O M P O N E N T S High-Speed D ircuit-reakers for Fixed Installation Type UR26, UR36, UR40 & UR46
The UR26, UR36, UR40 & UR46 are D high-speed current limiting air ircuit-reakers, trip free, single pole, bi-directional, with electromagnetic blow-out, electric control circuits and direct over-current instantaneous release. Their simple design and high insulation level combined with its compliance to both standards EN50123/IE61992 for fixed installations and EN/IE60077 for rolling stock, guarantee to the UR26, UR36, UR40 & UR46 range a very high reliability and an exceptionally long life time. With its proven worldwide experience and acceptance, Sécheron's circuit-breaker offers you the key product for such a strategic and critical application that is to guarantee the highest safety to your equipment as well as to the people operating it and using it. pplications Line circuit-breaker type* H/L//O for D traction power substations Interconnecting circuit-breaker type* H/I//O for D traction power substations Rectifier circuit-breaker type* H/R,lr,r//O for D traction power substation * Type designation according to standards EN50123-2 / IE61992-2 Main features onventional thermal current 2600 (UR26), 3600 (UR36), 4000 (UR40) and 4600 (UR46) Rated operational voltage 900 Vdc, 1800 Vdc, and also 3600 Vdc High rated insulation voltage up to 2300 Vdc or 4800 Vdc Safe with a high insulation level: Over-Voltage category OV4 Pollution degree PD3 Limited maximum arc voltage High rated short-circuit making and breaking capacity Electro-magnetic closing with electric holding or magnetic latch Five double contacts auxiliary switches Low voltage connector for auxiliary contacts and control coil Operational frequency 3 Very low maintenance requirements Proven design with worldwide experience and acceptance Insulation material according to relevant S, NF, STM, IE and DIN standards Designed and tested according to EN50123-1/2, IE61992-1/2 standards large number of different options to match the various applications requirements reaking current parameters Track line supplied by a rectifier d: duty d - distant fault e: duty e - maximum energy f: duty f - maximum fault current reaking current parameters Îss>1.42Iss I t c f e d Typical duty f haracteristics of the duties d, e and f t c /T Nc 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 d >63 31.5 T Nc [ms] 16 0 0.4 0.6 0.8 1 2I Ne /I Nss e f I ss /I Nss Iss 0.63 Iss Icut off Id V Ûarc UNe t l di/dt Typical duty e and d t t Iss Îss INss Id Icut off Ûarc UNe di/dt tc tl TNc = Prospective sustained short-circuit current = Peak of Iss = Rated short-circuit current of the circuit-breaker = Setting of maximum current release = ut off current = Maximum arc voltage = Rated operational voltage = Initial current rate of rise = Time-constant of the circuit = Opening time = Rated track time constant of the circuit-breaker 2
Opening time t l t l Relationship between opening time tl and the initial rate of rise of current di/dt for direct instantaneous over-current release. Example for an initial rate of rise of current of 3.10 6 /s: the opening time is about 3.5 ms for UR26 and about 4.7 ms for UR36 and UR40. Remark: for a shorter opening time the indirect release option can be used (refer to option section). Designation code (standard version) e sure to establish the designation code from our latest version of the brochure by downloading it from our website www.secheron.com. e careful to write down 21 digits for the type designation code when placing your order. The bold part of this designation code defines the device type and the complete designation defines the identification number of the product, as they