Harmonics Reduction using 4-Leg Shunt Active Power Filters

Similar documents
Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Harmonics Elimination Using Shunt Active Filter

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Power Control and Quality Management in DG Grid Interfaced Systems

Review on Shunt Active Power Filter for Three Phase Four Wire System

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

2020 P a g e. Figure.2: Line diagram of series active power filter.

Power Quality improvement of a three phase four wire system using UPQC

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Modeling of Shunt Active Filter Using P-Q Theory

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Power Quality Improvement in Fourteen Bus System using UPQC

World Journal of Engineering Research and Technology WJERT

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality Improvement using Shunt Passive Filter

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System

Application of Fuzzy Logic Controller in Shunt Active Power Filter

A Novel Control Strategy of Shunt Active Filters

COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

Literature Review for Shunt Active Power Filters

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

ISSN Vol.04,Issue.16, October-2016, Pages:

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Speed Control of Induction Motor using Space Vector Modulation

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Control of Shunt Active Power Filter for Improvement of Power Quality

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

POWER QUALITY IMPROVEMENT USING SHUNT ACTIVE FILTER

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Neural Network Controlled Hybrid Active Power Filter with Distorted Mains for PMSM Drive

Three-Level Shunt Active Filter Compensating Harmonics and Reactive Power

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Improving the Power Quality by Four Leg VSI

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Active Harmonics Filtering of Distributed AC System

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

A New Control Method for Series Active Filter in Distribution System using Unit Vector Control

ISSN Vol.03,Issue.07, August-2015, Pages:

Simulation Study of PWM Techniques for Voltage Source Converters

Single Phase Shunt Active Filter Simulation Based On P-Q Technique Using PID and Fuzzy Logic Controllers for THD Reduction

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Performance Improvement of Active Power Filter using a New Control Strategy under Unbalanced Grid Voltage

A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply

SHUNT ACTIVE POWER FILTER

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

Universal power quality conditioner

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Power Quality improvement with Shunt Active Power filter using p-q control technique

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Harmonic Analysis in Non-linear Load by using Hybrid UPQC

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Power Control Scheme of D-Statcom

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

A Time Domain Reference-Algorithm for Shunt Active Power Filters

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Transcription:

Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear devices which degrade its performance. Controlling and reducing such harmonics have been a major concern of power engineers for many years. The line current harmonics cause increase in losses, instability, and also voltage distortion. With the proliferation of the power electronics converters and increased use of magnetic, power lines have become highly polluted. Both passive and active filters have been used near harmonic producing loads or at the point of common coupling to block current harmonics. The Generalized Theory of the Instantaneous Reactive Power in Three-Phase Circuits", proposed by Akagi et al., and also known as the p-q theory, is an interesting tool to apply to the control of s, or even to analyze three-phase power systems in order to detect problems related to harmonics, reactive power and unbalance. In this project, p q theory based a new control algorithm is proposed for 3-phase 4-wire and 4-leg shunt (APF) to suppress harmonic currents, compensate reactive power and neutral line current and balance the load currents under unbalanced non-linear load and non-ideal mains voltage conditions. The APF is composed from 4-leg voltage source inverter (VSI) with a pair of DC-link capacitors and PWM current controller. All simulations are performed by using Matlab-Simulink Power System Block set. The performance of the 4-leg APF with the proposed control algorithm is found considerably effective and adequate to compensate harmonics, reactive power and neutral current and balance load currents under all non-ideal mains voltage scenarios. Simulation results obtained with MATLAB employing a three phase four wire shunt active filter test system.thd plots with and without APF is presented. Keywords Harmonics, DSTATCOM I. INTRODUCTION Due to the widespread increase of non-linear loads now a days, significant amounts of harmonic currents are being injected into power system [1]. Harmonic currents flow through the power system, causing voltage distortion at the harmonic current s frequencies. The distorted voltage waveform causes harmonic currents to be drawn by other loads connected at the point of common coupling (PCC) [2-4]. The existence of current and voltage harmonics in power system increase losses in the lines decrease the power factor and can cause timing errors in sensitive electronic equipments. The harmonic currents and voltages produced by balanced 3-phase non-linear loads such as motor drivers, silicon controlled rectifiers (SCR), large uninterrupted power supplies (UPS) are positivesequence harmonics (7th, 13th, etc.) and negativesequence harmonics (5th, 11th, etc.). However, harmonic currents and voltages produced by single phase non-linear loads such as switched mode power supplies(smps) in computer equipment which are connected phase to neutral in a 3-phase 4-wire system are third order zero-sequence harmonics (triplen harmonics-3rd, 9th, 15th, 21st, etc.) [5]. these triplen harmonic currents unlike positive and negativesequence harmonic currents do not cancel but add up arithmetically at the neutral bus. This can result in neutral current that can reach magnitudes as high as 1.73 times the phase current. In addition to causing damage of cables and transformers overheating the third harmonic can reduce energy efficiency. The traditional method of current harmonics reduction involves passive LC filters, which are known for its simplicity and low cost. However, passive filters have several drawbacks such as large size, tuning and risk of resonance problems. On the contrary, the 4-leg APF can solve problems of current harmonics [6-8], reactive power, load current balancing and excessive neutral current simultaneously, and can be a much better solution than conventional approach. The Generalized Theory of the Instantaneous Reactive Power in Three-Phase Circuits", proposed by Akagi et al., and also known as the p-q theory has been used very successfully to design and control of the APF for 3-phase systems. This theory was extended by Aredes et al. for applications in 3-phase 4-wire systems. The IRP theory was mostly applied to calculate the compensating currents [9-10]. The control strategy for a shunt generates the reference current, that must be provided by the power filter to compensate reactive power and harmonic currents demanded by the load [11]. This involves a set of currents in the phase domain, which will be tracked generating the switching signals applied to the electronic converter by means of the appropriate closed-loop switching control technique. ISSN: 2348 8379 www.internationaljournalssrg.org Page 20

II. MODELLING OF 4 LEG SHUNT ACTIVE POWER According to EPRI (Electrical power research institute), 70% of the loads are non-linear loads which are injecting harmonics into the power system. These harmonics cause detrimental effects on power quality. To mitigate these harmonics many topologies have been introduced. The traditional method of current harmonics reduction involves passive LC filters, which are its simplicity and low cost. However, passive filters have several drawbacks such as large size, tuning and risk of resonance problems. On the contrary, the 4-leg APF can solve problems of current harmonics, reactive power, load current balancing and excessive neutral current simultaneously, and can be a much better solution than conventional approach. Here we have implemented shunt by considering a three phase four wire distribution system. Developed a model considering a 415v, 3-phase 4- wire distribution system with tapped linear as well as non- linear loads, created a situation such that the linear load switch alternatively for every 0.1 sec which creates unbalance and transients in the system. The below figure shows the Matlab/Simulink based model of the considered system. Fig. 2.2.Sub system-six pulse diode based converter with R-L load Non-linear load parameters Voltage=415v Active power=50kw Reactive power=3kvar Frequency=50Hz 2.4 ACTIVE POWER A three- phase four-wire split phase four leg shunt is modelled based on Instantaneous Reactive Power Theory (pq-theory) as shown below. Fig. 2.1 3-phase 4-wire simulink model with 4- leg shunt The system model comprises of three main parts. Linear load Non- linear load(diode bridge) 4-Leg Active Power Filter 2.1 LINEAR LOAD A three phase RL load is considered whose switching is achieved by connecting circuit breaker (CB) which switches for every 0.1 sec. Initially the breaker is closed. The switching of circuit breaker causes unbalance and transients in the system. Linear load Parameters Voltage=415v Active power =100 KW Reactive power=10 KVAR Frequency=50 Hz 2.3 NON-LINEAR LOAD Here a six-pulse diode bridge is connected to RL load as shown below. A star neutral-star connected transformer used to enable the neutral connection. Here the non-linear load is always connected to the circuit. Fig.2.3. Subsystem IGBT Inverter with pq controller It consists of IGBT inverter bridge DC operating circuit based pulse generator Current tracking and PWM circuit. 2.5 IGBT INVERTER BRIDGE It is a four leg inverter bridge as shown below. The fourth leg is connected to neutral of the system. A pair of capacitors (split phase) are provided to input the dc voltage. Firing pulses are generated by considering pq theory. To limit the filter current use series impedance. Fig.2.4 3-phase 4-leg IGBT Inverter Parameters C 1 =C 2 =2200µF R a =R b =R c =3Ω ISSN: 2348 8379 www.internationaljournalssrg.org Page 21

