GENETIC ALGORITHM BASED OPTIMAL LOAD FREQUENCY CONTROL IN TWO-AREA INTERCONECTED POWER SYSTEMS

Similar documents
Multi-Area Load Frequency Control Using Ip Controller Tuned By Harmony Search

The Effect of Fuzzy Logic Controller on Power System Stability; a Comparison between Fuzzy Logic Gain Scheduling PID and Conventional PID Controller

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

Load frequency control in Single area with traditional Ziegler-Nichols PID Tuning controller

TWO AREA CONTROL OF AGC USING PI & PID CONTROL BY FUZZY LOGIC

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET)

Automatic Generation control of interconnected hydrothermal power plant Using classical and soft computing Technique

Performance Analysis of PSO Optimized Fuzzy PI/PID Controller for a Interconnected Power System

NEURAL NETWORK BASED LOAD FREQUENCY CONTROL FOR RESTRUCTURING POWER INDUSTRY

CHAPTER 5 PSO AND ACO BASED PID CONTROLLER

International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 ISSN

COMPUTATION OF STABILIZING PI/PID CONTROLLER FOR LOAD FREQUENCY CONTROL

Load Frequency Controller Design for Interconnected Electric Power System

Automatic Load Frequency Control of Two Area Power System Using Proportional Integral Derivative Tuning Through Internal Model Control

Decentralized Model Predictive Load Frequency Control of deregulated power systems in tough situations

Load Frequency Control of Three Area System using FOPID Controller

Design of PI Controller using MPRS Method for Automatic Generation Control of Hydropower System

Automatic Generation Control of Two Area using Fuzzy Logic Controller

MATLAB Simulink Based Load Frequency Control Using Conventional Techniques

Stability Control of an Interconnected Power System Using PID Controller

Load Frequency Control of Three Different Area Interconnected Power Station using Pi Controller

MM7 Practical Issues Using PID Controllers

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

CHAPTER 4 LOAD FREQUENCY CONTROL OF INTERCONNECTED HYDRO-THERMAL SYSTEM

CHAPTER 1 INTRODUCTION

Control of Load Frequency of Power System by PID Controller using PSO

CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING. Professor Dae Ryook Yang

AUTOMATIC VOLTAGE REGULATOR AND AUTOMATIC LOAD FREQUENCY CONTROL IN TWO-AREA POWER SYSTEM

Load Frequency Control in an Interconnected Hydro Hydro Power System with Superconducting Magnetic Energy Storage Units

Research Article Multi-objective PID Optimization for Speed Control of an Isolated Steam Turbine using Gentic Algorithm

OPTIMAL LOAD FREQUENCY CONTROL IN SINGLE AREA POWER SYSTEM USING PID CONTROLLER BASED ON BACTERIAL FORAGING & PARTICLE SWARM OPTIMIZATION

AUTOMATIC GENERATION CONTROL OF REHEAT THERMAL GENERATING UNIT THROUGH CONVENTIONAL AND INTELLIGENT TECHNIQUE

A new approach for Tuning of PID Load Frequency Controller of an Interconnected Power System

1. Governor with dynamics: Gg(s)= 1 2. Turbine with dynamics: Gt(s) = 1 3. Load and machine with dynamics: Gp(s) = 1

Automatic load frequency control of multi-area power system using ANN controller and Genetic algorithm

Design of GA Tuned Two-degree Freedom of PID Controller for an Interconnected Three Area Automatic Generation Control System

Modeling and Simulation of Load Frequency Control for Three Area Power System Using Proportional Integral Derivative (PID) Controller

Load Frequency Control of Multi-Area Power Systems Using PI, PID, and Fuzzy Logic Controlling Techniques

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011

Load Frequency Control of Single Area Thermal Power Plant Using Type 1 Fuzzy Logic Controller

Load Frequency Control of Multi Area Hybrid Power System Using Intelligent Controller Based on Fuzzy Logic

Effects of Super Conducting Magnetic Energy Storage Device and Redox Flow Battery in a Genetic Algorithm Based Load Frequency Controller

Different Controller Terms

Optimal PID Tuning for AGC system using Adaptive Tabu Search

PID Tuning Using Genetic Algorithm For DC Motor Positional Control System

COMPARISON OF TUNING METHODS OF PID CONTROLLER USING VARIOUS TUNING TECHNIQUES WITH GENETIC ALGORITHM

Load Frequency Control of Interconnected Hydro-Thermal Power System Using Fuzzy and Conventional PI Controller

