Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

Similar documents
MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Protection from Voltage Sags and Swells by Using FACTS Controller

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

ISSN Vol.07,Issue.21, December-2015, Pages:

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Voltage Sag and Swell compensation using DVR to enhance Power Quality

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Design and Simulation of Dynamic Voltage Restorer (DVR) Using Sinusoidal Pulse Width Modulation (SPWM)

Mitigation of voltage sags/swells unbalanced in low voltage distribution systems

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Multi level DVR with Energy Storage System for Power Quality Improvement

Simulation of a Dynamic Voltage Restorer to Compensate Voltage Sag for Improving Power Quality

DYNAMIC VOLTAGE RESTORER (DVR) FOR VOLTAGE SAG COMPENSATION WITH FUZZY LOGIC CONTROLLER. Chennai, Tamilnadu, India. Chennai, Tamilnadu, India.

Comparative Analysis of Grid Power Quality using DVR, DSTATcom, Open UPQC and SVC Light In Grid Wind Energy System

Investigation of Dynamic Voltage Restorer for Compensation of Voltage Sag and Swell

MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Self-Tuning PI Control of Dynamic Voltage Restorer Using Fuzzy Logic

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Power Quality Improvement using Hysteresis Voltage Control of DVR

II. RESEARCH METHODOLOGY

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT

SIMULATION OF D-STATCOM IN POWER SYSTEM

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTURBANCES

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

International Journal of Advance Engineering and Research Development CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

A Power Control Scheme for UPQC for Power Quality Improvement

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Compensation of Balanced and Unbalanced voltage disturbance using SRF controlled DVR

ISSN: [Singh* et al., 6(6): June, 2017] Impact Factor: 4.116

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

Improvement of Dynamic Voltage Restorer (DVR) Using Proportional Integral (PI)Controller for Mitigation of Voltage Sag

Simulation of Dynamic Voltage Restorer Using Matlab to Enhance Power Quality in Distribution System

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Voltage Improvement Using SHUNT FACTs Devices: STATCOM

Voltage Sag/ Voltage Swell Compensation and Reduction Harmonic Distortion using Dynamic Voltage Restorer

Modelling And Analysis of DVR With SEPIC Converter And Supercapacitor

Performance of DVR under various Fault conditions in Electrical Distribution System

Mitigation of Voltage Complication by a Novel Control Algorithm Based Dynamic Voltage Restorer

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

ISSN Vol.03,Issue.11, December-2015, Pages:

Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Simulation and Implementation of DVR for Voltage Sag Compensation

Voltage Sag Matigation in Distribution Network by Dynamic Voltage Restorer

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

New Topology of a Three Phase Dynamic Voltage Restorer (DVR) for Voltage Swells Mitigation in Electrical Distribution System

Volume I Issue VI 2012 September-2012 ISSN

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Improvement of Power Quality Using a Hybrid Interline UPQC

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Voltage Correction Methods in Distribution System Using DVR

Performance of DVR & Distribution STATCOM in Power Systems

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Compensation of Different Types of Voltage Sags in Low Voltage Distribution System Using Dynamic Voltage Restorer

Power Quality enhancement of a distribution line with DSTATCOM

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)

CHAPTER 6 MITIGATION OF VOLTAGE SAG, SWELL AND SINGLE PHASE OUTAGE USING MULTI WINDING TRANSFORMER

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

DYNAMIC VOLTAGE RESTORER USING THREE PHASE AC-AC CONVERTER

Voltage Sag Mitigation of DVR using Matlab Simulation

ISSN: ; e-issn

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Design Requirements for a Dynamic Series Compensator for Voltage Sags Mitigation in Low Voltage Distribution System

Power Quality Improvement in Distribution System Using D-STATCOM

Reduce the Harmonics Distortion of Sensitive Load against the Induction Motor Drive Non-Linear Load

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

SIMULATION VERIFICATION OF DYNAMIC VOLTAGE RESTORER USING HYSTERESIS BAND VOLTAGE CONTROL

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

p. 1 p. 6 p. 22 p. 46 p. 58

ITEE Journal. Information Technology & Electrical Engineering International Journal of Information Technology and Electrical Engineering

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Design of DVR against Voltage Sags & Swell Using Matrix Converter

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Design and Development of DVR model Using Fuzzy Logic Controller for Voltage Sag Mitigation

Transcription:

