8 VAr Q = 0 + 3042.61 + 979.8 = 4022.41 VAr (c) A 20 kva transformer (1 mark) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 11

Question 7 Marks Reference Marking notes (a) A certified design is required because it does not comply with Part 2 of AS/NZS 3000. (1 mark) GK (b) It must identify the location of the installation It must identify the standards with which the installation is intended to comply The person who prepared the design must sign and date it. ESR 58(1)(a) ESR 58(1)(b) ESR 58(1)(c) (c) Any TWO of: (2 marks) If the installation is a 2-wire or a 4- wire installation in which no conductor is earthed: * switched and circuit breakers must be fitted in all conductors used in the installation. * all poles must operate substantially together. Switches fuse links or circuit breakers must not be inserted into an earthing conductor or any earthing connection. The voltage drop must not be more than 5% under maximum load conditions between the point of supply and any socket outlet within an installation operating at standard low voltage The voltage drop must not be more than 5% under maximum load conditions between the supply terminals of any fixed wired appliance connected to an installation operating at standard low voltage. ESR 61(2) ESR 61(3) ESR 61(4) ESR 61(4) (d) The installation will comply with the regulations. The installation will be electrically safe, as required by regulation 14. (1 mark) ESR 58(2)(a) (1 mark) ESR 58(2)(b) (e) All of it GK FINAL - IT30 ANSWERS 15 NOVEMBER 2014 12

Question 7 Marks Reference Marking notes (f) The work is high-risk prescribed electrical work All high-risk prescribed electrical work is required to be inspected. (1 mark) ESR 6A(2)(a) (1 mark) ESR 70(1) (g) That the installation is safe to use on the grounds that it is electrically safe and complies with the regulations. (1 mark) ESR 74A(1) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 13

Question 8 Marks Reference Marking notes (a) Luminaire starting current 70W = 0.63A Luminaire starting current 250W = 1.9A Maximum voltage drop = 230 x 5% = 11.5V Vd for each section of cable, commencing at the switchboard mv/a.m = V d x 1000 A x m Vd = mv/a.m x A x L 1000 Vd1 = (1.9 + (4 x 0.63)) x 18.02 x 40 1000 = 3.19V Vd2 = (1.9 + (3 x 0.63)) x 18.02 x 30 1000 = 2.05V Vd3 = (1.9 + (2 x 0.63)) x 18.02 x 30 1000 = 1.71V Vd4 = (1.9 + 0.63) x 18.02 x 30 1000 1.37V Vd5 = 1.9 x 18.02 x 30 1000 = 1.03V Total Vd = 3.19 + 2.05 + 1.71 +1.37 +1.03 = 9.35V (1 mark) (b) Yes Because the 250W light will not (1 mark) start if the volt drop is more than 11.5V FINAL - IT30 ANSWERS 15 NOVEMBER 2014 14

Question 9 Marks Reference Marking notes (a) A domestic electrical installation that has a maximum demand at or below 80A per phase if single-phase A domestic electrical installation that has a maximum demand at or below 50A per phase if multi-phase (1 mark) ESR 57(2)(a) (1 mark) ESR 57(2)(b) (b) The person does not enter (whether directly, or by holding any material or equipment, or otherwise) any enclosure where live conductors are likely to be present. (1 mark) ESR 57(3)(e)(i) (c) Lighting circuit. 1 mm 2 ECP 51: Table 3 Socket outlet circuit 2.5 mm 2 ECP 51: Table 3 The permanently connected hot water cylinder 1.5 mm 2 ECP 51: Table 3 The permanently connected room heater 2.5 mm 2 ECP 51: Table 3 (d) It must have an isolating switch next to it. The isolation switch must have a minimum rating of 15A The cable and flexible cord must be three-core and include an earth wire. The wire insulation for flexible cord in the element enclosure must have a minimum temperature rating of 85 0 C ECP 51 5.4.1 ECP 51 5.4.1 ECP 51 5.4.2 ECP 51 5.4.3 (e) Minimum size of 0.75 mm 2 ECP 51: 5.3.3 Flexible cord of the sheathed, rounded type ECP 51: 5.3.3 (f) (i) A person authorised to inspect mains work. ESR 57(3)(e)(ii) (ii) AS/NZS 3000 ESR 57(3)(e)(ii) (iii) Any TWO of: (1 mark) FINAL - IT30 ANSWERS 15 NOVEMBER 2014 15

Question 9 Marks Reference Marking notes Earth continuity test AS/NZS 3000: 8.3.5 Insulation resistance test AS/NZS 3000: 8.3.6 Polarity test AS/NZS 3000: 8.3.7 Correct circuit connections test AS/NZS 3000: 8.3.8 FINAL - IT30 ANSWERS 15 NOVEMBER 2014 16