ROBUST TECHNIQUE LFC OF TWO-AREA POWER SYSTEM WITH DYNAMIC PERFORMANCE OF COMBINED SMES AND SSSC CONTROL

IMPROVING POWER SYSTEM STABILITY USING REAL-CODED GENETIC ALGORITHM BASED PI CONTROLLER FOR STATCOM

Design of Fractional Order PID Controller for SMIB Power System with UPFC Tuned by Multi-Objectives Genetic Algorithm. Abstract:

A new fuzzy self-tuning PD load frequency controller for micro-hydropower system

TUNING OF PID CONTROLLERS USING PARTICLE SWARM OPTIMIZATION

Determination of the PID Controller Parameters by Modified Genetic Algorithm for Improved Performance

A Novel PSS Design for Single Machine Infinite Bus System Based on Artificial Bee Colony

MULTI STAGE FUZZY PID LOAD FREQUENCY CONTROLLER IN A RESTRUCTURED POWER SYSTEM

Load Frequency Control for Two Area Deregulated Power System Using ANN Control

Robust controller design for LFO damping

Design of Fractional Order Proportionalintegrator-derivative. Loop of Permanent Magnet Synchronous Motor

QFT based Robust Load Frequency Controller Design for Multi-Area Power System

LFC in hydro thermal System Using Conventional and Fuzzy Logic Controller

F. Greg Shinskey. "PID Control." Copyright 2000 CRC Press LLC. <

Modeling and Control of Liquid Level Non-linear Interacting and Non-interacting System

LOAD FREQUENCY CONTROL FOR TWO AREA POWER SYSTEM USING DIFFERENT CONTROLLERS

AUTOMATIC GENERATION CONTROL OF INTERCONNECTED POWER SYSTEM WITH THE DIVERSE SOURCES USING SUPERCONDUCTING MAGNETIC ENERGY STORAGE (SMES)

AGC in Five Area Interconnected Power System of Thermal Generating Unit Through Fuzzy Controller

An intelligent fuzzy logic controller applied to multi-area load frequency control

The Open Automation and Control Systems Journal, 2015, 7, Application of Fuzzy PID Control in the Level Process Control

Position Control of DC Motor by Compensating Strategies

Multi Machine PSS Design by using Meta Heuristic Optimization Techniques

Transient Stability Improvement Of LFC And AVR Using Bacteria Foraging Optimization Algorithm

Tuning of PID Controller in Multi Area Interconnected Power System Using Particle Swarm Optimization

UNIT-II REAL POWER FREQUENCY CONTROL. 1. What is the major control loops used in large generators?

PID Controller Optimization By Soft Computing Techniques-A Review

CHAPTER 4 PID CONTROLLER BASED SPEED CONTROL OF THREE PHASE INDUCTION MOTOR

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

COMPARATIVE PERFORMANCE OF WIND ENERGY CONVERSION SYSTEM (WECS) WITH PI CONTROLLER USING HEURISTIC OPTIMIZATION ALGORITHMS

Digital Simulation and Analysis of Sliding Mode Controller for DC-DC Converter using Simulink

A Fast PID Tuning Algorithm for Feed Drive Servo Loop

LOAD FREQUENCY CONTROL FOR A TWO-AREA INTERCONNECTED POWER SYSTEM BY USING SLIDING MODE CONTROLLER

Analysis of Transient Response for Coupled Tank System via Conventional and Particle Swarm Optimization (PSO) Techniques

Load Frequency Control of Single Area Power System Using JAYA Algorithm

Design Of PID Controller In Automatic Voltage Regulator (AVR) System Using PSO Technique

Automatic Generation Control of Three Area Power Systems Using Ann Controllers

STABILITY IMPROVEMENT OF POWER SYSTEM BY USING PSS WITH PID AVR CONTROLLER IN THE HIGH DAM POWER STATION ASWAN EGYPT

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Design of Self-Tuning Fuzzy PI controller in LABVIEW for Control of a Real Time Process

Experiment 9. PID Controller

CHAPTER 3 DESIGN OF MULTIVARIABLE CONTROLLERS FOR THE IDEAL CSTR USING CONVENTIONAL TECHNIQUES

Application Of Power System Stabilizer At Serir Power Plant

Load frequency control in two area multi units Interconnected Power System using Multi objective Genetic Algorithm

Rawalpindi, Pakistan. Ayesha Saddiqa: Lab Engineer & MSc Scholar, Faculty of Electrical