L a =L b =L c =30mH Neutral impedance: R n =2 Ω, L n =100mH III. SIMULATION RESULTS The simulation results are obtained through Power system tool boxes in SIMULINK by taking system parameters as mentioned in the previous chapter. The simulation and test results without and with shunt configuration is presented here. 3.1 RESULTS WITHOUT The current waveforms of source, non-linear load, linear load and Total Harmonic Distortion (THD) of source voltage and source current without filter is shown below Fig.2.1 Source voltage waveform (without filter) Due to the presence of non-linear load and due to switching action of linear load for every 0.1 sec. observed harmonics in supply voltage. Fig.2.5 Linear load current waveform (without filter) Linear load switches for every 0.1 sec. During this period load current flows. For 0.1sec to 0.2 sec. linear load is switched off, thereby creating unbalance in the system. Variation of source current and Non-linear load current due to switching of the linear load is shown in Fig 2.4 and Fig 2.5 respectively. From the above figure it is observed that due to the presence of nonlinear load and switching of the linear load the source current waveform is distorted and is not in sinusoidal form. 3.2 TOTAL HARMONIC DISTORTION WITHOUT The THD in the source current without filter is obtained using FFT analysis tool box in Matlab Fig.2.2 Source current waveform without shunt In the system considered non-linear load always exists in the system and linear load switches for every 0.1 sec. Due to the switching action source current is abruptly high for 0.1sec when both linear and non linear loads are present. For 0.1 sec. to 0.2 sec. when only non linear load is present source current is reduced greatly. Switching action even though causes unbalance in the system. Fig.2.6 THD of source voltage Fig.2.3 Load voltage waveform without filter Fig.2.7 THD of source current 3.3 RESULTS WITH SHUNT ACTIVE POWER Fig.2.4 Non-linear load current waveform (without filter) Non-linear load current causes unbalance in the system.the THD of the nonlinear load current is 19.9%. Fig.3.1 Source voltage waveform with shunt active power filter ISSN: 2348 8379 www.internationaljournalssrg.org Page 22

Due to the presence of non-linear load and due to switching action of linear load for every 0.1 sec. Observed harmonics in supply voltage Fig.3.2 Source current waveform with shunt In the system considered non-linear load always exists in the system and linear load switches for every 0.1 sec. Due to the switching action source current is abruptly high for 0.1sec when both linear and non linear loads are present. For 0.1 sec. to 0.2 sec. when only non linear load is present source current is reduced greatly. Switching action even though causes unbalance in the system due to filter THD is still maintained to 1.57% The type of filter here used is band reject filter which rejects 50Hz supply and rest of the harmonics are passed through. The filter injects corresponding current in the system with 180 degrees phase shift to harmonics there by eliminating the harmonics from source current. The split phase capacitor voltage waveforms are shown below Fig. 3.7 Capacitor-1 voltage wave form Fig. 3.3 Load voltage waveform with shunt Fig. 3.4 Linear load current waveform with shunt Linear load switches for every 0.1 sec. During this period load current flows. For 0.1sec to 0.2 sec. linear load is switched off, thereby creating unbalance in the system. Fig. 3.8 Capacitor-2 voltage waveform 3.4 TOTAL HARMONIC DISTORTION WITH Fig. 3.5 Non-linear load current waveform with shunt The non linear load current causes unbalance in the system.the THD of the nonlinear load current is 19.9%. Though non-linear load injects harmonics in the system still source parameters are within limits due to the presence of shunt. Fig. 3.9 THD of source voltage Fig. 3.6 Active filter current waveform Fig. 3.10 THD of source current ISSN: 2348 8379 www.internationaljournalssrg.org Page 23