are displayed on the identification plate attached to the product. The customer shall write down the setting value Ids in its order form. It can happen that for technical reasons, some configurations of variants and options indicated in the designation code cannot be combined. Type designation UR 36 81 S L 1 E 0 0 0 0 0 0 0 Description Designation ode reaker type UR UR onventional free-air thermal current 2600 26 3600 36 4000 40 4600 46 Rated operational voltage 900 V 81 1800 V 82 (Only for UR26-36-40) 3600 V 64 pplication Traction substation (according to EN 50123-1/2) S Use Line breaker L rc chute installation Opening of arc chute 81/82 on LV connector side 1 Type S- for arc chute 64 5 Nominal control voltage 24 Vdc 36 Vdc 48 Vdc 72 Vdc D 110 Vdc E Holding type Electric E Varistor on coil No 0 Direct over-current release (UR26 only) 1.4-2.7 k 2.0-5.0 k Indirect release No 0 uxiliary contacts 5a+5b LV connector type on circuit-breaker Veam type 22 pins Manual release No 0 Manual closing device No 0 Position Indicator No 0 Overcurrent release detector No 0 ontact wear indicator No 0 3
Main dimensions UR26/36-81/82 UR40/46-81/82 UR26/36/40/46-81/82 View without coolers 617 (82) 238 419 (81) 168 69 51 R490 60 160 240 UR26/36-64 420 320 40 90 90 4x Ø11 380 (UR40) 376 (UR46) UR40-64 23 194 319.5 UR26/36/40-64 View without coolers 700 140,5 D 95 100 D 95 100 E 371 386 1025 784 4x Ø11 E 160 40 380 60 240 194 319.5 Dimensions [mm] UR26 UR36 UR40 UR46 645 760 760 760 131.5 246.5 246.5 246.5 131.5 176.5 176.5 176.5 D 20 30 30 40 E 176 176 176 177 4
ircuit breakers weight [kg] UR26 UR36 UR40 UR46 with arc chute 81 77 94 98 110 with arc chute 82 87 104 108 120 with arc chute 64 133 150 154 - UR 26 UR 40 UR 36 UR 46 Insulating distances Minimum insulating distances [mm] (1) UR..81TD UR..82TD UR..64TD To insulating wall 25 25 25 95 95 200 (2) 750 750 875 To earth 200 200 240 300 300 280 (2) 750 750 1500 (1) t maximum short-circuit breaking capacity. For smaller short-circuit values, smaller distances can be used. (2) Grid with 50% of surface opening. UR..81/82 UR..64 238 238 617 (82) 419 (81) 240 700 632 376 5
Technical data MIN IRUIT Symbol Unit UR26 UR36 UR40 UR46 Rated voltage UNe [Vdc] - arc chute type 81 900 900 900 900 - arc chute type 82 1800 1800 1800 1800 - arc chute type 64 3600 3600 3600 - Maximal operational voltage [Vdc] - arc chute type 81 1000 1000 1000 1000 - arc chute type 82 2000 2000 2000 2000 - arc chute type 64 4000 4000 4000 - Rated insulation voltage - arc chute type 81 UNm [Vdc] 3000 3000 3000 3000 - arc chute type 82 3000 3000 3000 3000 - arc chute type 64 4800 4800 4800 - Rated impulse withstand voltage - arc chute type 81 UNi [kvdc] 20 20 20 20 - arc chute type 82 20 20 20 20 - arc chute type 64 40 40 40 - onventional free air thermal current (Tamb=+40 ) Ith [] - acc to EN50123-2 / IE61992-2 2600 3600 4000 4600 - acc. to NSI 37.14-2002 2150 2900 3200 3600 - acc. to IE60947 2600 3600 4000 4600 Rated service current INe [] 2600 3600 4000 4600 Rated short-circuit making & breaking capacity INSS/TNc - at UNe 900 Vdc (arc chute type 81) [k]/[ms] 125/100 125/100 125/100 125/100 - at UNe 1800 Vdc (arc chute type 82) [k]/[ms] 80/31.5 80/31.5 80 /31.5 80/31.5 - at UNe 3600 Vdc (arc chute type 64) [k]/[ms] 40/31.5 40/31.5 40/31.5 - Direct over-current instantaneous release [k] 1.4-2.7 2.0-8.0 2.0-8.0 2.0-8.0 [k] 2.0-8.0 4.0-15.0 4.0-15.0 4.0-15.0 Power frequency withstand voltage (50 Hz, 1 min): - arc chute type 81 Ua [kv] 12 12 12 12 - arc chute type 82 12 12 12 12 - arc chute type 64 18.5 18.5 18.5 - Maximum arc voltage - arc chute type 81 Ûarc [V] 2500 2500 2500 2500 - arc chute type 82 4000 4000 4000 4000 - arc chute type 