Non Linear Tank Level Control using LabVIEW Jagatis Kumaar B 1 Vinoth K 2 Vivek Vijayan C 3 P Aravind 4

Frequency Response Characteristic Survey Training Document

ADVANCED DC-DC CONVERTER CONTROLLED SPEED REGULATION OF INDUCTION MOTOR USING PI CONTROLLER

Cohen-coon PID Tuning Method; A Better Option to Ziegler Nichols-PID Tuning Method

Simulation and Analysis of Cascaded PID Controller Design for Boiler Pressure Control System

Load frequency control of interconnected system

Digital Control of MS-150 Modular Position Servo System

SSRG International Journal of Electrical and Electronics Engineering ( SSRG IJEEE ) Volume 3 Issue 1 January 2016

DC Motor Speed Control: A Case between PID Controller and Fuzzy Logic Controller

Transcription:

ransaction on Power system optimization ISSN: 9-87 Online Publication, June www.pcoglobal.com/gjto.htm CG-P4 /GJO GENEIC ALGORIHM BASED OPIMAL LOAD FREQUENCY CONROL IN WO-AREA INERCONECED POWER SYSEMS Armin Ebrahimi Milani, Babak Mozafari Young Researchers club, Science and Research Branch, Islamic Azad University, ehran, Iran Department of Electrical Engineering, Science and Research Branch, Islamic Azad University, ehran, Iran. Email: a.milani@srbiau.ac.ir, mozafari_babak@nri.ac.ir Received August, Revised October, Accepted January Abstract Load frequency control in power systems introduces as one of the most important items in order to supply reliable electric power with good quality. he goals of the Load Frequency Control (LFC) are to maintain zero steady state errors in a two area interconnected power system. o achieve this goal a fast controller with having no steady-state error will be necessary to be included in power systems. In this paper a new genetic algorithm based method is presented to obtain optimal gains of this controller included in two-area interconnected power system. Simulation results in comparison with correspondence methods confirm the efficiency of proposed method through fastdamping steady-state deviations in power and frequency with presence of step load disturbance. Keywords: wo-area interconnected power systems, Load Frequency Control, Optimal controller design, Genetic Algorithm.. Introduction One of the principle aspect of Automatic Generation Control (AGC) of power system is the maintains of frequency and power change over the tie-lines at their scheduled values and due to the fact that modern power systems with industrial and commercial loads need to operate at constant frequency with reliable power, the load frequency control (LFC) of an interconnected power system is being improved over the last few years. In LFC problem, each area has its own generator or generators and it is responsible for its own load and scheduled interchanges with neighboring areas. he tie-lines are utilities for contracted energy exchange between areas and provide inter-area support in abnormal conditions. Area load changes and abnormal conditions lead to mismatches in frequency and scheduled Copyright @ /gjto power interchanges between areas. hese mismatches have to be corrected by LFC, which is defined as the regulation of the power output of generators within a prescribed area []. herefore, the LFC task is very important in interconnected power systems. Over the past decades, many techniques have been developed for the LFC problem. A number of state feedback controllers based on linear optimal control theory, robust and conventional adaptive controller have been proposed to achieve better performance [,3,4 and 5] state adaptive controllers [6] involve large computational burden and time. Also, Most of proposed techniques were based on the classical proportional and integral (PI) or proportional, integral and derivative (PID) controllers. Its use is not only for their simplicities, but also due to its success in a large number of industrial applications. In Classical methods, such as Ziegler-Nichols and Cohen-Coon, these controllers are tuned based on trial-error approaches and, therefore, have not good performance. Meanwhile, these controllers may be unsuitable in some operating conditions due to the complexity of the power systems such as nonlinear load characteristics and variable operating points. Due to these facts using a flexible algorithm to obtain optimal gains in designing control feedbacks will be an important matter. Also, because there should be a sudden feedback to restore the frequency to its desire point that had before, a fast response should be considered as the main goal. In this paper genetic algorithm is used to solve this non-liner optimization problem which will cause a fast response to two-area interconnected power system load frequency controllers with determining optimal gains in LFC feedbacks.. Modeling of a two-area interconnected power system A two-area system consists of two single areas connected through a power line called the tie-line. Each area feeds its user pool and the tie-line allows electric power to flow between areas. Since both areas are tied together, a load agitation in one area affects the output frequencies of both areas as well as the power flow on the tie-line.