PAR AME TERS Sourc e volta ge Sourc e curre nt THD% WITHOUT B A C A THD% WITH B C 0.08 0.08 0.07 0.03 0.03 0.02 9.76 9.92 10.2 0 1.83 1.94 2.54 Table 3.1 Comparison table of %THD without and with filter IV. CONCLUSIONS A generic 3-phase 4-wire distribution system was considered. 4-leg Shunt is implemented in order to provide acceptable THD. THD of source voltage waveform has been reduced from 0.076% to 0.025%, THD of source current waveform has been reduced from 9.96% to 1.85% Dr K.Srinivas received B.E. degree in Electrical and Electronics Engineering from Chithanya Bharathi Institutue of Technology and Science, Hyderabad, Osmania University, Hyderabad, India, in 2002, M.Tech. Degree in power systems and Power Electronics from the Indian Institute of Technology Madras, Chennai, in 2005, Ph. D from Jawaharlal Nehru Technological University Hyderabad. Currently, he is an Assistant Professor in Electrical and Electronics Engineering Department, Jawaharlal Nehru Technological University Hyderabad College of Engineering Jagitial. His fields of interest include power quality, power Electronics control of power systems. REFERENCES [1] H. Akagi, Y. Kanazawa, A. Nabae, Generalized Theory of the Instantaneous Reactive Power in Three- Phase Circuits, IPEC'83 - Int. Power Electronics Conf., Tokyo, Japan, 1983, pp. 1375-1386. [2] H. Akagi Y. Kanazawa, A. Nabae, Instantaneous Reactive Power Compensator Comprising Switching Devices without Energy Storage Components, IEEE Trans. Industry Applic., vol. 20, May/June 1984. [3] E. H. Watanabe, R. M. Stephan, M. Aredes, New Concepts of Instantaneous Active and Reactive Powers in Electrical Systems with Generic Loads, IEEE Trans. Power Delivery, vol. 8, no. 2, April 1993, pp. 697-703. [4] M. Aredes, E. H. Watanabe, New Control Algorithms for Series and Shunt Three-Phase Four- Wire Active Power Filters, IEEE Trans. Power Delivery, vol 10, no. 3, July 1995, pp. 1649-1656. [5] J. L. Afonso, C. Couto, J. S. Martins, Active Filters with Control Based on the p-q Theory, IEEE Industrial Electronics Society Newsletter, vol. 47, nº 3, Set. 2000, pp. 5-10. [6] J. L. Afonso, H. R. Silva, J. S. Martins, Active Filters for Power Quality Improvement, IEEE Power Tech 2001, Porto, Portugal, 10-13 Set. 2001. [7] [7] Simulink Model-Based and System-Based Design, Modelling, Simulation, Implementation, version 5, The MathWorks, July 2002. [8] M. Peterson and B. N. Singh, Active and passive filtering for harmonic compensation, IEEE Conference 40th southeastern symposium on system theory, USA, pp. 188-192,March 2008 [9] Roger C. Dugan, Mark F. McGranaghan, H. Wayne Beaty: Electrical Power Systems quality. New York: McGraw Hill, c1996 [10] IEEE STD 1531-2003, IEEE Guide for Application and Specification of Harmonic Filters. [11] J. Arrillaga, R. W. Neville, Power System Harmonics, 2nd Edition, 2003, John Wiley & Sons.J. Breckling, Ed., The Analysis of Directional Time Series: Applications to Wind Speed and Direction, ser. Lecture Notes in Statistics. Berlin, Germany: Springer, 1989, vol. 61. ISSN: 2348 8379 www.internationaljournalssrg.org Page 24