International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 8 (2011), pp. 889-898 International Research Publication House http://www.irphouse.com Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation Anmol and Parag Nijhawan Dept. Electrical and Inst. Engg., Thapar University, Patiala, Punjab, India E-mail: anmol173@gmail.com, parag.nijhawan@rediffmail.com Abstract Dynamic voltage restorer has been considered the very effective solution for the mitigation of voltage sags and swells in the distribution network. DVR has other added features such as harmonics and power factor correction capability due to which it has gained a widespread importance. In this paper, the effectiveness of dynamic voltage restorer for voltage balancing is presented. The dqo based control algorithm is considered. The system is connected to the adjustable speed drive load. The MATLAB/Simulink demonstrates the validity and superiority of proposed control strategy during various voltage unbalancing conditions on low voltage distribution system. Index Terms: Adjustable speed drive (ASD), custom power, dynamic voltage restorer (DVR), power quality. Introduction Power quality is an issue that is becoming increasingly important to electricity consumers at all levels of usage [1, 4]. With the increasing developments in power electronics and the modern microprocessor based loads, the need of quality in power is felt. Several steps have been taken to compensate for the fluctuations observed on the distribution networks in order to ensure highest possible power quality for the customers. Power quality problem: Any power problem manifested in voltage, current, or frequency deviations that result in the failure or misoperation of customer equipment [2]. Power quality problems are associated with power systems with broad ranges of time frames such as long duration variations, short duration variations and other disturbances.

890 Anmol and Parag Nijhawan Fig. 1 describes the demarcation of the various power quality issues defined by IEEE Std. 1159-1995[3]. Figure 1: Definitions of events by IEEE Std.l159-1995. Voltage sags can occur at any instant of time, with amplitudes ranging from 10 90% and a duration lasting for half a cycle to one minute [5]. Voltage swells are not as important as voltage sags because they are less common in distribution systems. There are many different methods to mitigate voltage quality problems like voltage sags, swells or unbalancing in the line but the use of a custom Power device is considered to be the most efficient. Each of custom power devices has its own advantages and limitations. Dynamic Voltage Restorer is one of the most effective device for mitigation of voltage unbalancing problems. There are numerous reasons why the DVR is preferred over the others. A few of these reasons are presented as follows. The DVR is preferred over SVC because the SVC has no ability to control active power flow [6]. Another reason is that the DVR is less costly and requires low maintenance as compared to the UPS. Also it has higher energy capacity and lower costs as compared to the SMES device. Furthermore, the DVR is smaller in size and costs less when compared to the DSTATCOM. Based on these reasons, the DVR is considered as an effective custom power device. DVR has other added features such as harmonics reduction and Power Factor correction capability. Compared to the other devices, the DVR clearly provides the best economic solution for its size and capabilities. This paper, introduces DVR, its operating principles and structures. Meanwhile the application of DVR in power system network for balancing the voltage of three phase supply system with ASD as load is proposed. Dynamic Voltage Restorer Dynamic voltage restorer is a series connected power-electronic converter-based device with the distribution feeder to protect critical loads from all supply-side

Application of Dynamic Voltage Restorer 891 disturbances other than outages. It can provide the most cost effective solution to mitigate voltage imbalance by establishing the proper voltage quality level that is required by customer. When a fault happens in a distribution network, sudden voltage sag will appear on adjacent loads. DVR installed on a sensitive load, restores the line voltage to its nominal value within the response time of a few milliseconds thus avoiding any power disruption to the load. The DVR works independently of the type of fault or any event that happens in the system, provided that the whole system remains connected to the supply grid. The DVR has two modes of operation which are: standby mode and boost mode. In standby mode (V DVR =0), the booster transformer s low voltage winding is shorted through the converter. No switching of semiconductors occurs in this mode of operation. The DVR will be most of the time in this mode. In boost mode (V DVR >0), the DVR is injecting a compensation voltage through the booster transformer due to a detection of a supply voltage disturbance The general configuration of the DVR consists of an Injection / Booster transformer, a Harmonic filter, a Voltage Source Converter (VSC), and a Control and Protection system as shown in fig 2. Figure 2: DVR series topology. The Injection / Booster transformer The Injection / Booster transformer is a specially designed transformer that attempts to limit the coupling of noise and transient energy from the primary side to the secondary side [7]. It connects the DVR to the distribution network via the HVwindings and transformers and couples the injected compensating voltages generated by the voltage source converters to the incoming supply voltage. In addition, the Injection / Booster transformer serves the purpose of isolating the load from the system. Harmonic Filters The main task of harmonic filter is to keep the harmonic voltage content generated by