7 Genetic Algorithm Based Optimal Load Frequency Control in wo-area Interconnected Power Systems he frequency control is accomplished by two different control actions in interconnected two area power systems: he primary speed control and supplementary or secondary speed control actions. he primary speed control makes the initial vulgar readjustment of the frequency. By its actions the various generators in the control area track a load variation and share it in proportion to their capacities. he speed of response is limited only by the natural time lags of the turbine and the system itself. Depending upon the turbine type the primary loop typically responds within to seconds. he supplementary speed control takes over the fine adjustment of the frequency by resetting the frequency error to zero through an integral action. he control system of each area needs information about the transient situation of both areas in order to brings the local frequency back to its steady state value. Information about the other areas found in the output frequency fluctuation of that area and in the tie-line power fluctuation. herefore, the tie-line power is sensed and the resulting tie-line power signal is feed back into both areas by determined gains. A two-area interconnected power system is shown in figure. his kind of system can be represented for the load frequency control in terms of its components like governor system, turbine, generator, load and tie line between two-area, where f and f are the frequency deviations in area and area respectively. Also P D and PD represent sudden load demand increments: In this block diagram parameters of power system are H, D, R which indicates inertia constant, load sensitivity to frequency factor, regulator slope respectively. Meanwhile, transfer function for turbine and governor is assumed as follow: F F urbine Governor = + S. + S. = () Where: : urbine ime constant G : Governor ime constant G With these base definitions it is convenient to obtain the dynamic model in state variable form from the transfer function model. ransfer function for system illustrated in figure can be written as: x& ( = Ax( + Bu( + Fd( y( = Cx( Where: () PC X PR P F x = P P C X PR P F u = d = G tie G [ u u ] [ P P ] d d and A, B, C and F are the system matrix, input, output and disturbance distribution matrices, respectively, where x(, u( and d( are the state, control and load changes disturbance vectors, respectively. hese matrix and vectors are obtained using the nominal parameters of the system. A step load of P.U has been considered as a disturbance in the two-area interconnected power system. 3. Application of genetic algorithm to solve LFC problem Genetic algorithm (GA) is one of the optimization methods based on heredity and evolution. his algorithm is one of the statistic searching methods and as it mentioned before due to the fact that load frequency control involves with inconstant loads and we face to a non-liner problem, real coded GA can be considered as an appropriate method for reaching optimal gains with fast response to system Considering y as output vector we can assume that: y = [ ACE ACE ] (4) Where ACE i is Area Control Error signal due to step type load disturbance can be calculated as: ACEi = Ptie, i + Bi Fi (5) Note that in this equation, B i is the frequency bias, f i is the frequency deviation and P tie,i is the change in tie-line power for the i-th area. In designing the controller, cost function can be assumed as minimization of Integral of Absolute Error (IAE), Integral of Square Error(ISE) or Integral of ime Multiplied Square Error (ISE) for step response of load deviation: (3) Copyright @ /gjto

Genetic Algorithm Based Optimal Load Frequency Control in wo-area Interconnected Power Systems 8 Figure : A two-area interconnected power system block-diagram. IAE = e( ISE = e ISE = te ( ( Practical cases show that IAE and ISE functions will cause more minimization in overshot than ISE and due to the fact that ISE will cause fast response with shorter settling time we consider this cost function as our objective function in this essay: F Cost = t ACE i., For i =, (6) In GA algorithm -considering the cost function- a fitness function is considered for each string of values, so that in the next stage the initial population will be chosen in a way that we can use the probability of roulette for this choice. he suggested fitness function for creating the initial population can be written as: F = Fitness (7) + F Cost Consequently the roulette is divided in according to the quantities of fitness function of each real coded string and with each circulation one string for creating a new generation is selected. hen the act of creating a new generation is done by the genetic operators such as cross-over and mutation. Afterward the fitness quantity for each one of the newly created strings is calculated and strings with more fitness are chosen as the next generation. Absolutely the strings with high fitness values are more probable to be transferred to the next generation. his process will be continued until the best answer in successive repetitions has minimum variance to unit (So J will have minimum variance to zero) and the best solution does not change for a prespecified interval of generations. he resulted string shows the information of the final optimized gains. Following flow chart illustrates basic steps in real coded genetic algorithm used for load frequency control. Meanwhile, real coded GA parameters are given in table. 4. Schematic results in implementation of suggested method For examining the efficiency and improvement, the presented model is developed in MALAB, on a Pentium-4 PC (.86GHz & GB RAM), and is performed on a sample two-area interconnected power system with system parameters included in table and a step load disturbance in one of these areas. Changes in frequencies after load deviation are illustrated on figure 3 for two areas when there is no LFC in system. As it is clear system can not compensate frequency deviation by its self. Copyright @ /gjto