64 8000 8000 8000 - ONTROL IRUIT Nominal voltage Un [Vdc] 24, 36, 48, 72, 96, 110, 220 Nominal closing power (Tamb=+20 ) [W]/[s] 1300/1 Nominal holding power for electric holding (Tamb=+20 ) [W] 2.3 Nominal holding power for magnetic holding (Tamb=+20 ) [W] 0 Nominal opening power for magnetic holding (Tamb=+20 ) [W]/[s] 25/1 Mechanical opening time* at Un and Tamb=+20 to [ms] 15 to 30 Mechanical closing time* at Un and Tamb=+20 tc [ms] ~ 150 * Starting when the signal is received by the coil UXILIRY ONTTS IRUIT Number of contacts 5a (NO)+5b (N) Rated voltage (potential free contacts) [Vdc] 24 to 110 Rated current [] 10 Maximum breaking current - Ohmic load at 110 Vdc [] 1 - Inductive load τ = 15 ms at 110 Vdc [] 0.3 Minimum let-through current at 24 Vdc (1) [m] 10 (silver contacts - standard) [m] 4 (gold contacts - option) (1) For a dry and clean environment 6 OPERTING ONDITIONS mbient temperature Tamb [ ] -25 to +40 Minimum mechanical durability N 8x25000 operations ltitude [m] <1400 Humidity lass 5K2 Pollution degree PD4
Options (subject to additional costs) Type designation UR 36 81 S R 2 H M 1 D 2 1 1 1 1 1 Description Designation ode Use Rectifier breaker R Interconnection breaker I rc chute installation Opening of arc chute 81/82 on LV connector opposite side 2 Type SI- for arc chute 64 3 Type SI-O for arc chute 64 4 Type S-O for arc chute 64 6 Type SE for arc chute 64 9 Nominal control voltage 64 Vdc F 96 Vdc G 125 Vdc H Holding type Magnetic M Varistor on coil Yes (battery voltage) 1 Direct over-current release (special) 2.0-5.0 k 2.0-8.0 k D (special) 4.0-8.0 k E Indirect release IM5 2 IM6 3 uxiliary contacts 5 change-over switch LV connector type on circuit-breaker Harting Han K 6/36 Manual release Yes 1 Manual closing device Yes 1 Position Indicator Yes 1 Overcurrent release detector Yes 1 ontact wear indicator Yes 1 LV connector type for circuit-breaker Harting Veam Varistor on coil Position indicator Manual closing Over current release detector and ontact wear indicator 7
rc chute installation rc chutes 81 and 82 Opening of the arc chute on the LV connector side. Opening of the arc chute on the LV connector opposite side. rc chute 64 The type SI-O includes an arc chute lifting lever located on the connector opposite side and an additional insulation around the arc chute. The type SI- includes an arc chute lifting lever located on connector side and an additional insulation around the arc chute. The type S-O includes an arc chute lifting lever located on the connector opposite side. The type S- includes an arc chute lifting lever located on connector side. The type SE includes two arc chute locking levers. IM5 & IM6 indirect and manual releases Special direct overcurrent instantaneous release ( and E) M3 manual release The indirect releases enable to shorten the opening time when required by specific application. The choice of the relevant type has to be validated by Sécheron prior quoting. This device can also be manually activated. Opening time ontrol mode - IM 5 4.5-5.5 ms ID-3* - IM 6 12-19 ms Direct battery 77-140 Vdc * Not included in the D circuit-breaker - To be ordered separately SG101001EN_D00-09.08 Sécheron S Rue du Pré-ouvier 25 1217 Meyrin - Geneva H-Switzerland Tel: +41 22 739 41 11 Fax: +41 22 739 48 11 info@secheron.com www.secheron.com This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product, whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser's responsibility to inform himself, no matter what the circumstances, of the product's maintenance conditions and requirements. Sécheron reserves all rights, especially those arising from our "General Delivery onditions". opyright 2008 Sécheron S