892 Anmol and Parag Nijhawan the inverter within tolerable limits. These filters are placed at the high voltage side to avoid introductions in phase angle shift, which can disrupt the control algorithm [8]. Voltage Source Converter A VSC is a power electronic system consisting of a storage device and switching devices, which can generate a sinusoidal voltage at any required frequency, magnitude, and phase angle. In the DVR application, the VSC is used to temporarily replace the supply voltage or to generate the part of the supply voltage which is missing. Control and Protection System The control mechanism of the general configuration typically consists of Digital Signal Processing (DSP) boards. The software on the DSP board provides the controls such as detection and correction. Filters are commonly used for these purposes [9]. Principle of Operation The basic principle of a DVR is inserting a voltage of required magnitude and frequency so that the load-side voltage to the desired amplitude and waveform can be restored. Usually a DVR is connected to protect sensitive loads during faults in the supply system [11]. Fig. 3 [10] shows the equivalent circuit of the DVR. When the source voltage is drops or increases; the DVR injects a series voltage V inj through the injection transformer so that the desired load voltage magnitude V L can be maintained. Figure 3: Equivalent circuit of DVR. The series injected voltage V inj of the DVR can be written as V inj = V L + V s (1) Where V L is the desired load voltage magnitude V s is the source voltage during sags/swells condition

Application of Dynamic Voltage Restorer 893 The load current I L is given by, I L = (( P L ± J*Q L ) / V L ) (2) Proposed Method Main Circuit Fig. 4 shows the configuration of the proposed DVR design using MATLAB/SIMULINK, where the outputs of a three-phase half-bridge inverter are connected to the utility supply via wye-open connected series transformer. With the occurrence of voltage disturbance, the inverter output can be steered in phase with the incoming ac source while the load is maintained constant with the aid of dqo transformation based control scheme. The output of inverter is installed with capacitors and inductors for the filtering scheme. To evaluate the DVR and its operation in different situations, a system including a DVR, which is connected to the network, has been simulated in MATLAB/SIMULINK. Figure 4: Proposed system configuration. Control Algorithm The dqo transformation or Park s transformation is used to control of DVR. The dqo method expresses the voltage error and phase shift information as instantaneous space vectors with start and end times. The voltage is converted from abc reference frame to d-q-o reference. For simplicity, zero phase sequence components is ignored. The detection of error in voltage is carried out in each of the three phases. The control scheme for the proposed system is based on the comparison of a reference voltage and the measured terminal voltage (V a, V b, V c ). The error signal allows generation of a commutation pattern by means of the sinusoidal pulse width modulation technique (SPWM) [10].

894 Anmol and Parag Nijhawan The injection voltage is generated by difference between the reference load voltage and supply voltage and is applied to the VSC to produce the preferred voltage, with the help of pulse width modulation (PWM). Fig 5 shows the basic control scheme and parameters that are measured for control purposes. The control algorithm produces a three phase reference voltage to the series converter that tries to maintain the load voltage at its reference value. The d-reference component is set to a rated voltage and the q-reference components are set to zero [11]. Figure 5: Control structure of DVR [11]. Equation (3) defines the transformation from three phase system a, b, c to dqo stationary frame. The theta (θ) is defined by the angle between phase A to the d-axis phase. A is aligned to the d-axis that is in quadrature with the q-axis. = Cosθ Cosθ 1 Sinθ Sinθ 1 (3) Simulation and Results Analysis of the influence of induction motor loads on the mitigation ability of the DVR has been performed by simulation studies using MATLAB/SIMULINK. The system parameters and constant values and adjustable speed drive parameters are listed in Table I and Table II respectively. It is assumed that the voltage magnitude of the load bus is maintained at 1 pu during the period of unbalanced voltage.

Application of Dynamic Voltage Restorer 895 Table I: system parameters and constant values System Parameters Main Supply Voltage Per Phase 200 V Line Impedance Ls = 0.5 mh Rs = 0.1 Ω Series Transformer Turns Ratio 1:1 Dc Bus Voltage 300 V Filter Inductance 1mH Filter Capacitance 1μF Line Frequency 50 Hz Load Resistance 40 Ω Load Inductance 60mH Carrier Frequency of PWM 1080 Hz Table II: Field-Oriented Control Induction Motor Drive Parameters Referred To Rotor. Motor Parameters Rated Power 2238VA Rated Voltage 440Vrms Frequency 50Hz Combined Rotor and Load Inertia 0.089 kg.m 2 Stator Resistance 0.435 Ω Stator Reactance 2 mh Rotor Resistance 0.816 Ω Rotor Reactance 2 mh Magnetizing Inductance 69.31mH Pair of Poles 2 Shaft Mechanical Torque 2Nm The results of the simulation conducted in MATLAB considering different conditions are represented in this paper. In first case, the supply voltage of one phase is increased by 12.5%. The DVR compensates the voltage and thus balanced voltage is available at load. The results of simulation are as shown in fig 6. The comparison of FFT analysis depicts the vast improvement in total harmonic distortion on the load side of the system which is connected to DVR.