9 Genetic Algorithm Based Optimal Load Frequency Control in wo-area Interconnected Power Systems Figure 4 shows frequency deviation for area with GA based optimized gain and without optimization (with random gain selection). Figure 4: Frequency deviation in area with optimized gains and without optimization As it was clear proposed method caused faster response with minimum agitation where without optimization frequency response damps in a longer time with inappropriate response to load variations. Figure 5 depicts these results much more clear for second area. Figure : Flowchart of basic real coded genetic algorithm able : Main GA parameters used in this paper Option Number / ype Number of variables otal number of generation 3 Population size Cross over Scattered Cross over probability.4 Mutation probability. Fitness scaling Rank Elite count able : Sample two-area interconnected power system parameters Parameter Area Area.3.3 G.8.8 D.8.4 H 5 R.5.5 Figure 5: Frequency deviation in area with optimized gains and without optimization Moreover, changes in power of tie-line before and after optimal AFC are shown in figure 6. With presence of optimal controller error in power transfers between two areas will be zero after some seconds where without AFC control we will have error in steady-state response. Figure 6: ie line power deviation before/after optimization Figure 3: Frequency deviation in area & without LFC Copyright @ /gjto As a comparison to other correspondence papers the suggested method shows less agitation in frequency deviation whit much more faster response. Figure 7 campers suggested method with result of

Copyright @ /gjto Genetic Algorithm Based Optimal Load Frequency Control in wo-area Interconnected Power Systems reference [7] for frequency deviation in area with same system parameters. Figure 7: Comparison between Frequency deviation in area with proposed OLFC and proposed method in ref.[7] 5. Conclusion A new method for Optimal Load Frequency Control (OLFC) in interconnected power systems has been discussed in this paper which a real coded Genetic Algorithm used to solve this nonliner problem. Also suggested method implemented on a simple two-area interconnected system and the results showed reasonable fast response with no steady-state error to a step load disturbance. his is while, the efficiency and improvement of suggested method examined with comparing its results whit correspondence methods for LFC. his investigation can be extended for optimizing the gains including penalty factors in fitness function for future investigations. hese penalty factors can indicate some extra constraints such as governor saturation and can be model by means of Maximum Speed and Maximum Rotation. References [] J. Kumar, Kah-Hoe Ng, G. Sheble, AGC simulator for price-based operation, Part I: A model, IEEE ransactions on Power Systems, Volume, Issue, May 997, Page(s):57 53. [] M. Aldeen and H.rih,, load frequency control of interconnected power systems via constrained feedback control schemes, Comput. Elect. Eng., Issue, 994, page(s): 7-88. [3] C. Pan, C.. C.M. Liaw, An Adaptive Controller for Power System Load-Frequency Control, IEEE Power Engineering Review, Volume 9, Issue, Feb. 989, Page(s):45 46. [4] M. Zribi, M. Al-Rashed and M. Alrifai, adaptive decentralized load frequency control of multi-area power systems, Elect. Power Energy Syst., 5, page(s):55-583. [5] H. Beyran and. Hiyama, Robust decentralized PI based LFC design for time delay power systems, Energy Conversion Manage., 8, page(s):93-4. [6] M. K. Kazemi and M. B. Menhaj, Decentraized robust adaptive load frequency control using interaction estimation, Elect. Eng., 3, page(s): 9-7. [7] S. Ramesh and A. Krishnan, Modified Genetic Algorithm Based Load Frequency Controller for Interconnected Power Systems, International Journal of Electrical and Power Engineering, page(s): 6-3, 9. [8]. Inoue and H. Amano, A hermal Power Plant Model for Dynamic Simulation of Load Frequency Control, Power Systems Conference and Exposition 6 (PSCE'6), IEEE, Oct. 6, Page(s):44 447. [9] A. Bensenouci and A.M. Abdel Ghany, Step-Wise Optimum Adaptive Variable-Structure Load-Frequency Control Design Using Simulated Annealing, IEEE International Symposium on Industrial Electronics June 7, page(s):38-33. [] K. Vrdoljak, N. Peric, M. Mehmedovic, Optimal parameters for sliding mode based load-frequency control in power systems, International Workshop on Variable Structure Systems (VSS'8), June 8 Page(s):33 336.