896 Anmol and Parag Nijhawan Figure 6: (a) Source voltage (pu) (b) Voltage at load (c) Percentage of total harmonic distortion on the load without DVR (d) Percentage of total harmonic distortion on the load with DVR In second case, the source resistance of line impedance is altered from 0.1Ω to 0.001Ω. The results are as shown in fig 7. The voltage at load is regained and considerable improvement of total harmonic distortion is seen.

Application of Dynamic Voltage Restorer 897 Figure 7: (a) Source voltage (b) Load voltage (pu) (c) percentage of total harmonic distortion on the load without DVR (d) ) percentage of total harmonic distortion on the load with DVR The third case represents the single line to ground fault in the system which is effectively balanced by DVR at the load side by recovering the missing cycles shown in the waveform in fig 8. This case also represents the problem of single-phasing commonly encountered in power system network. The comparison of FFT analysis of the voltage waveform at the load side of the system with and without DVR depicts enormous improvement in the total harmonic distortion. Figure 8: (a) Source voltage (b) Load voltage (pu) (c) percentage of total harmonic distortion on the load without DVR (d) percentage of total harmonic distortion on the load with DVR

898 Anmol and Parag Nijhawan Conclusion The modeling and simulation of a DVR using MATLAB/SIMULINK has been presented. This paper proposed a low voltage dynamic voltage restorer connected to adjustable speed drive load. The dqo control algorithm which is a scaled error of the between source side of the DVR and its reference was implemented to restore the missing cycles of voltage. The proposed method can compensate for most of the voltage faults such as harmonics and any kind of voltage unbalance on the supply networks. References [1] Pierre Giroux, Gilbert Sybille, Hoang Le-Huy Modeling and Simulation of a Distribution STATCOM using Simulink s Power System Blockset, IECON; 01: the 27th Annual Conference of the IEEE Industrial Electronics Society, pp. 990-994. [2] Thomas E. Grebe, Application of Distribution System Capacitor Banks And Their Impact On Power Quality, IEEE Transactions On Industry Applications, vol. 32, no. 3, May/June 1996, pp 714-719. [3] Toshifiimi Ise, Yusuke Hayashi, and Kiichiro Tsuji, "Definitions of power quality levels and the simplest approach for unbundled power quality services," IEEE Proc. in the Ninth International Conference on Harmonics and Quality of Power, Orlando, FL, vol. 2, oct. 2000, pp. 385-390. [4] C. Sankaran, Power Quality, CRC Press LLC, 2002. [5] M.Arun Bhaskar, Dr.S.S.Dash, C.Subramani, M.Jagdeesh Kumar, P.R.Giresh and M.Varun Kumar, Voltage Quality Improvement Using DVR, IEEE International Conference on Recent Trends in Information, Telecommunication and Computing, 2010, pp378-380. [6] Chellali Benachaiba, Brahim Ferdi, Voltage Quality Improvement Using DVR, Electrical Power Quality and Utilisation, journal no. 1, vol. XIV, 2008, pp39-46. [7] Hyosung Kim, Jang-Hwan Kim, Seung-Ki Sul, A Design Consideration Of Output Filters For Dynamic Voltage Restorers, 35th Annual IEEE Power Electronics Specialists Conference, 2004, pp 4268-4272. [8] K.Chandrasekaran, P.A.Venkatachalam, Mohd Noh Karsiti, Dynamic Voltage Restorer As A Sag Mitigator And Harmonic Restorer, IEEE International Conference on Sustainable Energy Technologies, 2008, pp 904-909. [9] Mahesh Singh, Vaibhav Tiwari, Modeling analysis and solution of Power Quality Problems, Available: http://eeeic.org/proc/papers/50.pdf. [10] Rosli Omar And Nasrudin Abd Rahim, Modeling and Simulation for Voltage Sags/Swells Mitigation Using Dynamic Voltage Restorer (DVR), IEEE Australasian Universities Power Engineering Conference, 2008, Paper P-027. [11] Arindam Ghosh, and Gerard Ledwich, Compensation of Distribution System Voltage Using DVR, IEEE Transactions On Power Delivery, vol. 17, no. 4, October 2002, pp.1030-1036.